AKD2G-S Installation Manual, Safety 1 | 8 Electrical Installation
AC supply, group of drives, line fusing
F1, F2, F3: depends on sum of current and cabinet requirements.
Filters for special EMC requirements only (
FN1, FN2, FN3 maximum rating: fuse size for group installation is limited to 30 A max.
FN1, FN2, FN3 rating should be 1.25 * sum current.
Group sum current
FN1, FN2, FN3:
Ampere rating
Example class J
Eaton
Example class J
Ferraz Shawmut
6 A to 30 A
30 A (Time-Delay)
LPJ30SP/DFJ30
AJT30/HJ30
AC supply, single drives, automatic circuit breakers
F1, F2, F3: depends on sum of current and cabinet requirements.
Filters for special EMC requirements only (
FN maximum rating: 30 A
FN recommended rating and regional approvals see table below:
Drive Model
Ampere
rating
SCCR
rating
Example UL
Eaton or ABB
Example CE
Siemens
AKD2G-Sxx-6V
15 A
35 kA
SU203M-K30
3VA51954EC310
72
Kollmorgen | kdn.kollmorgen.com | July 2020