FUTURE® S AIR HANDLING UNIT
OPERATION AND MAINTENANCE
INSTRUCTIONS
15 December 2020
Ver 1.7 (We reserve the right to changes without prior notice)
29
Figure 7.4.4.3: Removing the belt connection for shortening the belt.
7.4.5 Rotor removal
WARNING
Removing the rotor requires disconnecting the electrical cables. Electrical installations
must be carried out by a qualified and authorised electrician only and general and
section-specific safety instructions must be observed throughout the procedure.
The rotor package is designed in such a way that it can be removed from unit casing, for example, for the
duration of maintenance. The rotor package is attached (depending on the model) with screws.
Removal instructions:
•
Remove the rotor mounting screws, 3 pcs on the top and 3 pcs on the bottom per side
•
Disconnect the power from the rotor control unit. The connections are located on the side of the
access door, at the bottom.
•
Carefully pull the rotor out of the casing, taking care not to damage the rotor.
•
Carefully push the rotor back to its place and attach it with screws.
•
Ensure the rotor’s tightness on the air supply and extract sides, as well as on the back.
•
Connect the power in accordance with the connection diagrams of the unit.
•
Close the access door.