TP-5660 11/98
Operation 13
2.3.2
Programmed Transition Switch,
400--3000 Amps
Manual Operation Procedure
1. Prevent the generator set, which provides the
emergency power source to the transfer switch,
from starting by moving the generator set master
switch to the OFF position; disconnecting power to
the generator engine start battery charger, if
installed; and disconnecting all generator engine
start batteries, negative (--) leads first.
2. Disconnect
BOTH
the normal and emergency
power sources by opening upstream circuit
breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
4. Set the disconnect switch (DS) to the INHIBIT
position to prevent the controller from energizing the
solenoid(s). See Figure 2-2.
AUTO INHIBIT
3
2
4
LOCK
LOCK
NORMAL
1
LOCK
LOCK
EMERGENCY
5660202
1. Normal switch lever, normal source shown connected to load
2. Emergency
switch
lever,
emergency
source
shown
disconnected from load
3. Disconnect switch, INHIBIT position shown
4. Manual operating handle, typical
Figure 2-2. Manual Operation, Programmed
Transition Switch 400--3000 Amps
5. Attach the manual operator handle to the normal
switch lever and move it
up
to the normal position to
manually connect the load to the normal source
and move it
down
to disconnect. The switch should
operate smoothly in both directions without
binding.
6. Attach the manual operator handle to the
emergency switch lever. Move the handle
down
to
the emergency position to manually connect the
load to the emergency source and move it
up
to
disconnect. The switch should operate smoothly in
both directions without binding.
NOTE
A mechanical interlock prevents simultaneous
emergency and normal source connection to the
load. Both sources can be manually disconnected
from the load simultaneously.
7. Manually connect the load to the normal source for
automatic operation.
8. Remove and return the manual operator handle to
the holder provided.
9. Move the disconnect switch (DS) to the AUTO
position for automatic operation.
10. Close and lock the transfer switch enclosure door.
11. Reconnect power supplies to the transfer switch.
NOTE
When initially applying power to the transfer switch,
the engine start contacts remain closed signalling
the generator to run until the ATS’s Time Delay
Engine Cooldown (TDEC), if equipped, ends.
12. Reconnect generator engine start battery cables,
negative (--) leads last; reconnect power to the
generator engine start battery charger, if installed;
and move the generator set master switch to the
AUTO (automatic) position. The generator may
start and run for a while (see NOTE above).
Содержание ZCS series
Страница 16: ...TP 5660 11 98 8 Specifications Notes...
Страница 30: ...TP 5660 11 98 22 Diagrams and Drawings Notes...
Страница 31: ...TP 5660 11 98 Diagrams and Drawings 23 Enclosure Dimensions Drawing 40 260 Amp NEMA Type 1 and Type 3R ADV 6180...
Страница 32: ...24 Diagrams and Drawings TP 5660 11 98 Enclosure Dimensions Drawing 400 Amp NEMA Type 1 and Type 3R ADV 5934 C...
Страница 34: ...26 Diagrams and Drawings TP 5660 11 98 Enclosure Dimensions Drawing 600 1200 Amp NEMA Type 12 ADV 5936B B...
Страница 35: ...TP 5660 11 98 Diagrams and Drawings 27 Enclosure Dimensions Drawing 1600 2000 Amp NEMA Type 1 ADV 5941 E...
Страница 38: ...30 Diagrams and Drawings TP 5660 11 98 Enclosure Dimensions Drawing 2500 3000 Amp NEMA Type 1 ADV 6242 B...
Страница 45: ...TP 5660 11 98 Diagrams and Drawings 37 Schematic Diagram S340 Logic 600 1200 Amp 321096 C...
Страница 46: ...38 Scheduled Maintenance TP 5660 11 98 Schematic Diagram S340 Logic 1600 3000 Amp 321097 A...
Страница 52: ...44 Scheduled Maintenance TP 5660 11 98 Schematic Diagram S340 Logic 400 Amp with Programmed Transition 321098 B...
Страница 54: ...46 Diagrams and Drawings TP 5660 11 98 Schematic Diagram M340 Logic 600 1200 Amp 321287 C...
Страница 55: ...TP 5660 11 98 Diagrams and Drawings 47 Schematic Diagram M340 Logic 1600 3000 Amp 321301 B...
Страница 61: ...TP 5660 11 98 Diagrams and Drawings 53 Schematic Diagram M340 Logic 400 Amp with Programmed Transition 321300 B...
Страница 70: ...TP 5660 11 98 62 Installation Notes...