Operation 11
2.3 Manual Operation
To test or troubleshoot the transfer switch, or when the
controller fails in an emergency situation, manually
operate the power switching device as described below.
Accidental starting.
Can cause severe injury or death.
Disconnect battery cables before
working on generator set. (Remove
negative
(--)
lead
first
when
disconnecting battery.
Reconnect
negative
(--)
lead
last
when
reconnecting battery.)
WARNING
Disabling the generator set. Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: 1) Move the generator set master switch to the
OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--) lead first. Reconnect
negative (--) lead last when reconnecting battery. Follow these
precautions to prevent starting of generator set by an
automatic transfer switch, remote start/stop switch, or engine
start command from a remote computer.
Hazardous voltage.
Can cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(under 600 Volt)
WARNING
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(600 Volt and above)
DANGER
Hazardous voltage.
Can cause severe injury or death.
Disconnect power sources before
servicing.
Install barrier after
adjustments,
maintenance,
or
service.
(under 600 Volt)
WARNING
Hazardous voltage.
Will cause severe injury or death.
Disconnect power sources before
servicing.
Install barrier after
adjustments,
maintenance,
or
servicing.
(600 Volt and above)
DANGER
Servicing the transfer switch. Hazardous voltage can
cause severe injury or death.
Deenergize all power sources
before servicing. Open main circuit breakers of all power
sources to the transfer switch and disable all generator sets as
follows: 1) Move all generator set master controller switches
to the OFF position. 2) Disconnect power to all battery
chargers. 3) Disconnect all battery cables, negative (--) leads
first. Reconnect negative (--) leads last when reconnecting
battery cables after servicing. Follow these precautions to
prevent starting of generator sets by an automatic transfer
switch, remote start/stop switch, or engine start command
from a remote computer.
NOTICE
Improper operator handle usage!
Use the manual operator
handle provided on the transfer switch for maintenance
purposes only. Return the transfer switch to the normal
position. Remove manual operator handle, if used, and store it
on the transfer switch in the place provided when service is
completed.
NOTE
A contactor in normal and serviceable condition
transfers smoothly without binding when operated
manually. Do not place the transfer switch into service if
the contactor does not manually operate smoothly
without binding; contact an authorized service center to
service the contactor.
Содержание ZCS series
Страница 16: ...TP 5660 11 98 8 Specifications Notes...
Страница 30: ...TP 5660 11 98 22 Diagrams and Drawings Notes...
Страница 31: ...TP 5660 11 98 Diagrams and Drawings 23 Enclosure Dimensions Drawing 40 260 Amp NEMA Type 1 and Type 3R ADV 6180...
Страница 32: ...24 Diagrams and Drawings TP 5660 11 98 Enclosure Dimensions Drawing 400 Amp NEMA Type 1 and Type 3R ADV 5934 C...
Страница 34: ...26 Diagrams and Drawings TP 5660 11 98 Enclosure Dimensions Drawing 600 1200 Amp NEMA Type 12 ADV 5936B B...
Страница 35: ...TP 5660 11 98 Diagrams and Drawings 27 Enclosure Dimensions Drawing 1600 2000 Amp NEMA Type 1 ADV 5941 E...
Страница 38: ...30 Diagrams and Drawings TP 5660 11 98 Enclosure Dimensions Drawing 2500 3000 Amp NEMA Type 1 ADV 6242 B...
Страница 45: ...TP 5660 11 98 Diagrams and Drawings 37 Schematic Diagram S340 Logic 600 1200 Amp 321096 C...
Страница 46: ...38 Scheduled Maintenance TP 5660 11 98 Schematic Diagram S340 Logic 1600 3000 Amp 321097 A...
Страница 52: ...44 Scheduled Maintenance TP 5660 11 98 Schematic Diagram S340 Logic 400 Amp with Programmed Transition 321098 B...
Страница 54: ...46 Diagrams and Drawings TP 5660 11 98 Schematic Diagram M340 Logic 600 1200 Amp 321287 C...
Страница 55: ...TP 5660 11 98 Diagrams and Drawings 47 Schematic Diagram M340 Logic 1600 3000 Amp 321301 B...
Страница 61: ...TP 5660 11 98 Diagrams and Drawings 53 Schematic Diagram M340 Logic 400 Amp with Programmed Transition 321300 B...
Страница 70: ...TP 5660 11 98 62 Installation Notes...