3: Installation
3-8
UPS413-01-00 Kohler PW 6000 (60-500kVA) User Manual 25 June 2012
3.6.3 Power cable terminations
The table below gives details of the cable termination sizes applicable to the various models across the
Kohler PW 6000 range. Figure 3.5 illustrates the terminal block/busbar layouts.
All the input and output power cables are routed through the bottom of the UPS cabinet below the power
connectors/busbars.
See the following assembly diagrams for details:
Figure 3.7 - 60kVA-100 kVA Module details
Figure 3.8 - 120kVA-200 kVA Module details
Figure 3.9 - 250kVA-300 kVA Module details
Figure 3.10 - 400kVA-500kVA Module details
Mains Supply
(3+N+PE)
Bypass Supply
(3+N)
Output Load
(3+N+PE)
Battery
(+ / N / – / PE)
Max admissible
cable section
(mm²)
Tightening
Torque
(Nm)
60kVA
4 x 35 mm
2
+ PE M8
4 x 35 mm
2
4 x 35 mm
2
+ PE M8
4 x M8
35
3.5
80kVA
4 x 50 mm
2
+ PE M8
4 x 50 mm
2
4 x 50 mm
2
+ PE M8
4 x M8
50
5
100kVA
4 x 70 mm
2
+ PE M8
4 x 70 mm
2
4 x 70 mm
2
+ PE M8
4 x M8
95
8
120kVA
5 x M10
4 x M10
5 x M10
4 x M10
185
Max. 50
160kVA
5 x M10
4 x M10
5 x M10
4 x M10
185
Max. 50
200kVA
5 x M10
4 x M10
5 x M10
4 x M10
240
Max. 50
250kVA
5 x M10
4 x M10
5 x M10
4 x M10
240
Max. 50
300kVA
5 x M10
4 x M10
5 x M10
4 x M10
240
Max. 50
400kVA
3x (5 x M12)
3x (4 x M12)
3x (5 x M12)
3x (4 x M12)
240
Max 84
500kVA
3x (5 x M12)
3x (4 x M12)
3x (5 x M12)
3x (4 x M12)
240
Max 84
Содержание PW 6000
Страница 1: ...User Manual Pioneering solutions for total power protection Kohler PW 6000 ...
Страница 2: ......
Страница 8: ...1 Safety 1 2 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 18: ...2 Description 2 10 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 52: ...4 Operation 4 14 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 58: ...6 Troubleshooting 6 4 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 74: ...8 Specifications 8 8 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...