UPS413-01-00 Kohler PW 6000 (60-500kVA) User Manual 25 June 2012
3-3
3: Installation
3.5
Planning the installation (site considerations)
A certain amount of pre-planning will help ensure a smooth and trouble-free installation of the UPS system.
The following guidelines should be taken into account when planning a suitable UPS location and operating
environment.
1.
The route to the installation location must allow the equipment to be transported in an upright position.
2.
The floor at the proposed installation site and en-route from the off-loading point must be able to safely
take the weight of the UPS and battery equipment plus fork lift during transit.
3.
Locations with high ambient temperature, moisture or humidity must be avoided.
a)
The installation site humidity should be <90% non-condensing.
b)
The prescribed ambient temperature is +15°C to +25°C. An ambient temperature of 20°C is
recommended to achieve a long battery life.
c)
Any requested cooling air flow must be available. The air entering the UPS must not 40°C.
d)
The air conditioning system must be able to provide a sufficient amount of cooling air to keep the
room within the prescribed temperature range.
4.
The following environmental conditions should also be considered:
a)
Fire protection standards must be respected.
b)
The location must be free of dust and corrosive/explosive gases.
c)
The location must be vibration free.
d)
If the UPS is located in bayed enclosures, partition walls must be installed.
e)
The available space must permit the minimum cabinet clearances shown below.
3.5.1 Clearances
Figure 3.1 UPS Cabinet access space recommendations
All cables enter the UPS via the bottom of the cabinet therefore no service/installation access is required from
the rear or sides of the cabinets.
> 200mm
>
10
00mm
> 900
mm
400/500kVA UPS
400/500kVA UPS
60-300kVA
60-300kVA
60-300kVA
> 200mm
400/500kVA UPS
400/500kVA UPS
60-300kVA
60-300kVA
60-300kVA
>
90
0mm
>
1
000
mm
50-100mm
50-100mm
Содержание PW 6000
Страница 1: ...User Manual Pioneering solutions for total power protection Kohler PW 6000 ...
Страница 2: ......
Страница 8: ...1 Safety 1 2 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 18: ...2 Description 2 10 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 52: ...4 Operation 4 14 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 58: ...6 Troubleshooting 6 4 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Страница 74: ...8 Specifications 8 8 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...