TT-1625 7/17
25
6.6
P39, 3-pin isolated/non-isolated jumper
. See
Figure 39 for P39 connections. See Figure 20 for
the location of P39 on the RSA III.
Insulated
Isolated RS-485 (default setting)
Non-isolated Non-isolated RS-485
Figure 39
P39 Isolation Jumper Connections
When using the
DEC 3+ controller
, choose the
isolated connection on the master RSA III where
the RS-485 cable shield and ground leads are
connected at the master RSA III, but are not
grounded to the RSA III circuit board.
Note:
When using the
DEC 550 and DEC 6000
controllers
, choose the non-isolated
connection on the master RSA III where
the RS-485 cable shield and ground leads
are connected at the master RSA III and
grounded to the RSA III circuit board. The
non-isolated connection ties the ground
wire and shield (both of which are
connected to the GND terminal of terminal
block P27) to the same ground as the
RSA III circuit board.
When the slave RSA III is not the only item on the
network, use the isolated connection where the
RS-485 cable shield and ground leads are
connected but not grounded to the RSA III circuit
board.
Note:
When the slave RSA III is the only item on
the network (connects only to a Modbus
r
to
Ethernet
converter),
use
the
non-isolated
connection
where
the
RS-485 cable shield and ground leads are
connected and grounded to RSA III circuit
board.
6.7
P40, 6-pin common fault output and horn dry
contacts.
These dry contact relays energize
when the alarm horn sounds and activate
user-supplied devices. See Figure 40 for P40
connections. See Figure 20 for the location of
P40 on the RSA III. The dry contacts are rated at
220 VAC @ 0.8 amps and 30 VDC @ 2 amps.
TT-1625
1
6
P40 Output Connections
P40-1
Common fault relay normally closed
P40-2
Common fault relay common
P40-3
Common fault relay normally open
P40-4
Horn relay normally closed
P40-5
Horn relay common
P40-6
Horn relay normally open
Figure 40
P40 Common Fault Output and Alarm
Horn Dry Contacts
Содержание APM802
Страница 14: ...14 TT 1625 7 17 Figure 15 Remote Serial Annunciator Dimension Print ADV 8661A...
Страница 15: ...TT 1625 7 17 15 Figure 16 Remote Serial Annunciator Dimension Print ADV 8661B modified...
Страница 31: ...TT 1625 7 17 31 Figure 53 RSA III Generator Set and ATS Setup on SiteTecht Sample Screen...
Страница 36: ...36 TT 1625 7 17 Figure 57 RSA III Wiring Diagram GM62554A J...
Страница 37: ...TT 1625 7 17 37 Figure 58 RSA III Wiring Diagram GM62554B J...
Страница 38: ...38 TT 1625 7 17 Figure 59 RSA III Wiring Diagram GM62554C J...
Страница 39: ...TT 1625 7 17 39 Figure 60 RSA III Wiring Diagram GM62554D J...
Страница 40: ...40 TT 1625 7 17 Figure 61 RSA III Wiring Diagram GM62554E J...
Страница 41: ...TT 1625 7 17 41 Figure 62 RSA III Wiring Diagram GM62554F J...
Страница 42: ...42 TT 1625 7 17 Figure 63 RSA III Wiring Diagram GM62554G J...
Страница 43: ...TT 1625 7 17 43 Figure 64 RSA III Interconnection Diagram ADV 6990A H...
Страница 44: ...44 TT 1625 7 17 Figure 65 RSA III Interconnection Diagram ADV 6990B H...
Страница 46: ...46 TT 1625 7 17 Notes...
Страница 47: ...TT 1625 7 17 47 Notes...