TP-6844 1/13
Section 6 Disassembly/Reassembly
85
Section 6 Disassembly/Reassembly
This section provides instructions for the disassembly
and reassembly of the generator set alternator. Before
beginning the generator disassembly or reassembly
procedure, carefully read all safety precautions at the
beginning of this manual.
The engine and generator set may use both American
Standard and metric hardware. Use the correct size
tools to prevent rounding of the bolt heads and nuts.
Disabling the generator set. Accidental starting can
cause severe injury or death.
Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set
off/reset button to shut down the generator set. (2)
Disconnect the power to the battery charger, if equipped. (3)
Remove the battery cables, negative (–) lead first.
Reconnect the negative (–) lead last when reconnecting the
battery. Follow these precautions to prevent the starting of
the generator set by the remote start/stop switch.
6.1 Initial Steps
Perform the following steps before disassembling the
generator set.
1. Disconnect power to the generator set.
2. Shut off the fuel supply. Disconnect the fuel
system if necessary to tilt the generator set.
Ventilate the area to clear fumes.
3. Allow the generator set and engine to cool.
4. Verify that any hoists or lifting devices used in the
disassembly or reassembly procedure are rated
for the weight of the generator set, which is
approximately 190 kg (420 lb.).
6.2 Disassembly
The disassembly procedure explains how to
disassemble the generator set enclosure and other
parts in order to access the alternator for service. The
procedure provides important information to minimize
disassembly time and indicates where special
configurations exist which may require taking notes.
Remove Enclosure
Remove the generator set enclosure as described in
the following steps. See Figure 6-1.
1. Open the front service door.
2. Press the OFF button on the controller.
3. Lift off roof and slide toward exhaust end to
disengage tabs from slots. Remove ground strap
if necessary.
WARNING
!
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (–) lead first
when disconnecting the battery.
Reconnect the negative (–) lead last
when reconnecting the battery.
DANGER
!
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
WARNING
!
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set
until it cools.
Содержание 6VSG
Страница 1: ...Service TP 6844 1 13a DC Generator Sets Models 6VSG 24VDC 36VDC 48VDC Controller VSC...
Страница 12: ...12 Service Assistance TP 6844 1 13 Notes...
Страница 26: ...26 Section 2 Scheduled Maintenance TP 6844 1 13 Notes...
Страница 50: ...50 Section 3 Controller TP 6844 1 13 Notes...
Страница 84: ...84 Section 5 Component Testing and Adjustment TP 6844 1 13 Notes...
Страница 90: ...90 Section 6 Disassembly Reassembly TP 6844 1 13 Notes...
Страница 92: ...92 Section 7 Drawings and Diagrams TP 6844 1 13 Figure 7 2 Figure 7 2 Dimension Drawing ADV 8060 Sheet 1...
Страница 93: ...TP 6844 1 13 Section 7 Drawings and Diagrams 93 Figure 7 3 Figure 7 3 Dimension Drawing ADV 8060 Sheet 2...
Страница 94: ...94 Section 7 Drawings and Diagrams TP 6844 1 13 Figure 7 4 Figure 7 4 Dimension Drawing ADV 8060 Sheet 3...
Страница 96: ...96 Section 7 Drawings and Diagrams TP 6844 1 13 Figure 7 6 Figure 7 6 Schematic Diagram 24V ADV 8460 Sheet 2...
Страница 107: ......