Section 5 Troubleshooting
Problem
Possible Cause
Corrective Action
The generator set
does not crank.
Fault shutdown
Check for a fault code on the controller display.
See Section 2.6.
Battery weak or dead
Check power to the battery charger.
Recharge or replace the battery.
Battery charger fuse blown
Replace the fuse. Contact an authorized
distributor/dealer for service if fuse blows
repeatedly.
Battery connections reversed or poor
Check the connections.
Fuse F2 blown
Replace the fuse. Contact an authorized
distributor/dealer for service if fuse blows
repeatedly.
Fuse F3 blown
Replace the fuse. Contact an authorized
distributor/dealer for service if fuse blows
repeatedly.
Generator set master switch in the OFF
position
Move the master switch to AUTO for remote start or
to RUN for local start.
The generator set
cranks but does not
start, starts hard,
lacks power, or
operates erratically.
Air cleaner clogged
Clean and/or replace the air cleaner.
Battery weak or dead
Check power to the battery charger.
Recharge or replace the battery.
Battery connection poor
Clean and tighten the battery connections.
Spark plug wire connection loose
Check the spark plug wires.
Low oil pressure shutdown
Check the oil level.
Fuel pressure insufficient
Check the fuel supply and valves.
Engine malfunction
Contact the distributor/dealer.
No AC output.
AC circuit breaker in the OFF position
Place the circuit breaker in the ON position.
AC circuit breaker tripping because of overload
Reduce the load on the generator set.
AC circuit breaker tripping because of short
circuit
Contact an authorized distributor/dealer for service.
Auxiliary winding fuse (F1) blown
Replace the fuse. Contact an authorized distributor/
dealer for service if fuse blows repeatedly.
Low output or
excessive drop in
voltage.
Generator set overloaded
Reduce the load.
Generator set stops
suddenly.
Low oil pressure shutdown
Check the oil level.
Out of fuel
Check fuel supply.
Overcrank shutdown
Reset the controller. If the overcrank fault occurs
again, contact the distributor/dealer.
Controller fuse (F3) blown
Replace the fuse. If the fuse blows again, contact
the distributor/dealer.
Overspeed shutdown
Reset the controller. If the overspeed fault occurs
again, contact the distributor/dealer.
Generator set master switch in the OFF/RESET
position
Move the switch to the correct position (RUN or
AUTO).
Remote stop command received from a remote
switch or ATS
Check the remote switch position.
Engine malfunction
Contact the distributor/dealer.
Auxiliary winding fuse (F1) blown
Replace the fuse. Contact an authorized distributor/
dealer for service if fuse blows repeatedly.
Figure 5-2
General Troubleshooting Chart
Содержание 12RESL
Страница 14: ...TP 6517 1 11 14 Section 1 Features Notes...
Страница 20: ...TP 6517 1 11 20 Section 2 Operation Notes...
Страница 30: ...TP 6517 1 11 30 Section 3 Scheduled Maintenance 12 kW Models Notes...
Страница 42: ...TP 6517 1 11 42 Section 5 Troubleshooting Notes...
Страница 45: ...Notes...
Страница 46: ...Notes...
Страница 47: ......