Section 8 Disassembly/Reassembly

12. Suspend the rotor

over the

generator set

assembly. Lower the rotor field into the stator. Be
extremely careful while lowering the rotor to avoid
damaging the exciter armature, field magnets,
stator

windings,

or

rotor

laminations.

See

Figure 8-16. Carefully align the rotor bearing to the
end bracket. Check for an outer race measurement
of 0.6 mm (0.25 in.) from the bracket to the bearing.
Make sure the photo transistor board and actuator
cup have clearance below the end bracket.

13. Place the fan over the rotor flange and torque the

bolts to 29 Nm (260 in. lbs.).

14. Attach the drive disc(s) to the end of the rotor shaft.

Torque the drive disc mounting bolts to 68 Nm
(50 ft. lbs.).

15. Attach the hoist to the adapter eye and place the

generator set assembly in a horizontal position.
Take care not to damage the rotor or stator.
Position the generator set so that the hoisting eyes
are to the top.

16. Apply Loctite

R

No. 271 red to the stud threads, if so

equipped, and thread the studs completely into the
flywheel as shown in Figure 8-17. Apply Loctite

R

No. 242 blue to the stud threads on the nut side.

3-090

R8348-19

Figure 8-16

Installing Rotor

3-098

R8371-9

1

1. Flywheel studs

Figure 8-17

Flywheel Studs

17. Place the hoist hooks into the end bracket and the

adapter eye. Raise the generator set assembly and
align the studs with the drive discs by turning the
flywheel. Move the generator set as necessary to
work the drive discs over the studs. When the drive
discs are about 25 mm (1 in.) over the studs, install
the spacers, if equipped. See Figure 8-18.

Note:

Some models mount the drive discs to the
flywheel using bolts. Some applications use
hardened washers.

3-097

R8371-14

1

2

3

1. Drive discs
2. Studs
3. Spacers

Figure 8-18

Installing Spacers

Содержание 125EOZ/100EFOZ

Страница 1: ...33CFOZ 40EOZ 33EFOZ 50COZ 40CFOZ 50EOZ 40EFOZ 65COZ 50CFOZ 65EOZ 55EFOZ 80EOZ 70EFOZ 99EOZ 80EFOZ 125EOZ 100EFOZ 150EOZ 125EFOZ Controllers Decision Makert 3 Decision Makert 1 Standard Decision Maker...

Страница 2: ...ble for future reference Record field installed kit numbers after installing the kits Generator Set Identification Numbers Record the product identification numbers from the generator set nameplate s...

Страница 3: ...10 2 7 4 Starting the Generator Set 10 2 7 5 Stopping the Generator Set 10 2 7 6 Prime Power Mode Operation 11 2 7 7 Fault Shutdowns 11 2 7 8 Controller Resetting Procedure Following Fault Shutdown 1...

Страница 4: ...al TB1 Terminal Strip 42 Section 6 Decision Makert 1 Controller Troubleshooting 45 6 1 Decision Makert 1 and Decision Makert 1 Expanded Relay Controller 45 6 2 Relay Controller 52 Section 7 Component...

Страница 5: ...Reassembly 83 8 1 Disassembly 87 8 2 Reassembly 89 Section 9 Wiring Diagrams 95 9 1 Voltage Reconnection 116 9 1 1 Introduction 116 9 1 2 Voltage Reconnection Procedure 116 9 2 Overvoltage Shutdown A...

Страница 6: ......

Страница 7: ...generator set Accidental starting can cause severe injury or death Before working on the generator set or connected equipment disable the generator set as follows 1 Move the generator set master swit...

Страница 8: ...ath Do not smoke or permit flames or sparks near the fuel system Keep the compartment and the generator set clean and free of debris to minimize the risk of fire Wipe up spilled fuels and engine oil C...

Страница 9: ...on contact with hot parts or from sparks Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors Keep the fuel lines and connections tight and in good condition D...

Страница 10: ...ackfeed to the utility Hazardous backfeed voltage can cause severe injury or death Connect the generator set to the building marina electrical system only through an approved device and after the buil...

Страница 11: ...oval Exposed moving parts can cause severe injury or death The generator set must be operating in order to perform some scheduled maintenance procedures Be especially careful if the sound shield has b...

Страница 12: ...TP 5737 5 01 VI Safety Precautions and Instructions Notes...

Страница 13: ...ervals Obtain service from an authorized service distributor dealer to keep equipment in top condition x in 001 002 a Service Assistance Please contact a local authorized distributor dealer for sales...

Страница 14: ...TP 5737 5 01 ii Service Assistance Notes...

Страница 15: ...ion in ohms COZ CFOZ Models Specification in ohms EOZ EFOZ Models Oil Pressure Sender 0 kPa 0 psi 120 9 8 240 17 15 172 kPa 25 psi 76 5 6 7 5 153 12 15 690 kPa 100 psi 16 8 33 5 Water Temperature Send...

Страница 16: ...See Figure 1 1 The flush mounted annunciator panel extends all of the fault and prealarm lights audio of the Decision Maker 3 controller The remote annunciator includes an alarm horn an alarm silence...

Страница 17: ...ircuit Breaker The line circuit breaker interrupts generator output in the event of an overload or short circuit Use the kit to manually disconnect the generator set from the load when servicing the g...

Страница 18: ...the FASTCHECK are listed below refer to Figure 1 5 to identify LEDs and switches LEDs on the FASTCHECK indicate the energizing of the following circuits D Fuel solenoid diesel D Engine crank D AC vol...

Страница 19: ...achine because it is not dependent upon the generator set output voltage for excitation power Possibly the greatest advantage of this type of machine is its inherent ability to support short circuit c...

Страница 20: ...ide detector is 1 in the craft 2 functional and 3 energized whenever the generator set operates Fuel Level Check the fuel level and keep the tank s full to ensure adequate fuel supply Oil Level Mainta...

Страница 21: ...nside controller 2 Frequency meter 3 AC voltmeter 4 Controller TB1 and TB2 terminal strips on circuit board 5 AC ammeter 6 Scale lamps upper lower 7 Selector switch 8 Annunciator panel lamps 9 Alarm s...

Страница 22: ...the engine reaches temperature shutdown range Hourmeter The hourmeter records the generator set total operating hours for reference in maintenance scheduling Lamp test switch The switch tests the con...

Страница 23: ...set in emergency situations Use the emergency stop switch for emergency shutdowns only Use the generator set master switch for normal shutdowns 2 7 2 Fuses and Terminal Strips The following table des...

Страница 24: ...lights and the engine shuts down immediately when any customer supplied sensing devices connected to auxiliary immediate shutdown ports P1 17 and P1 18 activate them x op 005 004 2 7 4 Starting the G...

Страница 25: ...er switch to the AUTO position to return controller functions to normal Prime Power Stopping Move the generator set master switch to the OFF RESET position to stop the generator set and power down the...

Страница 26: ...use of the shutdown has been corrected 6 Reconnect the generator set to the load via the line circuit breaker or automatic transfer switch 7 Place the generator set master switch in the AUTO position...

Страница 27: ...gine shuts down because of one of the following faults high engine temperature low water level low oil pressure overcrank or overspeed See Section 2 8 4 Fault Shutdowns for additional shutdown informa...

Страница 28: ...fety Precautions at the beginning of this section before proceeding 2 Correct the cause of the fault shutdown See the Safety Precautions at the beginning of this section before proceeding 3 Start the...

Страница 29: ...total operating hours for reference in maintenance scheduling Voltage adjust potentiometer Potentiometer fine tunes 5 generator output voltage 10 amp controller fuse Fuse protects the controller circ...

Страница 30: ...artup NOTE The low oil pressure shutdown does not protect against low oil level Check the oil level at the engine Overcrank Shutdown occurs after 30 seconds of continuous cranking Shutdown occurs afte...

Страница 31: ...or death Operate the generator set only when all guards screens and covers are in place WARNING Servicing the generator set when it is operating Exposed moving parts can cause severe injury or death K...

Страница 32: ...on using a coolant tester 2 Add or replace coolant as necessary to ensure adequate freezing protection Use the guidelines included in the engine operation manual 3 Run the generator set for 30 minutes...

Страница 33: ...rrective action and testing often require knowledge of electrical and electronic circuits To avoid additional problems caused by incorrect repairs have an authorized service distributor dealer perform...

Страница 34: ...roller Section 5 or 6 x x Controller circuit board s inoperative Replace the controller circuit board Section 5 or 6 Cooling System x x Air openings clogged Clean the air openings x Impeller inoperati...

Страница 35: ...he inoperative switch Gen S M or W D x x Starter starter solenoid inoperative Replace the starter or starter solenoid Eng S M x High water temperature switch inoperative Replace the inoperative switch...

Страница 36: ...r and check for AC voltage at the generator side of the circuit breaker x Transfer switch test switch in the OFF position Move the transfer switch test switch to the AUTO position ATS O M x Wiring ter...

Страница 37: ...showing input output circuits for reference in troubleshooting This information deals directly with the 16 light microprocessor 1 10 9 6 2 5 11 7 3 12 4 8 A 328917 X 1 Selector switch 2 Lamp circuit b...

Страница 38: ...processor chip 6 TB1 terminal strip 7 TB2 terminal strip 8 P3 connector control panel harness to P4 LED indicator panel assembly 9 LED4 K4 relay 10 P1 connector DC harness 11 LED3 K3 relay 12 P2 conne...

Страница 39: ...peration requires optional kit 5 9 Crank mode open cyclic ground continuous 6 9A Crank mode ground 7 4 Remote start active low 8 3 Remote start ground Check the operation of active low circuits by pla...

Страница 40: ...h run position wire 47 Figure 5 7 P3 Connector Pins Pin Description 1 Ground front panel wire 2 2 Not used 3 Not used 4 Output from generator set master switch auto position wire 46 5 Not used 6 Volta...

Страница 41: ...WT AOP Low Fuel Battery Charger Fault Low Battery Common Fault Indicator Activated By HWT AWT LOP AOP LWT OC OS LF AUX Connect AV Alarm or Common Fault Relay Kit Running Mode Cool Down Mode Common Fau...

Страница 42: ...enoid HWT High Water Temperature HXT High Exhaust Temperature LBV Low Battery Volts LF Low Fuel LOP Low Oil Pressure LWT Low Water Temperature NIA Not In Auto OC Overcrank OS Overspeed SG Safeguard Ci...

Страница 43: ...Auxiliary Prealarm AHET Anticipatory High Engine Temperature AWT Anticipatory High Water Temperature BC Battery Charger Fault EAD Engine Air Damper ES Emergency Stop FS Fuel Solenoid HET High Engine...

Страница 44: ...TP 5737 5 01 30 Section 5 Decision Makert 3 Troubleshooting ADV 6122 B Figure 5 12 Logic Schematic Decision Maker 3...

Страница 45: ...ercrank lamp flashes Speed sensor signal is absent longer than one second No AC output is present Auxiliary lamp flashes Battery power was reconnected or was low and then came back up again while gene...

Страница 46: ...cy stop LED4 is lit at all times except during emergency stop The K4 relay is located on the controller circuit board If the emergency stop kit is connected local or remote remove the jumper from circ...

Страница 47: ...nd correlated with possible causes and corrective action Before beginning any troubleshooting procedure read all safety precautions at the beginning of this manual and those included in the text Do no...

Страница 48: ...onent s Inoperative audio visual alarm Blown F1 fuse remote annunciator 3 amp Blown F2 fuse controller 3 amp Battery connections reversed Shorted DC supply to indicator panel Shorted controller circui...

Страница 49: ...s the controller LED4 lit Yes Is the emergency stop switch controller or remote activated See emergency stopping in Section 2 Operation Do the controller s LED2 and LED3 light with the generator set m...

Страница 50: ...ck the P1 harness and connector pins Is the harness inoperative Yes Repair or replace the harness No Replace the circuit board Check the bulbs Are the bulbs burned out Yes Replace the bulbs No Check t...

Страница 51: ...re 5 22 Controller Instrumentation Press the lamp test button Do the lamps light Lamp circuit board not functioning or not functioning properly i e fault lamps and alarm horn only Improper input signa...

Страница 52: ...sensor positive terminal and negative terminal Check wire 16 for 3 6 volts DC and wire 24 for 8 10 volts DC Does this test check out okay Is the speed sensor air gap greater than that specified in Sec...

Страница 53: ...UN engine running Indicator Lamps D IGN ignition lamp D Shows battery voltage supplied to fuel solenoid D Lights during cranking and running D CRK crank lamp D Shows battery voltage switched to starte...

Страница 54: ...nector P1 and to the top of the FASTCHECK 3 Move the generator set master switch to the OFF RESET position 4 Move the FASTCHECK engine switch to the OFF position 5 Clip the red and black harness leads...

Страница 55: ...on FASTCHECK should light for approximately 5 seconds and then go out Five seconds later the IGN CRK and REG lamps should relight for 5 seconds before going out again 15 seconds total elapsed time The...

Страница 56: ...ts etc do not function Test point connections are shown in Figure 5 29 and Figure 5 30 Note When checking controller test point voltage place the negative lead of the voltmeter on the terminal designa...

Страница 57: ...and TB1 40 Anticipatory Low Engine Oil Pressure AOP Master switch in RUN position engine switch in RUN hold toggle switch to AOP TB1 42A and TB1 41 Low Water Temperature LWT if equipped Master switch...

Страница 58: ...TP 5737 5 01 44 Section 5 Decision Makert 3 Troubleshooting Notes...

Страница 59: ...lay 6 Ground strap 7 Hourmeter front panel 8 Fault lamp front panel 9 Voltage adjust potentiometer front panel 10 10 amp fuse front panel 11 Generator set master switch front panel Figure 6 1 Decision...

Страница 60: ...uit between N and 47 K2 Open Open Deenergizes engine components generator set shuts down Fault shutdowns Low oil pressure LOP high engine temperature HET after the engine operating temperature reaches...

Страница 61: ...D Overcrank Overspeed LWL HET and LOP drive the fault shutdown circuit D Fault latch provided by K1 normally open contacts D Overcrank shutdown is only driven by AC D Crank disconnect driven by AC an...

Страница 62: ...TP 5737 5 01 48 Section 6 Decision Makert 1 Controller Troubleshooting ADV 6120 A Figure 6 5 Decision Maker 1 Relay Controller with E 254717 Circuit Board...

Страница 63: ...TP 5737 5 01 49 Section 6 Decision Makert 1 Controller Troubleshooting ADV 6120 D Figure 6 6 Decision Maker 1 Relay Controller with F 254717 Circuit Board...

Страница 64: ...TP 5737 5 01 50 Section 6 Decision Makert 1 Controller Troubleshooting ADV 6121 Figure 6 7 Decision Maker 1 Expanded Relay Controller with E 254717 Circuit Board...

Страница 65: ...TP 5737 5 01 51 Section 6 Decision Makert 1 Controller Troubleshooting ADV 6121 C Figure 6 8 Decision Maker 1 Expanded Relay Controller with F 254717 Circuit Board...

Страница 66: ...remote computer Hazardous voltage Can cause severe injury or death Operate the generator set only when all guards and electrical enclosures are in place Moving rotor WARNING Grounding electrical equi...

Страница 67: ...f the start stop switch N 4 and 47 See Wiring Diagrams D Check the battery condition and connections Do the above items check out okay Yes Is the 10 amp fuse functioning Is the K4 relay LED4 lit The K...

Страница 68: ...okay No Yes Replace the circuit board Repair replace the wiring harness No Unit starts but then shuts down Is the K2 relay energized Yes Is the K10 with F 254717 or K5 with E 254717 relay energized N...

Страница 69: ...es Is the K3 relay LED3 lit No Check for 120 volts AC output from the stator 10 7 winding at V0 and V7 See Section 7 Stator Testing Run the generator set while performing this test Test the speed sens...

Страница 70: ...TP 5737 5 01 56 Section 6 Decision Makert 1 Controller Troubleshooting Notes...

Страница 71: ...y an automatic transfer switch remote start stop switch or engine start command from a remote computer Hazardous voltage Can cause severe injury or death Operate the generator set only when all guards...

Страница 72: ...place the photo transistor board If no voltage is detected test the rotor Do the exciter armature and main field windings check out okay If no DC voltage is present unplug the connector at the LED cir...

Страница 73: ...eplace the voltage regulator Yes No Yes No No Yes Yes No Figure 7 2 Troubleshooting Generator High Output Voltage Accidental starting Can cause severe injury or death Disconnect the battery cables bef...

Страница 74: ...meter for AC output voltage 2 If AC output is not present then a Check wire 1B from the safeguard breaker and wire 7N ground to the voltage regulator b Check for voltage to the safeguard breaker if eq...

Страница 75: ...Hz 60 Hz C A LED BOARD PHOTO TRANSISTOR BOARD MAGNETS MAGNETS EXCITER ARMATURE SCR ASSEMBLY GENERATOR FIELD 12 LEAD STATOR BATTERY STARTER P S P HC 15 AMP CONTROL RELAY CONTACTS SELECTOR SWITCH T3 T1...

Страница 76: ...y 3 Check the stator for shorted or open windings See Section 7 6 Stator 4 Verify the AVR adjustment See Section 7 5 Automatic Voltage Regulator Operation and Adjustment 7 3 LED Circuit Board Test The...

Страница 77: ...be high Switch the flashlight off or turn it away from the rotating photo transistor board The AC output voltage should be low If these conditions exist high voltage while the photo transistor board i...

Страница 78: ...oving the entire SCR assembly for testing See Section 7 9 End Bracket Removal and Replacement and Section 8 Disassembly Reassembly for end bracket removal Testing the SCR assembly and photo transistor...

Страница 79: ...orking Note When testing the SCR assembly secure all connections with nuts to ensure good contact between the wire terminals and the foil pattern The threaded studs are insulated from the foil pattern...

Страница 80: ...er until minimum flicker is obtained 6 Use the controller voltage adjustment potentiometer or remote voltage adjustment potentiometer to make adjustments to the generator while running under normal lo...

Страница 81: ...oller If this circuit is open repair or replace the inoperative components and or wiring 6 Check for battery voltage at the voltage regulator harness plug pins 2 and 11 with the generator set running...

Страница 82: ...ot windings exist See Figure 7 12 Note Disconnect V7 V8 V9 and V0 leads at the controller AC fuse terminal blocks before performing the open winding test b Open windings With an ohmmeter check each pa...

Страница 83: ...t Removal and Replacement and Section 8 Disassembly Reassembly 3 Disconnect F and F from the SCR assembly 4 With an ohmmeter check for continuity across the F and F leads see Figure 7 14 Resistance re...

Страница 84: ...ere injury or death Avoid touching the generator set field or exciter armature When shorted the generator set field and exciter armature become hot enough to cause severe burns Exciter Armature Test 1...

Страница 85: ...icates the field winding is functional A reading of less than 5 7 kOhms approximately indicates deterioration of the winding insulation and possible current flow to ground 8 Repair or replace the roto...

Страница 86: ...ch inside the stator shell and disconnect the photo transistor board leads from the SCR assembly to allow for slack when removing the end bracket 5 Remove the four bolts holding the end bracket to the...

Страница 87: ...speed sensor voltmeter and DC voltage source as shown in Figure 7 19 o 1 2 3 TP 5353 7 1 DC voltmeter 2 12 volt battery or DC power supply 3 Speed sensor Figure 7 19 Speed Sensor Test 2 Touch the sens...

Страница 88: ...ts can cause bodily injury and or equipment damage Do not contact electrical connections with tools or jewelry while making adjustments or repairs Remove all jewelry before servicing the equipment 7 1...

Страница 89: ...r master switch in the RUN position 5 Use the controller or remote voltage adjusting potentiometer on each generator set to fine adjust voltage as necessary 6 Apply resistive load 1 0 power factor unt...

Страница 90: ...n information Use the engine service manual for troubleshooting ECM senders switches 7 13 1 Oil Pressure Sender Testing Disconnect the oil pressure sender lead 7C See Figure 7 21 Check the sender resi...

Страница 91: ...d control to the fuel injection pump lever 5 Stop the generator set TP 5353 7 1 2 1 Injection pump lever 2 Fast idle adjusting screw Figure 7 23 Governor Adjustments Typical 7 14 2 Electronic Governor...

Страница 92: ...he power is off The magnetic pickup air gap is 0 36 0 71 mm 0 014 0 028 in TP 5353 7 1 2 1 Actuator 2 Linkage Figure 7 26 Throttle Actuator Barber Colman Dyna 2500 John Deere 6076 Shown The Barber Col...

Страница 93: ...3 If governing is unstable turn the I and gain potentiometers slightly CCW Note Except for the speed potentiometer control unit potentiometers have internal stops at 0 and 100 4 With the engine runnin...

Страница 94: ...guard breaker terminal strip 5 Connect to cranking solenoid battery 6 Connect to 70 on safeguard breaker terminal strip 7 Actuator 8 Magnetic pickup Figure 7 28 Governor Control Unit Nonparalleling Ge...

Страница 95: ...pump s internal components Note Follow this procedure carefully to prevent engine overspeed and damage to the generator or other load 3 Turn the droop adjusting screw counterclockwise until it stops...

Страница 96: ...ockwise until the engine becomes unstable After the engine becomes unstable slowly turn the gain potentiometer counterclockwise until stable Interrupt the governor by momentarily removing power from t...

Страница 97: ...tions exist which may require taking notes The reassembly procedure includes important alignment steps and provides critical torque specs Accidental starting Can cause severe injury or death Disconnec...

Страница 98: ...ondition Donotreplaceflexiblefuellineswithrigidlines Use flexible sections to avoid fuel line breakage caused by vibration Do not operate the generator set in the presence of fuel leaks fuel accumulat...

Страница 99: ...ltage regulator panel 3 Voltage regulator 4 Voltage regulator wiring harness 5 Junction box cover 6 Junction box panel 7 Junction box 8 Alternator assembly 9 End bracket cover 10 Skid 11 Generator fan...

Страница 100: ...circuit board cover 2 LED circuit board 3 Photo transistor board 4 Insulating washer 5 Insulator 6 Magnetic actuator 7 End bracket 8 Exciter field assembly 9 Rotor assembly 10 SCR assembly 11 Generat...

Страница 101: ...ywheel housing 6 Remove the nuts and spacers holding the drive discs to the flywheel 7 Work the drive discs over the studs if equipped to separate the generator set from the engine See Figure 8 4 8 Se...

Страница 102: ...wly lower the rotor to a horizontal position Set the rotor on a wooden surface Take care not to damage the windings laminations or bearing See Figure 8 7 14 Place the generator set assembly on the gen...

Страница 103: ...ring inside the end bracket bore Install a new tolerance ring when reinstalling the end bracket 2 Place the stator in a vertical position with the end bracket side up Note The end bracket side of the...

Страница 104: ...sembly on the end bracket end when installing the rotor Fasten the hoisting hook to the end bracket eye and lower the generator set assembly to a horizontal position 8 Attach the hoisting hooks to the...

Страница 105: ...Figure 8 14 Push the lead through the hole in the rotor shaft and then through the exciter laminations ending near the SCR assembly 11 Attach the photo transistor board and magnetic actuator to the e...

Страница 106: ...ssembly in a horizontal position Take care not to damage the rotor or stator Position the generator set so that the hoisting eyes are to the top 16 Apply LoctiteR No 271 red to the stud threads if so...

Страница 107: ...ywheel Torque the hardware to the values given in Section 1 Specifications Generator 22 Install the fan guard 23 Install the speed sensor and set the speed sensor air gap at 0 36 0 71 mm 0 01 0 03 in...

Страница 108: ...TP 5737 5 01 94 Section 8 Disassembly Reassembly Notes...

Страница 109: ...ch or engine start command from a remote computer Hazardous voltage Can cause severe injury or death Operate the generator set only when all guards and electrical enclosures are in place Moving rotor...

Страница 110: ...TP 5737 5 01 96 Section 9 Wiring Diagrams Notes...

Страница 111: ...TP 5737 5 01 97 Section 9 Wiring Diagrams 344496A E Figure 9 1 Wiring Diagram Decision Makert 1 Standard Controller Sheet 1 of 3...

Страница 112: ...TP 5737 5 01 Section 9 Wiring Diagrams 98 344496B E Figure 9 2 Wiring Diagram Decision Makert 1 Standard Controller Remote Panel Options Sheet 2 of 3...

Страница 113: ...TP 5737 5 01 99 Section 9 Wiring Diagrams 344496C E Figure 9 3 Wiring Diagram Decision Makert 1 Standard Controller Remote Panel Options Sheet 3 of 3...

Страница 114: ...TP 5737 5 01 Section 9 Wiring Diagrams 100 344497A D Figure 9 4 Wiring Diagram Decision Makert 1 Expanded Controller Sheet 1 of 4...

Страница 115: ...TP 5737 5 01 101 Section 9 Wiring Diagrams 344497B D Figure 9 5 Wiring Diagram Decision Maker t1 Expanded Controller Remote Panel Options Sheet 2 of 4...

Страница 116: ...TP 5737 5 01 Section 9 Wiring Diagrams 102 344497C D Figure 9 6 Wiring Diagram Decision Maker t1 Expanded Controller Remote Panel Options Sheet 3 of 4...

Страница 117: ...TP 5737 5 01 103 Section 9 Wiring Diagrams 344497D D Figure 9 7 Wiring Diagram Decision Makert 1 Expanded Controller Remote Panel Options Sheet 4 of 4...

Страница 118: ...TP 5737 5 01 Section 9 Wiring Diagrams 104 344498A C Figure 9 8 Wiring Diagram Decision Makert 3 Controller Sheet 1 of 5...

Страница 119: ...TP 5737 5 01 105 Section 9 Wiring Diagrams 344498B C Figure 9 9 Wiring Diagram Decision Makert 3 Controller Remote Panel Options Sheet 2 of 5...

Страница 120: ...TP 5737 5 01 Section 9 Wiring Diagrams 106 344498C C Figure 9 10 Wiring Diagram Decision Makert 3 Controller Remote Panel Options Sheet 3 of 5...

Страница 121: ...TP 5737 5 01 107 Section 9 Wiring Diagrams 344498D C Figure 9 11 Wiring Diagram Decision Makert 3 Controller Remote Panel Options Sheet 4 of 5...

Страница 122: ...TP 5737 5 01 Section 9 Wiring Diagrams 108 344498E C Figure 9 12 Wiring Diagram Decision Makert 3 Controller Remote Panel Options Sheet 5 of 5...

Страница 123: ...TP 5737 5 01 109 Section 9 Wiring Diagrams ADV 6120 A Figure 9 13 Decision Maker 1 Relay Controller with E 254717 Circuit Board...

Страница 124: ...TP 5737 5 01 Section 9 Wiring Diagrams 110 ADV 6120 D Figure 9 14 Wiring Diagram Decision Makert 1 Standard Controller with F 254717 Circuit Board...

Страница 125: ...TP 5737 5 01 111 Section 9 Wiring Diagrams ADV 6121 Figure 9 15 Decision Maker 1 Expanded Relay Controller with E 254717 Circuit Board...

Страница 126: ...TP 5737 5 01 Section 9 Wiring Diagrams 112 ADV 6121 C Figure 9 16 Wiring Diagram Decision Makert 1 Expanded Controller with F 254717 Circuit Board...

Страница 127: ...TP 5737 5 01 113 Section 9 Wiring Diagrams ADV 6122 B Figure 9 17 Wiring Diagram Decision Makert 3 Controller...

Страница 128: ...TP 5737 5 01 Section 9 Wiring Diagrams 114 Notes...

Страница 129: ...fault lamp active low if used 63 Low fuel LF fault connect fuel level sensor to TB1 63 to activate fault lamp active low if used 70C Generator in cool down mode signal 70R Generator in running mode s...

Страница 130: ...negative lead first Reconnect the negative lead last when reconnecting the battery Follow these precautions to prevent starting of the generator set by an automatic transfer switch remote start stop...

Страница 131: ...sets are reconnectable The 6 lead 600 volt generator set is not reconnectable Some specially wound stators made for a single voltage are also not reconnectable Note 600 volt models only Use 1 turn of...

Страница 132: ...wardthegeneratorset Somegeneratorsetshave no current transformers Note Phase Rotation A L1 B L2 and C L3 Note All 12 lead generator sets are reconnectable The 6 lead 600 volt generator set is not reco...

Страница 133: ...or 3 phase configuration depending on generator set connection Connect a voltmeter across leads L1 and L2 if the controller has no meters Note Equipment damage Verify that the voltage ratings of the...

Страница 134: ...ge to 115 of the nominal output voltage using the voltage adjustment potentiometer If the voltage configuration is 139 240 volts low wye or 277 480 volts high wye 3 phase 4 wire 60 Hz adjust the outpu...

Страница 135: ...rminal 2 T1 terminal 3 T3 terminal Figure 9 25 Jumper Location for 50 or 60 Hz Operation 9 3 2 Frequency Adjustment Check the frequency meter for a no load reading of 63 Hz for 60 Hz operation and 53...

Страница 136: ...TP 5737 5 01 122 Section 9 Wiring Diagrams Notes...

Страница 137: ...e CWC city water cooled cyl cylinder D A digital to analog DAC digital to analog converter dB decibel dBA decibel A weighted DC direct current DCR direct current resistance deg degree dept department...

Страница 138: ...onal Safety and Health Administration O V overvoltage oz ounce p pp page pages PA packed accessory PC personal computer PCB printed circuit board pF picofarad PF power factor ph phase PHC Phillips hea...

Страница 139: ...p of nut 3 Below top of nut Figure 1 Acceptable Bolt Lengths Steps for common hardware application 1 Determine entry hole type round or slotted 2 Determine exit hole type fixed female thread weld nut...

Страница 140: ...0 32 68 0 50 95 0 70 1 2 13 Nm ft lb 60 0 44 92 0 68 130 0 96 1 2 20 Nm ft lb 66 0 49 103 0 76 146 0 108 9 16 12 Nm ft lb 81 0 60 133 0 98 187 0 138 9 16 18 Nm ft lb 91 0 67 148 0 109 209 0 154 5 8 11...

Страница 141: ...al External Tooth Lock Hardness Grades American Standard Grade 2 Grade 5 Grade 8 Grade 8 9 Hex Socket Head Metric Number stamped on hardware 5 8 shown 5 8 Allent head screw is a trademark of Holo Krom...

Страница 142: ...6024 2 7 16 14 x 1 00 X 6024 8 7 16 14 x 1 25 X 6024 3 7 16 14 x 1 50 X 6024 4 7 16 14 x 2 00 X 6024 11 7 16 14 x 2 75 X 6024 12 7 16 14 x 6 50 X 129 15 1 2 13 x 75 X 129 17 1 2 13 x 1 00 X 129 18 1 2...

Страница 143: ...25 x 20 M933 10020 60 M10 1 50 x 20 M933 10025 60 M10 1 50 x 25 M933 10030 60 M10 1 50 x 30 M933 10030 82 M10 1 50 x 30 M961 10035 60 M10 1 25 x 35 M933 10035 60 M10 1 50 x 35 M933 12016 60 M12 1 75...

Страница 144: ...Log Use the log below to keep a cumulative record of operating hours on your generator set and the dates required services were performed Enter hours to the nearest quarter hour OPERATING HOURS SERVIC...

Страница 145: ......

Страница 146: ......

Страница 147: ......

Страница 148: ...5 3381 Web site www kohlergenerators com Fax 920 459 1646 U S A Sales Fax 920 459 1614 International For the nearest sales and service outlet in U S A and Canada Phone 1 800 544 2444 Kohlerr Power Sys...

Отзывы: