TP-6161
1/12
15
Section 1 Specifications and Features
1.2.7
DIP Switches
The controller circuit board contains eight DIP switches,
see Figure 1-9.
DIP
Switch Description
Switch Position
Open
Closed
1
Overspeed selection
60 Hz
70 Hz
2
Temperature Cooldown
Enable
Cooldown
Disabled
Cooldown
Functional
3
Crank Mode Selection
Cyclic
Continuous
4
Engine Comm. Setting
See selections for
DIP switch 4 and
DIP switch 5 below
5
Engine Comm. Setting
6
Modbus
r
Address Bit 0
Value = 0
Value = 2
7
Modbus
r
Address Bit 1
Value = 0
Value = 4
8
Modbus
r
Address Bit 2
Value = 0
Value = 8
4
No ECM
Open
5
Open
4
MDEC/ADEC Comm.
Closed
5
Isochronous
Open
4
J1939 Communication
Open
5
Closed
4
MDEC/ADEC Comm.
Closed
5
Governor (VSG)
(Doosan, GM, and
Volvo engine only)
Closed
Figure 1-9
DIP Switch Functions
Note: After setting DIP switches to the generator set
application,
be sure to
power down
and then
power up
the controller (disconnect the battery
and then reconnect the battery of the generator
set) or use the prime power switch, if equipped.
The controller will NOT acknowledge the DIP
switch change until after generator set controller
is
powered up
.
Push down the end of the DIP switch near the OPEN
label to open the switch, or push down the other end to
close it. See Figure 1-10.
6126
1. Push this side down to open circuit.
OPEN
1
2
3
1
4 5
6
7 8
Figure 1-10
DIP Switch Open Position
Typically, the factory default settings have all the DIP
switches in the closed position except the crank mode
selection switch SW3 which is open for cyclic cranking.
The overspeed selection switch SW1 is open on 50 Hz.
units.
Be sure to select the correct DIP switch
configuration for each generator set application.
Overspeed Frequency (DIP Switch 1)
. The generator
set overspeed frequency is set using DIP switch 1.
Select 70 Hz for 60 Hz voltages and 60 Hz for 50 Hz
voltages.
Temperature Cooldown (DIP Switch 2).
The
generator set will continue to run during a five-minute
cooldown cycle or shut down immediately. The choice is
made using DIP switch 2.
Engine Cranking (DIP Switch 3).
The controller is
factory-set for cyclic cranking.
To change to the
continuous cranking mode, use DIP switch 3.
Engine Configuration (DIP Switches 4 and 5).
See
Figure 1-9 for the DIP switch positions based on engine
configurations regarding non-ECM, MDEC, and J1939
engine communication selections.
Modbus
r
Address (DIP Switches 6--8).
Each
Modbus
r
device requires a unique address. Address
numbers are created using a binary number system with
DIP switches 6--8. Figure 1-11 shows the DIP switch
position for each address number.
Modbus
r
Address
DIP Switches
6
7
8
Value = 2
Value = 4
Value = 8
1
Open
Open
Open
3
Closed
Open
Open
5
Open
Closed
Open
7
Closed
Closed
Open
9
Open
Open
Closed
11
Closed
Open
Closed
13
Open
Closed
Closed
15
Closed
Closed
Closed
Figure 1-11
Modbus
r
Device Address
Modbus
r
is a registered trademark of Schneider Electric.
Содержание 1250-2250 kW
Страница 27: ...TP 6161 1 12 27 Section 3 Scheduled Maintenance ADV 7600B B Figure 3 6 Gas Fuel Connections Wiring Diagram...
Страница 38: ...TP 6161 1 12 38 Section 3 Scheduled Maintenance Notes...
Страница 57: ...TP 6161 1 12 57 Section 6 Accessories Figure 6 19 RSA Wiring Connections GM62554A G...
Страница 58: ...TP 6161 1 12 58 Section 6 Accessories Figure 6 20 RSA Wiring Connections GM62554B G...
Страница 59: ...TP 6161 1 12 59 Section 6 Accessories Figure 6 21 RSA Wiring Connections GM62554C G...
Страница 60: ...TP 6161 1 12 60 Section 6 Accessories Figure 6 22 RSA Wiring Connections GM62554D G...
Страница 61: ...TP 6161 1 12 61 Section 6 Accessories Figure 6 23 RSA Wiring Connections GM62554E G...
Страница 68: ...TP 6161 1 12 68 Section 6 Accessories Figure 6 38 Accessory Connections 328912A H...
Страница 69: ...TP 6161 1 12 69 Section 6 Accessories Figure 6 39 Accessory Connections 328912B H...
Страница 70: ...TP 6161 1 12 70 Section 6 Accessories Figure 6 40 Accessory Connections 328912C H...
Страница 75: ......