14
Section 1 Specifications and Features
1.2.5
Switches and Controls
Figure 1-6 describes the switches and controls located
on microprocessor controllers.
Name
Description
Alarm horn
Horn sounds if any fault or prealarm condition
exists (except emergency stop, battery charger
fault, high battery voltage, or low battery voltage).
Place the generator set master switch in the
AUTO position before silencing the alarm horn.
See controller resetting procedure in Section
2.3.5, Controller Resetting After a Fault Shutdown.
Alarm
silence
switch
Switch silences the alarm during service. Place
the generator set master switch in the AUTO
position before silencing the alarm horn. To avoid
reactivating the alarm horn, restore all alarm horn
switches (controller, remote annunciator, and
audiovisual alarm) to their normal positions after
correcting the fault. See controller resetting
procedure in Section 2.3.5, Controller Resetting
After a Fault Shutdown.
Emergency
stop switch
Switch (if equipped) immediately shuts down the
generator set in emergency situations. Reset the
emergency stop switch after shutdown by pulling
the knob slightly outward. Use the emergency
stop switch for emergency shutdowns only. Use
the generator set master switch for normal
shutdowns. The local emergency stop switch is
standard on selected generator sets.
Generator
set master
switch
Switch functions as the controller reset and
generator set operation switch. Refer to
Section 2.3.1, Normal Operation, Section 2.3.2,
Prime Power Mode Operation
,
and Section 2.3.5,
Controller Resetting After a Fault Shutdown.
Lamp test
switch
Switch displays the controller indicator lamps.
Selector
switch
Switch selects the generator set output circuits to
measure. When switched to a position with three
circuit labels, the meters display the amperage on
the lead shown in the upper label and the voltage
between the two leads shown in the lower label.
The AC ammeter and voltmeter function only with
the switch in the ON position.
Voltage
adjustment
control, if
equipped
Control fine tunes (
±
5%) the generator set output
voltage. Used with 20--400 kW permanent
magnet/wound field alternator models only. The
voltage adjustment on 350--2000 kW pilot-excited
models is located in the generator junction box.
Figure 1-6
Switches and Controls
1.2.6
Terminal Strips
Two terminal strips are mounted on the controller circuit
board. See Figure 1-7 and Figure 1-8. Refer to Section
2.3.2, Prime Power Mode Operation, for information on
enabling prime power mode.
Terminal
Strip
Description
TB1/TB3
Terminal strip for connecting generator set
accessories such as an emergency stop switch, a
remote start/stop switch, audiovisual alarms, etc.
Refer to the wiring diagrams for information on
connecting accessories to the TB1 terminal strip.
TB2
Terminal strip for selecting the remote start/stop
switch inputs and prime power mode.
P3/P7
Communication module connection for remote serial
annunciator (RSA) or network communication.
P21
RS-485 communication connection for Modbus
r
to
download new application program software or for
connecting the remote serial annunciator.
P22
CAN (engine) communication connection.
Figure 1-7
Controller Terminal Strips/Connections
1. TB1 (TB1A) terminal strip
2. TB3 (TB1B) terminal strip
3. TB2 terminal strip
4. P3 annunciator panel lamp and RSA communication
module connections
5. P21 for Modbus
r
RS-485 communication connection
6. P22 for CAN (engine) communication connection
7. SW1 DIP switch (8 positions)
8. P7 RSA communication module connection
9. Fuses
GM28725-
5
6
9
7
2
3
1
4
8
Figure 1-8
Controller DIP Switches
Modbus
r
is a registered trademark of Schneider Electric.
Содержание 1250-2250 kW
Страница 27: ...TP 6161 1 12 27 Section 3 Scheduled Maintenance ADV 7600B B Figure 3 6 Gas Fuel Connections Wiring Diagram...
Страница 38: ...TP 6161 1 12 38 Section 3 Scheduled Maintenance Notes...
Страница 57: ...TP 6161 1 12 57 Section 6 Accessories Figure 6 19 RSA Wiring Connections GM62554A G...
Страница 58: ...TP 6161 1 12 58 Section 6 Accessories Figure 6 20 RSA Wiring Connections GM62554B G...
Страница 59: ...TP 6161 1 12 59 Section 6 Accessories Figure 6 21 RSA Wiring Connections GM62554C G...
Страница 60: ...TP 6161 1 12 60 Section 6 Accessories Figure 6 22 RSA Wiring Connections GM62554D G...
Страница 61: ...TP 6161 1 12 61 Section 6 Accessories Figure 6 23 RSA Wiring Connections GM62554E G...
Страница 68: ...TP 6161 1 12 68 Section 6 Accessories Figure 6 38 Accessory Connections 328912A H...
Страница 69: ...TP 6161 1 12 69 Section 6 Accessories Figure 6 39 Accessory Connections 328912B H...
Страница 70: ...TP 6161 1 12 70 Section 6 Accessories Figure 6 40 Accessory Connections 328912C H...
Страница 75: ......