34
C35-FC
14.8. Two stage chilled or heated ceiling
HOME > MENU > ADVANCED > PARAMETERS [1/4]
Application type:
2-stage chilled/heated ceiling
Control sequence:
Cooling only
Heating
only
Cooling
or
heating
HOME > MENU > ADVANCED > IN / OUT [1/2]
Binary input:
Dew point sensor
RTD Sensor function:
Changeover
sensor
Remote
sensor
Temperature sensor:
Internal
Remote
D1
– C35-FC
V1
– Cooling or heating valve stage one (DC 0-10 V)
V2
– Cooling or heating valve stage two (DC 0-10V)
H1
– Dew point sensor
T1
– Changeover or remote sensor (PT1000)
Figure 14.8.1.
Figure 14.8.2.
Figure 14.8.3.
14.9. Applications with 3 or 1 speed motor and thermal valve actuators using FC-RB
AO1
AO2
AO3
24V
GND
G
D-
D+
RTD
RTD
BIN1
GND
230V AC
50 Hz
L
N
V1
V2
AI1
AI2
AI3
24V AC
GND
10 A
DO1
DO2
DO3
DO5
D2
L
DO4
M1
D1
S1
T
T1
Figure 14.9.1. Connection diagram of C35-FC… (D1) and FC-RB (D2)
For applications with 3/1 speed motor and/or with thermal valve actuators which are
controlled by mechanical and solid state relays, use the FC-RB fan coil relay board.
Voltage output (AO1) from the C35-FC device is applied to analog input 1 (AI1) of the FC-RB, and
it controls the 3 or 1 speed fan through digital outputs (DO1, DO2, DO3).
H1
V1
T1
V2
T1
AO1
AO2
AO3
24V
GND
G
D-
D+
GND
GND
GND
RTD
RTD
BIN1
GND
24V
AC/DC
/+
/-
D1
T
T1
V1
V2
6A
H1
AO2A
O3
Analog outputs
[V, DC]
10
t [s]