Kobold NRM Скачать руководство пользователя страница 16

NRM 

page 16 

 

NRM K06/0422 

8.1.3 

Echo map 

Pressing the   button in the measurement 
screen the echo map screen will appear. This 
screen shows the following information: 
1.  Echo diagram 
2.  Actual measured distance 
3.  Maximal measuring range 
 
The  echo  map  screen  returns  back  to  main 
screen after 30 seconds. 
By pressing the   button the user can return to 
the main screen any time. Pressing the 

E

 button 

in  any  of  the  screens  the  user  can  enter  main 
menu.  After  exiting  the  menu  always  the  main 
screen will be shown. 
 
 

8.2  Programming with the NRM-300P display module 

When  entering  the  menu  the  instrument  makes  a  copy  of  the  actual  parameters 
and all changes are done to this duplicated parameter set. During programming the 
instrument  keeps  measuring  and  transmitting  with  the  current  (and  intact) 
parameter  set.  After  exiting  the  menu  the  instrument  replaces  the  original 
parameters  with  the  new  parameter  set  and  will  measure  according  to  the  new 
parameters.  This  means  that  the  change  of  the  parameters  does  not  become 
immediately effective when pressing the 

E

 button! 

 

Entering the menu can be done by pressing the 

E

 button, while exiting the menu 

can be done by pressing the   button. 
If the instrument is left in programming mode after 30 minutes it will automatically 
return  to  measuring  mode.  If  the  NRM-300P  display  is  removed  during 
programming the instrument immediately returns to measuring mode. 
As programming with NRM-300P (manual programming) and HART (remote mode) 
programming  is  not  possible  at  the  same  time,  only  one  programming  method 
could be chosen. Measured values can be read out through HART at any time. 
 
 

8.2.1 

Components of the programming interface 

The  parameters  of  the  instrument  are  grouped  according  to  their  functions.  The 
programming  interface  consists  of  lists,  dialog  windows,  edit  windows  and  report 
windows. 

Содержание NRM

Страница 1: ...Operating Instructions for Non Contact Radar Level Transmitter Model NRM...

Страница 2: ...egulation Use 4 5 Operating Principle 5 6 Installation 6 6 1 Mounting 6 7 Wiring 9 7 1 Wiring of the devices 10 7 2 Determine the appropriate power supply voltage 11 7 3 Loop current checking with han...

Страница 3: ...6 0422 page 3 Manufactured and sold by Kobold Messring GmbH Nordring 22 24 D 65719 Hofheim Tel 49 0 6192 2990 Fax 49 0 6192 23398 E Mail info de kobold com Internet www kobold com Edition August 2017...

Страница 4: ...to be used maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health Safety and prevention of accidents When used in mac...

Страница 5: ...independently from the process temperature and pressure so the measured distance is not affected by the physical parameters of medium to be measured The NRM level transmitter is a Pulse Burst Radar op...

Страница 6: ...he measurement accuracy and the maximal measuring range To avoid these effects the mounting placement should be as far as possible from the sources of these disturbing effects According to measurement...

Страница 7: ...se the microwave signals and eliminates the false reflections which disturb the reliable measurement If there is no possible mechanical solution to avoid these kinds of false reflections the programmi...

Страница 8: ...he tank bottom or the objects at the bottom disperse or reflect the emitted microwave signals Furthermore the lower signal level dispersed radar impulses may interfere with itself inside the tank In o...

Страница 9: ...ial network Resistance of the EP network should be R 2 Ohm measured from the neutral point Shielding of the cable should be grounded at the control room side to the EP network To avoid disturbing nois...

Страница 10: ...es in cooled and or heated tanks 7 1 Wiring of the devices Using HART communication Using Ex approved instrument In non Ex environment in hazardous environment In case of integrated version Prior to w...

Страница 11: ...ance to the below diagram 22 21 20 19 18 17 16 15 14 13 12 2 4 6 8 10 12 14 16 18 20 22 19 1 13 6 B A Minimal supply voltage on the input terminals of the device Minimal supply voltage considering the...

Страница 12: ...s of the unit can be accessed and all parameters can be set such as measurement configuration and optimisation outputs dimensions for 11 tanks with different shape 99 point linearization Programming w...

Страница 13: ...ports NRM 300P Warning The NRM 300P module is based on LCD technology so please make sure it is not exposed to permanent heat or direct sunlight in order to avoid damage of the display unit If the ins...

Страница 14: ...ddress is not 0 so output current has become overwritten to 4 mA see 8 3 2 1 E Analogue transmission reacts to a programmed failure condition if an upper or lower fault current is programmed see 8 3 2...

Страница 15: ...and the amplitude of the echoes Dist Amp are listed The listed items are the reflections detected by the NRM measured in dB and the approximate distance from the process connection The listed values...

Страница 16: ...ng the menu the instrument replaces the original parameters with the new parameter set and will measure according to the new parameters This means that the change of the parameters does not become imm...

Страница 17: ...rnings to the users by dialog windows These usually can be acknowledged by pressing the button or the user can choose between two options usually YES or NO by pressing the buttons In some cases one of...

Страница 18: ...Anglo Saxon American unit system 8 3 1 2 Dimension of the fault unit system Parameter P00 b and P02 b or P02 c Default value mm m3 t Path BASIC SETUP UNITS ENGINEERING UNITS Description The dimension...

Страница 19: ...P00 d Default value OFF Path BASIC SETUP DEMO MODE Description OFF The operation is performed with considering all the application parameters such as filling emptying speed echo selection etc ON This...

Страница 20: ...change in measured value and the change in the output value are the same normal or opposite directional inverse operation For example 1m level is 4 mA 10m level is 20 mA or 1m level is 20 mA and 10m...

Страница 21: ...and false reflections which are close to the sensor can be eliminated by entering the dead zone value manually 8 3 4 2 Echo selection Parameter P25 a where a 0 1 2 3 Default value AUTO Path OPTIMIZAT...

Страница 22: ...s procedure the software will automatically recognise and ignore the reflections coming from the disturbing objects crossing the microwave beam see 6 1 Obstacles Warning The background image should be...

Страница 23: ...rds the echo signal as false reflection 8 3 5 Calculations 8 3 5 1 Specific gravity Parameter P32 Default value 0 Path CALCULATION SPECIFIC GRAVITY Description Entering a value other than 0 of specifi...

Страница 24: ...done in arbitrary order because the device sorts according to ascending order Both sides of the table have to be strictly monotonic increasing In case of any error warning message see 9th chapter will...

Страница 25: ...0 Path CALCULATION V M CALC MODE TANK FUNCTION SHAPE Description This menu only appears if it has an importance on the selected tank shape type SHAPE0 SHAPE1 SHAPE2 SHAPE3 8 3 5 6 Tank dimensions Para...

Страница 26: ...this Parameter the current value which is proportional to the actual measurement value will appear on the display and the output In loop current test mode values between 3 9 and 20 5 can be entered T...

Страница 27: ...E Description Cycle time of the simulation Bottom value of the simulation Parameter P86 Default value 0 mm Path SERVICE DIST SIMULATION BOTTOM VALUE Description Lowest value of the simulation Upper va...

Страница 28: ...or monotonicity error in the input level side of the table Check the content of the VMT See 8 3 5 3 13 VMT OUTPUT ERROR Linearization table error monotonicity error in the output volume or mass side o...

Страница 29: ...in the measured value 0 999 25 Echo selection in the measuring windo 0 AUTO 1 FIRST 2 HIGHEST AMPLITUDE 3 LAST 26 Filling speed Rate of change of the measured value when distance is decreasing which...

Страница 30: ...n in the selected unit e g mm Its default value is the same as the programmed maximal measurement range 11 Menu map MAIN MENU BASIC SETUP OUTPUT SETUP OPTIMIZATION CALCULATION SERVICE BASIC SETUP UNIT...

Страница 31: ...BOT STD RECT W CHUTE LYING CYLINDRICAL SPHERICAL BOTTOM SHAPE SHAPE 0 SHAPE 1 SHAPE 2 SHAPE 3 TANK DIMENSION DIM 0 DIM 1 DIM 2 DIM 3 DIM 4 DIM 5 DIMx V M TABLE VIEW EDIT TABLE ADD ITEM DELETE ITEM BA...

Страница 32: ...1G Ex ia IIB T6 T4 Ga II 1 2 D Ex ia IIIC T85 C T110 C Da Db II 1 2 D Ex ta tb IIIC T85 C T110 C Da Db Li 200 H Ci 16nF Ui 30V Ii 140mA Pi 1W II 1G Ex ia IIB T6 T3 Ga II 1 2 D Ex ia IIIC T85 C T180 C...

Страница 33: ...inst rare occurring impacts and friction effects that may be source of a potential ignition Meeting the requirements of the technical process Please carefully consider that all parts of the instrument...

Страница 34: ...cess temperature 30 100 C up to max 2 min 120 C with PP antenna enclosure max 80 C 30 180 C Maximal medium pressure 25 bar at 120 C with plastic antenna enclosure or plastic flange 3 bar at 25 C Ambie...

Страница 35: ...RT with display high temp without DA 1 4 20 mA HART with display high temp ATEX DI 1 4 20 mA HART with display high temp IECEx 0 without Y 2 special version acc to description B horn antenna DN50 2 0...

Страница 36: ...thout Y 1 special version acc to description Y1 special cable length max 30 m B horn antenna DN50 0 2 23 m R90 BSP R9P 1 BSP connection with PP enclosure R9T 1 BSP connection with PTFE enclosure N90 N...

Страница 37: ...2 NPT 1 BSP 1 NPT 2 BSP 2 NPT Beam angle 3 dB 19 16 19 16 Dead zone Lmin 200 mm 200 mm 200 mm 200 mm Under reference conditions Aluminium housing 1 antenna with PP enclosure Plastic housing 1 PP encap...

Страница 38: ...200 mm 200 mm 300 mm 300 mm Under reference conditions Aluminium housing 2 Tri Clamp antenna with PTFE enclosure hygienic version Plastic housing 2 Tri Clamp antenna with PTFE enclosure hygienic versi...

Страница 39: ...6 6 Dead zone Lmin 200 mm 200 mm 200 mm 200 mm Under reference conditions High temperature version aluminium housing 1 horn antenna High temperature version aluminium housing 2 horn antenna High temp...

Страница 40: ...equirements EN 302372 1 2017 Electromagnetic compatibility and Radio spectrum Matters ERM Short Range Devices SRD Equipment for Detection and Movement Tanks Level Probing Radar TLPR operating in the f...

Страница 41: ...EN 61010 1 2010 Safety requirements for electrical equipment for measurement control and laboratory use Part 1 General requirements EN 302372 1 2017 Electromagnetic compatibility and Radio spectrum M...

Страница 42: ...ve 2014 53 EU RED Directive 2014 34 EU ATEX Quality Management Production Certificate number BVS 21 ATEX ZQS E110 Notified body DEKRA Exam GmbH Identification number 0158 2011 65 EU RoHS 2015 863 EU D...

Страница 43: ...NRM NRM K06 0422 page 43 20 ATEX certificate...

Страница 44: ...NRM page 44 NRM K06 0422...

Страница 45: ...NRM NRM K06 0422 page 45...

Страница 46: ...NRM page 46 NRM K06 0422...

Страница 47: ...NRM NRM K06 0422 page 47...

Страница 48: ...NRM page 48 NRM K06 0422...

Страница 49: ...NRM NRM K06 0422 page 49...

Страница 50: ...NRM page 50 NRM K06 0422 21 IECEx certificate...

Страница 51: ...NRM NRM K06 0422 page 51...

Страница 52: ...NRM page 52 NRM K06 0422...

Отзывы: