Kobold NMC Скачать руководство пользователя страница 9

NMC 

DT0305 

 

Page 9 

 

Pressing (+), we enter in Output adjustment menu. 

 

This asks, where do you want the NMC gives us mA. If 
you want it in 0 % of the probe. Using (+) and (-) we 
indicate this value in the display. Confirm with (OK) 

 

We do the same for the 20 mA. In this case, if we want 
this current in the 100 % of the probe, we will indicate 
this value using (+) and (-). Confirm with (OK) 

 

Finished the adjustment, we can incorporate a filter to 
avoid oscillations caused by quick movements of the 
liquid’s surface. This value between 0 and 5 (maximum 
filter). Confirm with (OK) 

 

Automatically return to output menu. 
Pressing ESC return to measuring mode. 

 

In this point, the NMC is adjusted. The number in % 
indicates the height that reaches the level in the probe 
(0 to 100). The value of the current will depend of the 
adjustment of the points 3 and 4 of this section, and it 
can be in any point of the probe. It can be in maximum 
point and in the 20 mA at the minimum. 

 
 

9.3 Output simulate 

 

Pressing any key, you enter in the main menu. 
Press (+) to enter in Output. 

Содержание NMC

Страница 1: ...Operating instructions for Capacitive level transmitter Model NMC 2 Wire 4 to 20mA...

Страница 2: ...Instructions ATEX 13 11 1 Validity 13 11 2 General considerations 13 11 3 Protection against ESD electrostatic discharges 13 11 4 Chemical resistance 13 12 Installation in classified zone ATEX 14 13 L...

Страница 3: ...maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health Safety and prevention of accidents When used in machines the m...

Страница 4: ...different given that the kind and the measures of the tank and the products that it contains change every unit must to be adjusted to be adapted to each tank and product Using the menus of the NMC th...

Страница 5: ...tween the probe and the tank s wall Electronic of the NMC unit should be protected with shelter against development of too high temperature by direct sunshine Be ensured that the connection to the tan...

Страница 6: ...NMC Page 6 DT0305 8 Electrical connection The maximum resistance of the line in serial depends on the power supply These values have to be bear in mind for the good run of the NMC...

Страница 7: ...he lowest level If for example when you adjust the low level the level of the tank is the 0 of the capacitance we will indicate it in the display using the and keys Confirm with OK In this moment the...

Страница 8: ...perations to calibrate the maximum level of the unit This operation takes some seconds The display shows this message to indicate NMC has finished the calibration internal process When the liquid leve...

Страница 9: ...r to avoid oscillations caused by quick movements of the liquid s surface This value between 0 and 5 maximum filter Confirm with OK Automatically return to output menu Pressing ESC return to measuring...

Страница 10: ...current testes without generator Pressing OK return to menu show in point 2 Pressing ESC return to read mode 9 4 Language Pressing any key you enter in the main menu Press to enter in Output Pressing...

Страница 11: ...m Medium temp standard 20 90 C NMC H 20 200 C Max pressure 1 30 bar Media DC value r min 1 5 Materials Housing Polycarbonate Connection St steel 1 4305 NMC N NMC T NMC H PVDF NMC S Probe St steel with...

Страница 12: ...ture range 10 2 Process pressure range 20 20 60 100 20 0 20 60 90 200 AMBIENT TEMPERATURE PROCESS TEMPERATURE Model H Model standard 0 5 10 15 20 25 30 35 20 0 20 60 90 200 PROCESS PRESSURE BAR PROCES...

Страница 13: ...ndations regarding installations in explosive zones as well as the instructions of this safety manual must be followed Verify that all data in the label of the instrument fits the installation require...

Страница 14: ...d with the housing in zone 21 22 dust and 1 2 for Gas category 2 or NOT CLASSIFIED Process connection is mounted in the border wall between areas of category 2 and 1 Probe can be mounted in ZONE 20 21...

Страница 15: ...e EMC2014 30 EU LVD2014 35 EU Atex2014 34 EU RoHS2011 65 EU Normas armonizadas y documentos de la normativa aplicados Applied harmonised standards and normative documents Angewandte harmonisierte Norm...

Страница 16: ...Europeas To which this declaration relates is in conformity with the following European Directives Mit folgenden Richtlinien konform ist auxquels se r f re cette d claration ils sont conformes aux Dir...

Страница 17: ...ity with the standards noted below BS EN 61010 1 2010 Safety requirements for electrical equipment for measurement controL and laboratory use General requirements BS EN 61000 6 2 2019 Electromagnetic...

Страница 18: ...NMC Page 18 DT0305 17 ATEX Certified...

Страница 19: ...NMC DT0305 Page 19...

Страница 20: ...NMC Page 20 DT0305...

Страница 21: ...NMC DT0305 Page 21...

Страница 22: ...NMC Page 22 DT0305...

Страница 23: ...NMC DT0305 Page 23 18 Models...

Страница 24: ...s Version Probe length Mechanical connection ATEX Supply NMC N NMC H NMC T 1 up to 1 meter 2 up to 2 meter 3 up to 3 meter 4 up to 4 meter 2G6 G1 st steel 0 without E ATEX 3 10 35 Vdc NMC S 9G9 G2 PVD...

Страница 25: ...KOBOLD MESURA S L U Avda Conflent N 68 Nave 15 08915 Badalona Tel 34 93 460 38 83 Fax 34 93 460 38 76 E Mail info es kobold com www kobold com Technical data Subject to change without prior notice...

Отзывы: