15
Operating instructions for KME flow meter for compressed air and gases
Secondary addressing:
In addition to primary addressing, the KME flow meter provides the option of secondary address
-
ing. The secondary address uses the fields of identification number, manufacturer, version and
medium. The M-Bus Standard http://www.m-bus.com/files/MBDOC48.PDF describes the exact
sequence of the secondary addressing.
Data transmission:
Factory settings
Adjustable values
Baud rate
2400
600, 1200, 2400, 4800, 9600
Data bits
8
8
Parity
EVEN
None, odd, even
Stop bits
1
1 or 2
Slave address
240
0...254
For several devices on the bus the max. recommended baud rate is 9600.
4.2.2 Modbus rtU (projected)
KME flow meter can be operated in a Modbus RTU network with max. 32 devices. Writing 0 into
the corresponding register will reset the MIN/MAX values and the consumption meter.
For Modbus protocol settings see Application Note Modbus AN0103.
Modbus Map:
register
[DeC]
Protocol
address [HeX]
Measured value
Unit
type
Read registers (function code 0x03 / 0x04)
30501
1F4
Temperature
°C
32-bit float
30503
1F6
Temperature
°F
32-bit float
30507
1FA
Standard flow
Nm/s
32-bit float
30509
1FC
Standard flow
SFPM
32-bit float
30511
1FE
Mass flow
kg/h
32-bit float
30513
200
Mass flow
kg/min
32-bit float
30517
204
Standard volume flow
Nm³/h
32-bit float
30519
206
Standard volume flow
Nm³/min
32-bit float
30521
208
Standard volume flow
l/min
32-bit float
30523
20A
Standard volume flow
l/s
32-bit float
30525
20C
Standard volume flow
SCFM
32-bit float
30529
210
Consumption meter status
m³
64-bit-double
30533
214
Consumption meter status
ft³
64-bit-double
31001
3E8
MIN value temperature
°C
32-bit float
31003
3EA
MIN value temperature
°F
32-bit float
31007
3EE
MIN value standard flow
Nm/s
32-bit float
31009
3F0
MIN value standard flow
SFPM
32-bit float
31011
3F2
MIN value mass flow
kg/h
32-bit float
31013
3F4
MIN value mass flow
kg/min
32-bit float
31017
3F8
MIN value standard volume flow
Nm³/h
32-bit float
31019
3FA
MIN value standard volume flow
Nm³/min
32-bit float
31021
3FC
MIN value standard volume flow
l/min
32-bit float
31023
3FE
MIN value standard volume flow
l/s
32-bit float
31025
400
MIN value standard volume flow
SCFM
32-bit float
31501
5DC
MAX value temperature
°C
32-bit float
31503
5DE
MAX value temperature
°F
32-bit float
31507
5E2
MAX value standard flow
Nm/s
32-bit float
31509
5E4
MAX value standard flow
SFPM
32-bit float
31511
5E6
MAX value mass flow
kg/h
32-bit float
31513
5E8
MAX value mass flow
kg/min
32-bit float
31517
5EC
MAX value standard volume flow
Nm³/h
32-bit float
31519
5EE
MAX value standard volume flow
Nm³/min
32-bit float
31521
5F0
MAX value standard volume flow
l/min
32-bit float
31523
5F2
MAX value standard volume flow
l/s
32-bit float
31525
5F4
MAX value standard volume flow
SCFM
32-bit float