 USER MANUAL CENTRAL HEATING STATION TYPE C32SPV24MEFB; C32SPV31MEFB; C22SPV23MEF

 

 

REV.12.06.2017

 

 

 

      

7 of 19

 

 

8.2

 

Racordul de gaz 

Danger! 

Danger  of  death  by  poisoning  and  explosion  because  of  breeches  in  the  gas  pipes  and  connections  in  case  of 
incorrect installation! 

Installation  of  gas  pipes  is  allowed  to  be  performed  only  by  an  authorized  agent.  During  installation  all  legal 
stipulations, as well as the local regulations of gas distribution companies are to be observed.  

When installing the gas pipe it is essential that it is not tensed so as not to create areas of leakage! 
 

Caution! 
Maximum safety pressure for the gas valve is 60 mbar! Going above this pressure limit may result in damage.  
Work pressure with G20 natural gas functioning must be 20 mbar! 
Gas pressure at the entry into the gas valve if GPL gas is used must be maintained between 30÷37 mbar! 

 

Caution! 
Is is obligatory to istall a pressure regulator on the fuel input circuit, adjusted at 20 mbar. 

 

Caution! 
In  case  parasite  voltage  appears  on  the  gas  pipe,  it  can  be  insulated  by  installing  an  electroinsulating  piece 
(according to the Technical Norms for the planning and execution of natural gas input systems). 

 

Central heating boiler types 

C32SPV24MEFB / C32SPV31MEFB / C22SPV23MEF

 function on 

GN

 natural gas

The gas connecting 

pipe is made of stainless steel with an interior diameter of 16.4 mm. The gas input pipe must not have a diameter smaller than 
that of the gas connecting pipe of the central heating station.  
The fuel input must be done according to applicable legal stipulations. 
 

8.3

 

General directions for the heating installation 

When designing the central heating system, please take in consideration the hydraulic characteristic of the pump that equips 
this boiler model! See chapter 11 for pump characteristic. 

Caution! Before connecting the central heating station carefully wash the entire heating installation! In this way, you 
eliminate  from  the  pipes various  debris  such  as welding  splashes,  scoria,  grummet,  putty,  dirt  or  similar.  Otherwise, 
these substances can form deposits in the heating switcher and can cause damage or malfunctioning. 

 

Caution! 
It is obligatory to install an impurity filter on the return of the thermal circuit installation! 
When installing connecting pipes it is essential for these not to be tensed to avoid creating areas of leakage!  

Maximum working pressure allowed is 3bar.

  

Recommended working pressure is 1.5 bar! 
 

Caution! 

It is forbidden to use the central heating station without thermal agent or partilally filled – danger of explosion! 

It is forbidden to use the central heating station if it is not completely aired! 

 
The  equipment  is  provided  with  a  7l  capacity  and  1  bar  loading  pressure  expansion  vessel.  Before  installing  the  equipment, 
check  whether  this  volume  is  sufficient.  If  not,  an  additional  expansion  vessel  must  be  installed  on  the  aspiration  side  of  the 
pump.   

Caution! 
Check the pressure inside the expansion vessel before commissioning.  
Pressure inside the expansion vessel must be 0.8÷1bar. 

 

8.4

 

General directions for the hot water circuit  

Connect the central heating station to the hot water installation. 

It  is  obligatory  to  install  filters  to  de-harden  the  water  and  a  mechanical  impurity  filter  on  the  cold  water  input 
connecting pipe! 
Caution! 

When installing connecting pipes it is essential for these not to be tensed to avoid creating areas of leakage!  

 

 

 The  apparition  of  pressure  shocks  (input  pressures  higher  than  3-4  bars  in  addition  to  symoultaneously  activating 

quick closing  taps)  can  affect the  components  of  the  hydraulic  circuit  inside  the central  heating  station.  We  recommend  the 
installation of a pressure regulator adjusted to 3-4 bars! 
Damage caused by the apparition of pressure shocks or by the use of higher pressure than recommended on the cold water 
input circuit is not covered by the warranty! 

 

 

We recommend the installation of a pressure regulator! Damage caused by the use of pressure higher than recommended on 
the cold water input circuit is not covered by the warranty! 
It is forbidden to install one-way valves on the the cold water input circuit. 
 

 

The cold water input pipe of the hot water preparation circuit will always be open (closing the network is done only by 

activating the taps at the consumer points) to allow take-over of possible dilatations on this circuit. 
 

Note! 

It  is  recommended  that  the  distance  between  the  hot  water  connecting  pipe  of  the  central  heation  station  and  the 
nearest conumer is minimum 6m of pipe. Otherwiswe, there is always the risk of hot water burns. 

 
 
 

Содержание C22SPV23MEF

Страница 1: ...t depending on the area and the purchase period KÖBER SRL no 25 Vaduri Al Tel 40 233 24 17 46 233 24 19 33 www motan ro KÖBER SRL VADURI BRANCH USER MANUAL GAS BOILER C32SPV24MEFB C32SPV31MEFB C22SPV23MEF Alexandru cel Bun Commune Neam 233 24 19 33 Fax 40 233 24 19 29 eamt 617511 Romania ...

Страница 2: ...aphic context functioning state 11 9 2 7 Graphic context adjustment of functioning parameters 11 9 2 8 Graphic context Service submenu 12 9 3 Central heating station startup 12 9 4 Functioning as waste hot water station WHW 12 9 5 Functioning as heating station HS 12 9 6 Preset functions related to station safety 12 9 7 Setting additional functions 12 9 8 Error signals 13 9 9 Station switch off in...

Страница 3: ...t not be used by people with limited psychological and sensitive capacities including children or by people with no experience or and no knowledge The station provides both heating in closed circuit central heating installations as well as hot water Use for other purposes or for additional purposes other than stipulated is considered inappropriate use The manufacturer is not responsible for possib...

Страница 4: ...rmal circuit 0 5 3 5 bar Maximum pressure on DHW circuit 8 bar Temperature on thermal circuit 30 80 C Temperature on the floor heating system circuit 15 45 C Temperature on domestic hot water circuit 35 55 C Hot water flow t 30 C 10 l min Electric characteristics Input 230VAC 50 Hz Rated power EEI pump 0 2 80 W Construction characteristics Height 700 mm Width 436 mm Depth 306 mm 328 mm 306 mm Weig...

Страница 5: ...ly in rooms with maximum 60 humidity between 20 30 C in order to prevent the damaging of electronic components Caution The burning air of the station must not contain substances such as flourine vapours chlorine sulphur dissolvants colorants adhesives or gasoline These substances can lead in time to the corrosion of the equipment and air gas incoming outgoing pipes Legend A Thermal input connector...

Страница 6: ...allation of the central heating station in the proximity of a swimming pool washing machine or cleaner can result in the contamination of the burning air with these compounds Water pH must be within the following limits 7 5 pH 9 5 It is recommended to check the water and thermal agent pH frequently and if the value does not fall within the limits provided by the manufacturer it will be treated aga...

Страница 7: ...filter on the return of the thermal circuit installation When installing connecting pipes it is essential for these not to be tensed to avoid creating areas of leakage Maximum working pressure allowed is 3bar Recommended working pressure is 1 5 bar Caution It is forbidden to use the central heating station without thermal agent or partilally filled danger of explosion It is forbidden to use the ce...

Страница 8: ...ions must comply with applicable norms Connection to the electric grid of the building must allow the entire electric insulataion of the central heating station for situations when interventions are required Grid connection is done taking into account the symbolism of colours as follows Brown phase Blue null Green and Yellow earthing The current plug must be accessible so that the user can easily ...

Страница 9: ...damage of the main switch of the station Incorrect airing of the installation can cause damage of the main heating switch Note Recommended pressure on the thermal circuit is 1 5 bars Emptying the central heating station Emptying of the station implies the following turn off the station by pressing Power si switch off the electric power close the gas tap close the thermal tap and the cold water inp...

Страница 10: ...parameter in the installation submenu Used to decrease the set temperature on hot water circuit or the value parameter in the installation submenu Used to switch the station on off Used to reset the electronic control board from an error state Used to change the functioning mode winter summer Used to activate deactivate the light on the display Description of graphic symbols in the LCD display Des...

Страница 11: ...tallation is 1 4 bar working mode is summer and the temperature in the installation is 17 C 9 2 6 Graphic context functioning state This state is associated with the presence of flame or the functioning of the circulation pump of the station In this state all the activating state elements of the central heating station are active and the burning request is accepted The display shows the delivered ...

Страница 12: ...HW request has priority over the heating request in the winter mode The station can function as instant WHW or as accumulation boiler WHW the boiler is functioning of the station as an accumulation boiler WHW station please contact an authorised service company In intant regime the minimum flow of hot water detected by the station is 2 4 l min For confort in using the station as a WHW station we r...

Страница 13: ...ESET E25 YES BCU malfunction Manually resettable by pressing RESET E30 YES Malfunctioning burnt gases sensor Manually resettable by pressing RESET E31 NO Malfunctioning thermal input sensor Manually resettable by pressing RESET when the cause disappears E32 NO Malfunctioning thermal output sensor Manually resettable by pressing RESET when the cause disappears E35 NO Malfunctioning external tempera...

Страница 14: ...is signed table 2 by which the user signs that they are aware of the correct way of using the central heating station This statement is also signed by the authorized person who commissioned the central heating station The authorised person who commissions the station has the right to refuse to sign the station commissioning statement if they notice defects of the local connecting installations and...

Страница 15: ...B C32SPV31MEFB C22SPV23MEF REV 12 06 2017 15 of 19 11 Drawings necessary for mounting and installation 11 1 Types of configurations for mounting for mural central heating stations with forced flue C32SPV24MEFB C32SPV31MEFB C12 C22 C32 C72 C82 C42 C52 C62 ...

Страница 16: ...e 300mm B distance over the window ventilation hole 300mm C distance left right to the window ventilation hole 300mm D E distance from the roof gutter 250mm F distance from the garage roof balcony 250mm G distance to vertical gutter 250mm H distance to internal external corners 250mm H distance to windows doors 300mm I distance to ground balcony 300mm J distance over the door 600mm L distance to t...

Страница 17: ...c curve Pump error codes If the pump has detecte one or more errors the bi colour LED 1 changes from green to red When an error is active LEDs indicate the type of error as presented in table 7 If more alarms are active at the same time LEDs show the rror with the highest priority Tab 7 Pump error codes 11 5 Hydraulic characteristic of non ER P pump Q PUMP FLOW mc h Display Meaning Pump action Rep...

Страница 18: ...32SPV31MEFB C22SPV23MEF REV 12 06 2017 18 of 19 11 6 Functioning schemes covered by warranty 11 6 1 Central heating with radiators and instant preparation of domestic hot water 11 6 2 Underfloor central heating and instant preparation of domestic hot water ...

Страница 19: ...SPV31MEFB C22SPV23MEF REV 12 06 2017 19 of 19 11 6 3 Central heating with radiators and accumulated preparation of domestic hot water accummulation boiler 11 6 4 Underfloor central heating and accumulated preparation of domestic hot water accummulation boiler ...

Отзывы: