Ambient temperature
-5 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
Outputs
Contact type
µ contact, monostable
Switching voltage
AC 250 V ~
Switching current AC1
16 A
Fluorescent lamps
16 AX
Current carrying capacity
Neighbouring outputs
Σ 20 A
Device
Art. No. 2304.16 REG HE
Σ 40 A
Art. No. 2308.16 REG HE
Σ 80 A
Art. No. 2316.16 REG HE
Σ 160 A
Loads per output
Ohmic load
3000 W
Capacitive load
max. 16 A (140µ)
Motors
1380 VA
Switch-on current 200 µs
max. 800 A
Switch-on current 20 ms
max. 165 A
Lamp loads
Incandescent lamps
3000 W
HV halogen lamps
2500 W
LV halogen lamps with Tronic transformer
1500 W
LV halogen lamps with inductive transformer
1200 VA
Fluorescent lamps T5/T8
uncompensated
1000 W
parallel compensated
1160 W (140 µF)
Duo circuit
2300 W (140 µF)
Compact fluorescent lamps
uncompensated
1000 W
parallel compensated
1160 W (140 µF)
Mercury vapour lamps
uncompensated
1000 W
parallel compensated
1160 W (140 µF)
Connections supply and load
Connection mode
Screw terminal
single stranded
0.5 ... 4 mm²
finely stranded without conductor sleeve
0.5 ... 4 mm²
finely stranded with conductor sleeve
0.5 ... 2.5 mm²
Fitting width
Art. No. 2304.16 REG HE
72 mm / 4 modules
Art. No. 2308.16 REG HE
72 mm / 4 modules
Art. No. 2316.16 REG HE
144 mm / 8 modules
Weight
Art. No. 2304.16 REG HE
approx. 250 g
Art. No. 2308.16 REG HE
approx. 290 g
Art. No. 2316.16 REG HE
approx. 460 g
KNX
KNX medium
TP 1
Commissioning mode
S-mode
Rated voltage KNX
DC 21 ... 32 V SELV
Power consumption KNX
typical 150 mW
Connection type for bus
Connection terminal
6.2 Troubleshooting
Manual control with button field not possible
Cause 1: Manual control has not been programmed.
Program manual control.
9/11
82560023
J:0082560023
05.08.2013
Switch actuator / blinds actuator