Fig. 2 
 
 
 
 
 

 

Remove one or more of the pre-fitted blank plugs as required by pushing out from the inside and install 

a suitable IP rated gland or adaptor (not supplied). For rear entry, cut or drill a 20/25mm hole where 

marked and install a suitable IP rated grommet (not supplied). Unused cable entries must have the 

blank plugs fitted 

 

Feed the mains cable into the unit and secure the base plate to the surface. The fixing holes are 

slotted to allow some rotational adjustment 

 

Replace the gasket onto the backbox, then wire as shown in Fig. 3 ensuring that correct polarity is 

observed: L - Live (brown), E - Earth (green/yellow), N - Neutral (blue)  

 
 
 
 
 
Fig. 3 
 
 
 
 
 
 
 
 
 

 

An earth connection must be made to the earth terminal of the socket. Use green/yellow sleeving on 

earth conductors that are not insulated. The earth terminal in the backbox is provided for convenience 

and does not need to be connected

 

 

Check all electrical connections are secure with no loose strands of cable

 

 

Ensuring the gasket does not become damaged or pinched, fit the socket assembly onto the backbox, 

taking care not to compress, damage or trap any cables, and secure with the screws provided - do not 

overtighten

 

 

Fit screw covers

 

 

Switch on and check for correct operation   

 

• The backbox has drain hole drilling guides marked (see Fig. 2). Drilling a drain hole is 
   advised if the unit is installed in a location subject to temperature fluctuations where a 
   build-up of condensation may occur. It is not advised if the unit will be subject to high 
   pressure jets as drilling a drain hole will reduce the IP rating. A 3-5mm hole should be 
   drilled at the bottom back edge of the enclosure where marked. If wiring in conduit to the 
   bottom entry, the drain hole should be drilled at the lowest point of the conduit run 
   not in the backbox

Fig. 2

Содержание OP9R

Страница 1: ...INSTALLATION MAINTENANCE MANUAL OP9R...

Страница 2: ...671 and current Building Regulations If in any doubt consult a qualified electrician Please isolate mains prior to installation or maintenance Check the total load on the circuit including when this p...

Страница 3: ...1 Using the backbox as a template mark the location for and drill the fixing holes ensuring not to infringe with any gas water pipes or electrical cables INSTALLATION Note the unit should be fixed to...

Страница 4: ...the backbox then wire as shown in Fig 3 ensuring that correct polarity is observed L Live brown E Earth green yellow N Neutral blue The backbox has drain hole drilling guides marked see Fig 2 Drilling...

Страница 5: ...h conductors that are not insulated The earth terminal in the backbox is provided for convenience and does not need to be connected Check all electrical connections are secure with no loose strands of...

Страница 6: ...ch on and check for correct operation For security and to prevent unwanted tampering with the product a lug feature with a 6mm hole is provided to accept a padlock or similar locking security device n...

Страница 7: ...mote and take out the PCB Remove the old batteries and insert two new CR2016 batteries see Fig 4 Fig 4 WARNING To ensure continued safe and proper weatherproof operation the unit must not be left with...

Страница 8: ...cessories reserve the right to alter product specification without prior notice GENERAL This product should be recycled in the correct manner when it reaches the end of its life Check local authoritie...

Страница 9: ...15 863 RoHS 2021 341 ERP Safety Standards Full individual declarations and specific safety standards applicable to relevant product series can be found on our website www mlaccessories co uk We hereby...

Страница 10: ...o 1095 The Ecodesign for Energy Related Products and Energy Information Lighting Products Regulations 2021 Included Legislation UK SI 2008 No 2852 UK REACH UK SI 2013 No 3113 WEEE Safety Standards Ful...

Страница 11: ...Manufacturer ML Accessories Ltd Unit E Chiltern Park Boscombe Road Dunstable LU5 4LT www mlaccessories co uk EU Authorised Representative nnuks Holding GmbH Niederkasseler Lohweg 18 40547 D sseldorf G...

Отзывы: