![Knightsbridge BF1430EMS Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/knightsbridge/bf1430ems/bf1430ems_installation-and-maintenance-manual_1980442004.webp)
WARNING
This luminaire must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
• The additional terminal called Slave Live (SL) is available to enable the sensor to power on additional
luminaires. A max. LED load of 500W can be controlled by the sensor
• Adjust sensor settings as required
• Ensure the battery is connected via the plug and socket to the emergency inverter
• Refasten the LED plate screws
• Reattach the diffuser by rotating clockwise
• Switch on and check for correct operation, ensuring the green indicator LED is illuminated
• We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying
out an emergency duration test
• If the batteries have been left in a discharged state for an extended period, we recommend that one or more
charge and discharge cycles are completed which should help to restore the battery capacity
SENSOR LAYOUT
•
The additional terminal called Slave Live (SL) is available to enable the sensor to power on additional
luminaires. A max. LED load of 500W can be controlled by the sensor
•
Adjust sensor settings as required
•
Ensure the battery is connected via the plug and socket to the emergency inverter
•
Refasten the LED plate screws
•
Reattach the diffuser by rotating clockwise
•
Switch on and check for correct operation, ensuring the green indicator LED is illuminated
•
We recommend, on commissioning the installation, a minimum charge period of 24 hours before
carrying out an emergency duration test
•
If the batteries have been left in a discharged state for an extended period, we recommend that one or
more charge and discharge cycles are completed which should help to restore the battery capacity
SENSOR LAYOUT
WARNING
This luminaire must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
This product contains an LED light source which can be replaced by the end user and a control gear which can
be replaced by a professional.
Clean the external surfaces with a damp cloth using a mild solution of detergent and warm water only, do not
use aggressive cleaning products or solvents which may damage the product.
Do not use any source of high-pressure washers to maintain or clean this luminaire.
This product is non-dimmable.
This product should be dismantled for disposal when it reaches the end of its life. Please see website for
dismantling instructions.