0900455 Rev: F (06/02)
Page 13 of 20
This feature is designed for applications where the Multi-Flow
remote control is used with an On-Premise (OP) or On-Premise
Plus (OPP) pump unit. It allows the Multi-Flow control to
compensate for multiple pumps running simultaneously. This
overcomes the slight drop in pump speed, and ensures that the
programmed dosages are properly injected.
This feature is available for use with normal operation or drain
mode only (not used with relay mode). It is not necessary to re-
program the dispenser, and all other pump functions will still work
in their normal manner. The software will automatically extend the
run time of the pumps in the following ways:
1 pump running — no effect, the pump will run its normal time.
2 pumps running — the run time counting down on the display
will appear normal, but the
actual time that the pumps run will be
increased by 10%.
3 pumps running — the run time counting down on the display
will appear normal, but the
actual time that the pumps run will be
increased by 20%.
This feature only affects the pumps while they are running
simultaneously. For example, if two pumps begin running at the
same time, but one finishes before the other, then the pump that
is still running will finish its remaining time without compensation.
Use INC/DEC to turn this feature on or off, then press MENU
to
continue.
DC PUMP COMP=OFF
INC / DEC
This selection allows you to determine the appropriate length of a
valid supply signal from the washer. Supply signals must be of a
duration that matches the minimum setting to activate any pump
in the system, or start a pump delay.
Use the SCROLL and INC/DEC buttons to choose a signal qualify
time of 1 to 255 seconds, then press ENTER. Press MENU
to
continue.
NOTE: The factory default setting is 5 seconds.
SIGNAL QUALIFY
=005 SEC (1-255)