KMC Controls STE-6012 Скачать руководство пользователя страница 4

STE-6012/6016 Room Temperature Sensors 

Application Guide, AN0412C Rev. B

back to 7.5 VDC.

 See, for example, the 

Control Basic example in the Override 

section below.

  1. In the BACstage software main menu, select 

Objects

 > 

Outputs

.

  2. Click 

Edit

.

  3. Type in a name in the appropriate 

Description

 

field and/or 

Name

 field.

  4. Select 

Object Type: Analog

 if it is not the default.

  5. Select 

Device Type: Volts 0–10

.

NOTE:  This only sets the scale; the actual voltage 

may go up to 12 volts DC.

  6. Click 

End Edit

.

  7. Click 

Yes

 for “Send Update Notification Now?”

  8. Click 

OK

.

Override

  1. In the BACstage software main menu, select 

Objects

 > 

Binary

 Values

.

  2. Click 

Edit

.

  3. Type in a name in the appropriate 

Description

 

field and/or 

Name

 field (see Control Basic 

example).

  4. Click in the 

Units

 column and select 

Off/On

 (or 

No/Yes

Stop/Start

Disabled/Enabled

Inactive/Active

 

according to preference).

  5. Click 

End Edit

.

  6. Click 

Yes

 for “Send Update Notification Now?”

  7. Click 

OK

.

  8. In the BACstage software main menu, select 

Objects

 > 

BASIC Programs

.

  9. Click 

Edit

.

10. Type in a name in the 

Description

 field and/or 

Name

 field.

11. Click 

Autorun

.

12. Click 

End Edit

.

13. Click 

Yes

 for “Send Update Notification Now?”

14. Click once in the

 #

 column.

15. Type in program lines (see the following 

example).

NOTE:  This is only an example. Details need to fit 

the controller configuration.

10 REM ** STE-6012/6016 OVERRIDE **

20 REM ** AI1 IS STE-6012/6016 

TEMPERATURE SENSOR INPUT **

30 REM ** BV3 IS OCCUPIED/UNOCCUPIED 

(ON/OFF) MODE **

40 

IF NOT 

BV3 

THEN 

AO1@9 = 7.5 

ELSE 

AO1@9 = 12 : 

REM ** AO1 IS SUPPLY 

VOLTAGE TO SENSOR **

50 

IF NOT 

BV3 

THEN GOSUB 

70

60 

END

70 REM ** OVERRIDE SUBROUTINE DURING 

UNOCCUPIED MODE **

80 REM ** PUSH UP OR DOWN BUTTON TO 

START OVERRIDE MODE (BV2) **

90 

IF

+ SENSOROFF( AI1 ) 

OR 

SENSORON( 

AI1 ) 

THEN START 

BV2

100 REM ** CHANGE DEFAULT TIMEON TO 

DESIRED AMOUNT OF OVERRIDE TIME **

110 

IF 

TIMEON( BV2 ) > 02:00:00 

THEN 

GOTO 

120 

ELSE GOTO 

140

120 

STOP 

BV2 : AO1@8 = 12 : 

REM ** 

REMOVES OVERRIDE DISPLAY FROM LCD 

SCREEN **

130 

WAIT 

0:00:04 : 

RLQ 

AO1@8

140 

RETURN

16. Click 

Send

.

17. Click 

OK

.

18. Click 

Yes

 for “Execute Program Now?”

19. Click 

Close

.

20. Click 

OK

.

TotalControl Software

NOTE:  Follow the relevant hardware instructions 

in the BACstage Software section (above) or 

KMDigital Software section (starting on the 

next page). Then see the TotalControl Help 

information for the equivalent software 

configuration in TotalControl.

Содержание STE-6012

Страница 1: ...ottom of the STE 6016 case is an EIA 485 formerly RS 485 computer port This port provides a temporary connection to the digital network for network setup or troubleshooting To use the port to connect to a computer a means of converting the EIA 485 signal to a USB or EIA 232 formerly RS 232 signal will be needed The exact connection depends on the computer and the opera tor workstation software See...

Страница 2: ...Controller Configuration section Fahrenheit Celsius Display Selection The STE 6012 6016 has an LCD display for showing room temperature and setpoint The display can be toggled between Fahrenheit the default and Celsius scales by performing the following procedure NOTE Doing this erases any stored calibration offset value see below and returns the calibration to the default setting 1 Press and hold...

Страница 3: ...ied the sensor is in setback unoccupied mode with 12 VDC applied the sensor is in normal occupied mode Pressing the Down button momentarily sends 0 VDC to the controller for a SENSORON signal on terminal C or orange wire pressing the Up button sends greater than 5 VDC for a SENSOROFF signal Pressing a button raises or lowers the setpoint voltage When in unoccupied mode pressing either button selec...

Страница 4: ...ield and or Name field 11 Click Autorun 12 Click End Edit 13 Click Yes for Send Update Notification Now 14 Click once in the column 15 Type in program lines see the following example NOTE This is only an example Details need to fit the controller configuration 10 REM STE 6012 6016 OVERRIDE 20 REM AI1 IS STE 6012 6016 TEMPERATURE SENSOR INPUT 30 REM BV3 IS OCCUPIED UNOCCUPIED ON OFF MODE 40 IF NOT ...

Страница 5: ...SE GOTO 190 170 STOP VAR4 180 OUT3 12 WAIT 0 00 02 190 RETURN 8 Click Send 9 Click OK 10 Click Close 11 Click OK NOTE See also the Override section below and Setpoint Voltage Input and Variable on page 6 NOTE For another sample application of program ming override timers adapt the informa tion in the Application Note AN0504F Programming Override Timers section of the Digital Designer s Guide SP 02...

Страница 6: ...nu select Control Setpoint Variables 11 Click Edit 12 Type in a name in the Description field and or Label field 13 Click Units which opens the Configure Variables screen 14 Select Type Analog if it is not the default 15 Select Degrees Fahrenheit or Celsius 16 Set Format to 0 17 Click OK 18 Click End Edit 19 Click OK NOTE See also Control Basic Setpoint Calculation and Override on page 5 Setpoint ...

Страница 7: ...field and or Label field 4 Select Units 5 Select Type Analog if it is not the default 6 Select 0 10 Volts 7 Leave the rest of defaults 8 Click OK 9 Click End Edit 10 Click OK BAC A1616BC BACnet Building Controller Tables and Jumpers Select the 0 12 VDC jumper position for the corre sponding inputs See the Installation section of the BAC A1616ABC Building Controller Installation and Operation Guide...

Страница 8: ...users or returns Exposed to air flow through the conduit from leaks in plenum ducts put plumber s putty or similar material inside the conduit to block air flow Setpoint Input 1 In the desired Analog Input setup screen of the web page interface select Device Type of 0 5 volts 2 Select the Lookup Table for the STE 6012 Setpoint BBC table 3 For the Fahrenheit scale the multiplier is 1 8 and the offs...

Страница 9: ...curacy 0 36 F 0 20 C Resistance 10 000 ohms 77 F 25 C NTC 4 37 C 25 C Dissipation Constant 2 mW C Temp Reading 0 5 VDC voltage output Front Buttons Two momentary push buttons that signal override condition adjust setpoint toggle C or F and calibrate temperature reading Power Requirements7 5 VDC 10 4 mA max cur rent draw for unoccupied setback mode or 12 VDC 9 7 mA for occupied normal mode Approval...

Отзывы: