STE-6012/6016 Room Temperature Sensors 

Application Guide, AN0412C Rev. B

Overview

Each STE-6012/6016 includes an LCD display for 

the room temperature and setpoint, which can be 

toggled between Fahrenheit (the default) and Celsius 

scales. The sensor allows a user to adjust the setpoint 

via the Up and Down arrow buttons on the front 

panel.

If the system is in 

occupied/normal mode (12 VDC 

applied to terminal D or the green wire)

, press-

ing a button will raise or lower the setpoint. When 

either button is pushed, the display will toggle from 

room temperature to the setpoint. The setpoint will 

increment or decrement (a degree with each press) 

depending on the button being pressed. When the 

button is released, the number displayed is the new 

setpoint, and the display will return to room tem-

perature after ten seconds.

If the system is in 

unoccupied/setback (for heating 

or setup for cooling) mode (7.5 VDC applied to 

terminal D or the green wire)

, pressing either but-

ton also selects override mode (and “OVERRIDE” is 

shown on the LCD display).

NOTE:  Pressing the 

 

Down button

 momentarily 

sends 

0 VDC

 to the controller (via the 

C terminal or the orange wire) for a 

SENSORON

 signal; pressing the 

 

Up 

button

 sends 

greate

r than 5 VDC

 for a 

SENSOROFF

 signal.

Controller Connection

For the STE-6012/6016, the 

controller

 will need signal 

lines for two inputs (thermistor and setpoint), one 

output (7.5/12 VDC supply), and common (ground).

Since each STE-6012/6016 has 0–5 volt DC outputs 

for both the temperature and the setpoint lines, 

turn OFF the corresponding 10,000 ohm pull-up re

-

sistors on the controller board!

 Consult the control-

ler’s setup instructions for information on turning off 

the pull-up resistors. (For the other STE-6000 series 

sensors, do 

not

 turn off the resistors on the controller 

board as stated for the STE-6012/6016.)

NOTE: 

For controller configuration instructions, 

see the appropriate section in the Controller 

Configuration section.

Fahrenheit/Celsius Display Selection

The STE-6012/6016 has an LCD display for showing 

room temperature and setpoint. The display can be 

toggled between Fahrenheit (the default) and Celsius 

scales by performing the following procedure.
NOTE:  Doing this 

erases any stored calibration 

offset value

 (see below) and returns the 

calibration to the default setting!

1.  Press and hold either the Down or Up arrow 

buttons for at least 20 seconds. The display will 

toggle from one temperature scale to the other.

2.  Release the button.
NOTE:  This setting is written to nonvolatile 

memory and will be saved even if power to 

the sensor is lost.

Displayed Temperature Calibration (Offset)

NOTE:  The total offset value is limited to +/– 3 

degrees from the default value.

The temperature value displayed by the STE-

6012/6016 may be fine-tuned if desired by 

performing the following steps. The sensor must be 

in a stable location and operating at least ten minutes 

before calibrating. Hold an accurate thermometer 

about an inch under the unit as a reference during 

this procedure.

1.  Click the Down arrow button to decrement the 

setpoint to its lowest value, 40° Fahrenheit or 4° 

Celsius, then press and hold the Down arrow 

button.

2.  After holding the Down arrow button for about 

ten seconds, the display will start flashing 

the room temperature value and start an 

approximately 15-second “exit calibration” timer.

NOTE:  Entering the calibration mode erases any 

previous saved offset value and will return 

to the default setting.

3.  While the room temperature value is flashing, 

press the Up or Down arrow button to modify the 

room temperature value. Each press of the Up or 

Down arrow button will change the temperature 

value by one degree.

4.  The display will continue to flash for approxi

-

mately 15 seconds after the last button press. 

Then the STE-6012/6016 will write the modified 

value to memory and return to normal operation.

NOTE:  This procedure affects only the temperature 

displayed on the LCD screen. It does 

not

 

affect the calibration or temperature value 

in the controller.

Sensor Configuration

Содержание STE-6012

Страница 1: ...ottom of the STE 6016 case is an EIA 485 formerly RS 485 computer port This port provides a temporary connection to the digital network for network setup or troubleshooting To use the port to connect to a computer a means of converting the EIA 485 signal to a USB or EIA 232 formerly RS 232 signal will be needed The exact connection depends on the computer and the opera tor workstation software See...

Страница 2: ...Controller Configuration section Fahrenheit Celsius Display Selection The STE 6012 6016 has an LCD display for showing room temperature and setpoint The display can be toggled between Fahrenheit the default and Celsius scales by performing the following procedure NOTE Doing this erases any stored calibration offset value see below and returns the calibration to the default setting 1 Press and hold...

Страница 3: ...ied the sensor is in setback unoccupied mode with 12 VDC applied the sensor is in normal occupied mode Pressing the Down button momentarily sends 0 VDC to the controller for a SENSORON signal on terminal C or orange wire pressing the Up button sends greater than 5 VDC for a SENSOROFF signal Pressing a button raises or lowers the setpoint voltage When in unoccupied mode pressing either button selec...

Страница 4: ...ield and or Name field 11 Click Autorun 12 Click End Edit 13 Click Yes for Send Update Notification Now 14 Click once in the column 15 Type in program lines see the following example NOTE This is only an example Details need to fit the controller configuration 10 REM STE 6012 6016 OVERRIDE 20 REM AI1 IS STE 6012 6016 TEMPERATURE SENSOR INPUT 30 REM BV3 IS OCCUPIED UNOCCUPIED ON OFF MODE 40 IF NOT ...

Страница 5: ...SE GOTO 190 170 STOP VAR4 180 OUT3 12 WAIT 0 00 02 190 RETURN 8 Click Send 9 Click OK 10 Click Close 11 Click OK NOTE See also the Override section below and Setpoint Voltage Input and Variable on page 6 NOTE For another sample application of program ming override timers adapt the informa tion in the Application Note AN0504F Programming Override Timers section of the Digital Designer s Guide SP 02...

Страница 6: ...nu select Control Setpoint Variables 11 Click Edit 12 Type in a name in the Description field and or Label field 13 Click Units which opens the Configure Variables screen 14 Select Type Analog if it is not the default 15 Select Degrees Fahrenheit or Celsius 16 Set Format to 0 17 Click OK 18 Click End Edit 19 Click OK NOTE See also Control Basic Setpoint Calculation and Override on page 5 Setpoint ...

Страница 7: ...field and or Label field 4 Select Units 5 Select Type Analog if it is not the default 6 Select 0 10 Volts 7 Leave the rest of defaults 8 Click OK 9 Click End Edit 10 Click OK BAC A1616BC BACnet Building Controller Tables and Jumpers Select the 0 12 VDC jumper position for the corre sponding inputs See the Installation section of the BAC A1616ABC Building Controller Installation and Operation Guide...

Страница 8: ...users or returns Exposed to air flow through the conduit from leaks in plenum ducts put plumber s putty or similar material inside the conduit to block air flow Setpoint Input 1 In the desired Analog Input setup screen of the web page interface select Device Type of 0 5 volts 2 Select the Lookup Table for the STE 6012 Setpoint BBC table 3 For the Fahrenheit scale the multiplier is 1 8 and the offs...

Страница 9: ...curacy 0 36 F 0 20 C Resistance 10 000 ohms 77 F 25 C NTC 4 37 C 25 C Dissipation Constant 2 mW C Temp Reading 0 5 VDC voltage output Front Buttons Two momentary push buttons that signal override condition adjust setpoint toggle C or F and calibrate temperature reading Power Requirements7 5 VDC 10 4 mA max cur rent draw for unoccupied setback mode or 12 VDC 9 7 mA for occupied normal mode Approval...

Отзывы: