KMC Controls STE-6012 Скачать руководство пользователя страница 1

STE-6012/6016 Room Temperature Sensors 

Application Guide, AN0412C Rev. B

Application Guide

Room Temperature Transmitters (with LCD Display)

STE-6012/6016

 

Models

Model

Number

Connections

Screw Clamp 

Terminals

RJ-45 

Connector

EIA-485 Data 

Port

STE-6012

X

STE-6016

X

X

NOTE:  For more product information, see the 

STE-

6000 Series Room Temperature Sensors/

Transmitters Data Sheet

 on the KMC 

Controls web site.

KMD-5624

Cable

KMD-5576

PC Port Network Connection

NOTE:  For mounting and wiring information, see 

the 

STE-6012/6016 Installation Guide

.

Contents

Models ...........................................................................1
PC Port Network Connection .........................................1
Sensor Configuration ......................................................2

Overview ....................................................................2
Controller Connection ...............................................2
Fahrenheit/Celsius Display Selection ..........................2
Displayed Temperature Calibration (Offset) ...............2

Controller Configuration ................................................3

Overview ....................................................................3
BACstage Software .....................................................3
TotalControl Software ................................................4
WinControl Software..................................................5
BAC-A1616BC BACnet Building Controller ................7

Mounting Considerations ...............................................8
Troubleshooting .............................................................8
Specifications .................................................................9
Accessories ....................................................................9
Important Notices ..........................................................9

At the bottom of the STE-6016 case is an EIA-485 

(formerly RS-485) computer port. This port provides 

a temporary connection to the digital network for 

network setup or troubleshooting.
To use the port to connect to a computer, a means of 

converting the EIA-485 signal to a USB or EIA-232 

(formerly RS-232) signal will be needed. The exact 

connection depends on the computer and the opera-

tor workstation software. (See also the instructions 

included with those devices and software.)

•  For 

USB

 (to WinControl or BACstage), use a 

KMD-5576 USB Communicator (see the illustra

-

tion above).

•  For 

EIA-232 to BACstage

, use a third-party 

interface.

•  For 

EIA-232 to WinControl

, use a KMD-5559 

CommTalk and KMD-5624 cable (or equivalent 

interface).

To access the network through the STE-6016’s port:

1.  Connect the keyed, flat end of the KMD-5624 

interface cable (included with the KMD-5576 but 

not the KMD-5559) to the port on the sensor.

2.  Connect the other end of the cable to the interface 

device that converts the EIA-485 signal into an 

EIA-232 or USB signal.

3.  Connect the suitable cable from the interface 

device to the computer’s serial or USB port. Install 

any required software and configure the port as 

necessary.

Содержание STE-6012

Страница 1: ...ottom of the STE 6016 case is an EIA 485 formerly RS 485 computer port This port provides a temporary connection to the digital network for network setup or troubleshooting To use the port to connect to a computer a means of converting the EIA 485 signal to a USB or EIA 232 formerly RS 232 signal will be needed The exact connection depends on the computer and the opera tor workstation software See...

Страница 2: ...Controller Configuration section Fahrenheit Celsius Display Selection The STE 6012 6016 has an LCD display for showing room temperature and setpoint The display can be toggled between Fahrenheit the default and Celsius scales by performing the following procedure NOTE Doing this erases any stored calibration offset value see below and returns the calibration to the default setting 1 Press and hold...

Страница 3: ...ied the sensor is in setback unoccupied mode with 12 VDC applied the sensor is in normal occupied mode Pressing the Down button momentarily sends 0 VDC to the controller for a SENSORON signal on terminal C or orange wire pressing the Up button sends greater than 5 VDC for a SENSOROFF signal Pressing a button raises or lowers the setpoint voltage When in unoccupied mode pressing either button selec...

Страница 4: ...ield and or Name field 11 Click Autorun 12 Click End Edit 13 Click Yes for Send Update Notification Now 14 Click once in the column 15 Type in program lines see the following example NOTE This is only an example Details need to fit the controller configuration 10 REM STE 6012 6016 OVERRIDE 20 REM AI1 IS STE 6012 6016 TEMPERATURE SENSOR INPUT 30 REM BV3 IS OCCUPIED UNOCCUPIED ON OFF MODE 40 IF NOT ...

Страница 5: ...SE GOTO 190 170 STOP VAR4 180 OUT3 12 WAIT 0 00 02 190 RETURN 8 Click Send 9 Click OK 10 Click Close 11 Click OK NOTE See also the Override section below and Setpoint Voltage Input and Variable on page 6 NOTE For another sample application of program ming override timers adapt the informa tion in the Application Note AN0504F Programming Override Timers section of the Digital Designer s Guide SP 02...

Страница 6: ...nu select Control Setpoint Variables 11 Click Edit 12 Type in a name in the Description field and or Label field 13 Click Units which opens the Configure Variables screen 14 Select Type Analog if it is not the default 15 Select Degrees Fahrenheit or Celsius 16 Set Format to 0 17 Click OK 18 Click End Edit 19 Click OK NOTE See also Control Basic Setpoint Calculation and Override on page 5 Setpoint ...

Страница 7: ...field and or Label field 4 Select Units 5 Select Type Analog if it is not the default 6 Select 0 10 Volts 7 Leave the rest of defaults 8 Click OK 9 Click End Edit 10 Click OK BAC A1616BC BACnet Building Controller Tables and Jumpers Select the 0 12 VDC jumper position for the corre sponding inputs See the Installation section of the BAC A1616ABC Building Controller Installation and Operation Guide...

Страница 8: ...users or returns Exposed to air flow through the conduit from leaks in plenum ducts put plumber s putty or similar material inside the conduit to block air flow Setpoint Input 1 In the desired Analog Input setup screen of the web page interface select Device Type of 0 5 volts 2 Select the Lookup Table for the STE 6012 Setpoint BBC table 3 For the Fahrenheit scale the multiplier is 1 8 and the offs...

Страница 9: ...curacy 0 36 F 0 20 C Resistance 10 000 ohms 77 F 25 C NTC 4 37 C 25 C Dissipation Constant 2 mW C Temp Reading 0 5 VDC voltage output Front Buttons Two momentary push buttons that signal override condition adjust setpoint toggle C or F and calibrate temperature reading Power Requirements7 5 VDC 10 4 mA max cur rent draw for unoccupied setback mode or 12 VDC 9 7 mA for occupied normal mode Approval...

Отзывы: