BAC-10000 Series
5
Operation Guide, Rev. J
Advanced Menu
ADVANCED
APPLICATION
CB PROGRAMS
COMMUNICATION
DATE/TIME
DEVICE
INPUTS
LIMITS
The Advanced Menu displays various submenus.
Not all submenus can be seen on the screen at one
time. Scroll up or down to see additional submenus.
To select the desired submenu, press:
1. Up
/
Down
to move.
2. Enter
to select.
NOTE: The Advanced Menu has more submenus
than can appear on the screen at once. Keep
scrolling up or down to see all the options.
(Advanced) Application Options
APPLICATION
DEGREES SCALE: °F
APP:
OPT: 4-PIPE
ADDITIONAL SETUP
FAN COIL
ADDITIONAL SETUP
DAMPER
FAN
HUMIDITY
SENSORS
VALVE
To change ° F or C, preprogrammed application type,
and options, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Right
/
Left
to move among value fields.
4. Up
/
Down
to increment/decrement value.
The type of application (as well as the model of
FlexStat) affects the context-sensitive options under
Additional Setup.
Auxiliary Heat (Heat Pump Only)
AUX HEAT SETUP
AUX HEAT:
DELAY (MINS): 60
COMP LOCKOUT
Damper Setup
DAMPER SETUP
ECON:
MIN POSITION (%): 10
CNTRL (0–100%): 2–10 V
ECON ENBLE TEMP: 55° F
LOW LIMIT ALARM: 45° F
MODULATING
NOTE: If the Economizer option is selected when
there is no mixed air temperature sensor
connected, a Low Limit Alarm will result.
See
Alarms on page 11
.
Fan Setup
FAN SETUP
SPEEDS:
OFF DELAY (SECS): 180
UNOCC: AUTO
OCC: AUTO
CONSTANT SPEED
NOTE: For a Fan Fail Alarm, see
Sensor Setup on
page 6
and
Alarms on page 11
.
Humidity Setup
HUMIDITY SETUP
DEHUMIDIFICATION
HUMIDIFICATION
DEHUMIDIFICATION
DEHUM:
ALLOW HTG DEHUM: NO
DEHUM SETPT: 60%RH
DEHUM DEADBAND: 5%RH
ENABLE
NOTE: If a dehumidification option is enabled, the
Space Humidity Alarm will also be enabled.
See
Alarms on page 11
.