Operation Guide, Rev. J
System Setup
SYSTEM
SYSTEM ENABLE:
OCC OVRIDE (HRS): 1.0
INACTIVITY (SECS): 60
DISPLAY BLANKING: NO
AUTO
To adjust the system configuration values, such as
system enable (auto, off, heat, or cool), occupancy
override time, and display inactivity time-out:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Up
/
Down
to increment/decrement value.
Occupancy Override on this menu
is the amount of
time (in hours) a manual change in the setpoint (via
the Up and Down buttons) will be allowed to over-
ride the scheduled setpoint.
When the time is set to
0, the override state will last until the next schedule
change.
When Display Blanking is enabled (Y),
the display
turns off at the same time the backlight goes off
(after reset, initial power-up, or time-out). When any
button is pressed, the display will reappear until the
time-out is reached again.
The menu/display/backlight time-out
(seconds
since the last button is pushed) is set in Inactivity.
Access to the Main Menu, setpoint adjust, and
System/Occupancy/Fan override have a default
password level of User. This level can be changed for
each function to None, Operator, or Administrator
through this screen. Passwords are set in the (Ad-
vanced) Passwords menu. See
(Advanced) Security
Levels and Passwords on page 9
.
Trend Viewer
TREND VIEWER
1:
2: SPACE HUMIDITY 27
3: FAN
19
4: COOL 1
18
5: COOL 2
21
6:
7:
SPACE TEMP 34
TL #1 SPACE TEMP
APR11 1:27PM, 70.3
APR11 2:27PM, 71.3
APR11 3:27PM, 71.6
APR11 4:27PM, 71.8
APR11 5:27PM, 76.3
APR11 6:27PM, 81.2
APR11 7:27PM, 82.3
To view trend log buffers, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
Trend logs are set up in the
(Advanced) Trend Logs
menus (see
page 10
).
Setpoints
SETPOINTS
COOL SETPT:
HEAT SETPT: 67° F
COOL SETBACK: 80° F
HEAT SETBACK: 64° F
MIN SETPT DIFF: 2° F
DEADBAND: 2° F
DEHUM SETPT: 60 % RH
74° F
In the Setpoints menu, deadband, setbacks, and
setpoints for various values are set. (The room
temperature setpoint can also be manually changed
from the Home menu.)
To adjust the setpoints, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Up
/
Down
to increment/decrement value.