background image

AppStat For Fan Coil Units

3

Installation Guide

the internal pull-up resistor. An STE-6011W10
sensor is suitable for this application. Follow the
instructions supplied with the sensor for
installation.

When a remote space temperature input is
connected to the AppStat, the remote temperature is
used instead of the internal temperature sensor.

Fan status switch (optional)

Connect a Normally Closed Fan Status switch to the
Discharge Air Temperature (DAT) input and ground
(GND) terminals. The input includes the internal
pull-up resistor. A CSE-1102 differential pressure
switch is suitable for this application. Follow the
instructions supplied with the switch for
installation.

Water temperature sensor

Connect a 10kΩ, Type III thermistor temperature
probe to the water temperature (WST) input. The
input includes the internal pull-up resistor. An
STE-1455 sensor is suitable for this application.
Follow the instructions supplied with the sensor for
installation.

Note:

The water temperature sensor is a required
input sensor for 2-pipe fan coil units.

Discharge air temperature

Connect a 10kΩ, Type III thermistor temperature
probe to the discharge air temperature (DAT) input.
The input includes the internal pull-up resistor. An
STE-1405 sensor is suitable for this application.
Follow the instructions supplied with the sensor for
installation.

Connecting outputs

The AppStat outputs are model dependent and are
configured for specific applications.

No field programming or set up is required or
possible.

Depending on model and application, the
AppStat outputs are designed for either 24
volt AC or 0-10 volt DC loads.

The outputs may represent analog or digital
signals.

Caution

Improperly connecting loads or
equipment to output terminals may
damage the equipment. Connect only
as shown in the following diagrams or
application drawings.

Illustration 5—FCU output terminals

0-10VDC

0-10VDC

0-10VDC

MS/TP

+B

–A

RS

WST

GND

DAT

COM

FAN-L

FAN-M

FAN-H

R

BO4

BO5

GND

AO6

AO8

AO7

24VAC

24 VAC

24VAC

24VAC

24VAC

24VAC

24VAC

Connecting power

The AppStat requires an external, 24 volt, AC power
source. Use the following guidelines when choosing
and wiring transformers.

Use only a Class-2 transformer of the
appropriate size to supply power.

KMC Controls recommends powering the
AppStat from a dedicated controls transformer.

Connect the transformer’s neutral lead to the
COM terminal.

Connect the AC phase lead to the 24VAC
terminal.

Power is applied to the controller when the
transformer is powered.

See

Installation accessories

on page 4

for a list of

transformers available from KMC Controls, Inc.

Illustration 6—Wiring for AppStat power

24 VAC
Class-2

Controls

transformer

MS/TP

+B

–A

RS

WST

GND

DAT

COM

FAN-L

FAN-M

FAN-H

R

BO4

BO5

GND

AO6

AO8

AO7

24VAC

Содержание AppStat

Страница 1: ...e surface temperature of the object and the background temperature of the room is too small Object movement in a direct line toward the sensor Very slow or very fast object movement Obstructions as shown in the illustration Typical motion sensing coverage area on page 1 False detections may be triggered by The temperature inside the detection range suddenly changes because of the entry of cold or ...

Страница 2: ...the mounting base 4 Position the base with the embossed UP toward the ceiling and fasten it directly to a vertical 2 x 4 inch electrical box For horizontal boxes or 4 x 4 applications use a wall plate kit See Installation accessories on page 4 for part numbers 5 Connect the wires for the AppStat to the terminals in the mounting base 6 Place the top of the sensor over the top of the mounting base a...

Страница 3: ...on Follow the instructions supplied with the sensor for installation Connecting outputs The AppStat outputs are model dependent and are configured for specific applications No field programming or set up is required or possible Depending on model and application the AppStat outputs are designed for either 24 volt AC or 0 10 volt DC loads The outputs may represent analog or digital signals Caution ...

Страница 4: ...ion Installation accessories The following accessories are available from KMC Controls Inc XEE 6111 040 Single hub 120 volt power transformer XEE 6112 040 Dual hub 120 volt power transformer XEE 6311 075 120 240 277 480VAC 24 VAC 75 VA transformer HMO 10000W White mounting plate kit for retrofit on horizontal boxes or 4 x 4 handy boxes Additional resources The latest support files are always avail...

Отзывы: