(a) Configuration menu of the SMY-CA
analyzer.
(b) Setting up the display options.
(c) Setting up the basic installation pa-
rameters of an instrument.
(d) Setting up the RS485 serial commu-
nication option.
(e) Setting up the Ethernet communi-
cation option.
(f) Setting up the time, date and time
synchronization options.
Figure 5: Set up screens of the SMY-CA analyzer.
4. press button
Â
. Configuration screen will be displayed (fig. 5a)
5. press multiple times button
Ä
and select
Install Config
item.
6. press button
Â
.
Install Config
screen is displayed.
7. select
Connection Type
according to the physical connection of the instrument.
8. insert correct value of voltage and current transformer ratio according to the used VT and CT.
9. press button
À
and accept the settings modifications on a displayed screen.
10. press button
Á
to confirm the change or button
Ã
to cancel the previous modifications.
2.5.2
Communication options
1. select the
Communication
item in menu
2. confirm ETH or RS-485 configuration according to the instrument option
(a) ETH: enter IP address, network mask and gateway.
(b) RS-485: enter communication line parameters according to your setup
2.5.3
Time and date options
1. select the
Time and Date
item in menu