KMB SMY-CA Скачать руководство пользователя страница 8

(a) Configuration menu of the SMY-CA
analyzer.

(b) Setting up the display options.

(c) Setting up the basic installation pa-
rameters of an instrument.

(d) Setting up the RS485 serial commu-
nication option.

(e) Setting up the Ethernet communi-
cation option.

(f) Setting up the time, date and time
synchronization options.

Figure 5: Set up screens of the SMY-CA analyzer.

4. press button

Â

. Configuration screen will be displayed (fig. 5a)

5. press multiple times button

Ä

and select

Install Config

item.

6. press button

Â

.

Install Config

screen is displayed.

7. select

Connection Type

according to the physical connection of the instrument.

8. insert correct value of voltage and current transformer ratio according to the used VT and CT.

9. press button

À

and accept the settings modifications on a displayed screen.

10. press button

Á

to confirm the change or button

Ã

to cancel the previous modifications.

2.5.2

Communication options

1. select the

Communication

item in menu

2. confirm ETH or RS-485 configuration according to the instrument option

(a) ETH: enter IP address, network mask and gateway.

(b) RS-485: enter communication line parameters according to your setup

2.5.3

Time and date options

1. select the

Time and Date

item in menu

7

Содержание SMY-CA

Страница 1: ...CA 2 2 2 Instrument overload warning 2 2 3 Installation 2 2 3 1 Connection step by step 3 2 3 2 Disconnection 4 2 3 3 Communication peripherals 5 2 4 Lock unlock the instrument 5 2 4 1 Locking the in...

Страница 2: ...ptions is specially designed to be used only in combination with provided external current sensors which are supported with the respective option SMY CA is based on SMY 133 panel power meter and share...

Страница 3: ...ected to the parts which are under dangerous voltage it is necessary to comply with all the necessary measures to protect users and equipment against injury with electrical shock Person performing the...

Страница 4: ...enerally the current sensors are interchangeable But for better orientation we recommend to respect their marking connect the brown sensor to the L1 current input the black one to the L2 input and the...

Страница 5: ...After recording of measurement for the desired period of time has been completed it is necessary to disconnect the instrument from the points of measurement and transfer the data recorded to a compute...

Страница 6: ...lock the instrument so as to prevent any unwanted modifications of its configuration by aliens 2 4 1 Locking the instrument 1 press the button in the default start screen 2 choose lock unlock symbol...

Страница 7: ...s 5 multifunction buttons located under the display area its actual function is dynamic and is symbolized by a pictogram on the lower edge of the screen above each button fig 3 For intention of use in...

Страница 8: ...l Config screen is displayed 7 select Connection Type according to the physical connection of the instrument 8 insert correct value of voltage and current transformer ratio according to the used VT an...

Страница 9: ...specific archive s you want to download The actual download will start by pressing the Download All button progress is displayed on screen When finished the archive can be viewed in the ENVIS applicat...

Страница 10: ...tarif and sums EP EQL EQL EQC a EQC and single phase L1 L2 and L3 values respectively 3 Technical Specifications 3 1 Basic Parameters Instrument Auxiliary Power Supply Voltage 100 275 VAC90 350 VDC po...

Страница 11: ...acy 2 seconds per day backup battery capacity 5 years without supply voltage applied weight max 0 3 kg EN 61000 4 2 4kV 8kV EN 61000 4 3 10 V m up to 1 GHz EN 61000 4 4 2 kV EN 61000 4 5 2 kV EN 61000...

Страница 12: ...balance measuring range 0 10 measuring uncertainty 0 3 THDU measuring range 0 20 measuring uncertainty 0 5 reference conditions measuring range measuring uncertainty twice the levels of class II acc t...

Страница 13: ...measuring uncertainty THDI 100 0 6 THDI 100 0 6 of rdg Temperature internal sensor measured value affected by the instrument power dissipation measuring range 40 80 C measuring uncertainty 2 C INOM IB...

Страница 14: ...ctive Reactive Power Power Factor PF cos PNOM UNOM x INOM reference conditions A ambient temperature tA U I for active power PF cos for reactive power 23 2 C U 80 120 UNOM I 1 120 INOM PF 1 00 PF 0 00...

Страница 15: ...nstrument less than 10 A If the cell is empty it is necessary to ship the instrument to the manufacturer for battery replacement Service in the case of failure or a breakdown of the product you should...

Отзывы: