NOVAR 2600 Operating Manual
2.2.2 Measured Electrical Quantities
2.2.2.1 Measured Voltages
Measured voltages in wye ( star ), delta or Aron connection connect to terminals
VOLTAGE / N
(No.
11),
U1
(No. 12),
U2
(No. 13), and
U3
(No. 14). Phase rotating direction is free.
Types of connections are stated in the following table.
Tab. 2.1: Connection of the measured voltages – VOLTAGE group of terminals
Terminal
Type of connection
VOLTAGE
wye-star (Y)
delta (D)
Aron (A)
U
1
L1-phase voltage
L1-phase voltage
L1-phase voltage
U
2
L2-phase voltage
L2-phase voltage
L2-phase voltage
U
3
L3-phase voltage
L3-phase voltage
L3-phase voltage
U
N
neutral wire voltage
-
-
It is advisable to protect the supply leads by 1A safety fuses.
The type of voltage and currents connection must be entered in
Installation
parameters : the code
shows the amount of connected phases,
3Y
means three-phase connection in wye ( star ),
3D
in delta.
3A
means Aron connection. For
1Y3
or
1D3
setup, the instrument operates in, so called,
single phase
mode
– see description in appropriate chapter below..
In the case of indirect connection via the measuring voltage transformers, it is necessary to enter this
matter ( connection
Mode
) and the values of the VT ratios during the setup of the instrument.
2.2.2.2 Measured Currents
The instruments are designed for indirect current measurement via external CTs only. Proper current
signal polarity (S1 & S2 terminals) must be observed. You can check the polarity by the sign of phase
active powers on the instrument display (in case of energy transfer direction is known, of course).
The CT-ratio must be set. in
the Installation
group of parameters (see below).
The I2 terminals stay free in case of the Aron (A) connection.
To get better precision when using overweighted CTs, you can apply more windings of
measured wire through the transformer. Then you must set the multiplier parameter (see
below). For standard connection with 1 winding, the multiplier must be set to 1.
The current signals from 5A or 1A (or 0.1A for the „X/100mA“ models) instrument current transformers
must be connected to the
CURRENT
connector terminal pairs
I11 – I12
,
I21 – I22
,
I31 –
I32
(No. 1÷6).
A particular connector is provided with a screw lock to prevent an accidental pullout and possible
unwanted disconnection of the current circuit.
A connection cable maximum cross section area is 2.5 mm
2
.
2.2.3 Outputs
Instruments can have up to 18 relay (“R”- models) or transistor (“T”-models) outputs. For models with
more than 9 outputs, the outputs are arranged in two output groups. The groups are isolated from
each other.
Each group has one relay common pole terminal
C1
,
C2
( No.15 and 25 ) and up to nine individual
relay output terminals
1.1
through
1.9
( No.16 ÷ 24 ) for group No. 1 and
2.1
through
2.9
( No.26 ÷
34 ) for group No. 2.
10
Содержание NOVAR 2600
Страница 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Страница 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Страница 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Страница 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Страница 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...