klover STAR 14 Скачать руководство пользователя страница 13

STAR 14 PELLET BOILER STOVE 

 

10 

 

EN - Rev. 2.1 

 

The unit must be installed on a floor with a suitable load capacity. If the existing building does not fulfil this requirement 

appropriate measures (e.g. load distribution plate) must be taken. 

The minimum safety distance from flammable materials must be at least 200 mm from the sides and back of the 
appliance. 

Relocating the appliance should not be done by forcing on the handle, glass or ceramics. 

The installation must guarantee easy access for cleaning the appliance, the flue gas exhaust pipes and the flue, and any 

subsequent maintenance operation by the Authorised technical assistance centre. 

 

Once you have found the best location for the appliance, position it following the instructions given below. 
 

Spaces around and above the appliance 

The figure below shows the minimum distances from walls or other not-easily-removable furniture, that need to be taken 

into consideration when positioning the appliance. 

 

REAR WALL

SI

D

WA

LL

SI
D


WA

LL

50 cm

50 cm

15 cm

 

Any shelves or false ceilings mounted above the appliance must be at least 100 cm away from the top part of it.  

Furniture and movable objects must be positioned at least 15 cm from the side surfaces of the appliance; these objects 

must be moved when performing maintenance on the appliance. 

Protect all structures that can catch fire against the radiated heat of the fire. 

Any extra intervention by the Authorised technical assistance centre, where it is necessary to disconnect the 
device from the system, will not be recognised under warranty as described in chapter 

“Warranty Conditions”

 

External air intake

 

During operation, the appliance takes in air from the environment in which it is installed; It is therefore essential that this 

air is replaced through an external air vent. The absence of the air vent may affect the flue draught and therefore the 
combustion and the safety of the appliance. 

 

Therefore it is mandatory to install an external air vent with a minimum completely free passage of at least 80 cm

2

 

(round hole with minimum diameter of 15 cm protected with a special fixed large mesh grid). 

 
If the wall behind the appliance is on the outside, we recommend you make the hole near it at about 20 cm above the 

ground 

(see example in Fig. A)

If it is not possible to put an air vent in the wall behind the appliance, make a hole in a perimeter wall in the room where it 

is installed. If it not possible to put the external air vent in the same room as where the appliance is installed, this hole 

can be made in an adjoining room as long as this room communicates permanently, by means of a transit hole (15 cm 

minimum diameter). 
The hole must be protected externally with a fixed grille. The protective grille must be checked periodically to ensure that 

it is not obstructed, thereby impeding the passage of air. Therefore keep the air vents clear of obstructions.

 

 

The UNI 10683 Standard FORBIDS the drawing of combustion air from garages, warehouses storing combustible 

materials, or from business premises with a fire hazard. 

Содержание STAR 14

Страница 1: ...ENGLISH STAR 14 Pellet boiler stove INSTALLATION USE AND MAINTENANCE USEFUL TIPS...

Страница 2: ......

Страница 3: ...e A1 Distance from combustible material 200 mm Fuel spillage risk Compliant Emission of combustion products Nominal power Reduced power CO at 13 of O2 0 010 CO at 13 of O2 0 037 Effective temperature...

Страница 4: ...ONTROL OF ANY COUPLED BOILER 14 CONNECTION TO THE ROOM THERMOSTAT 15 HYDRAULIC CONNECTION 15 THE DISPLAY 16 THE MENU 18 INITIAL START UP 22 FILLING THE SYSTEM FOR THE FIRST TIME 22 PELLET LOADING AND...

Страница 5: ...nce and its operation instructions for proper installation basic maintenance and control points which must be periodically performed furthermore it contains practical advice which helps to obtain maxi...

Страница 6: ...ncinerator or for any use other than that for which it was designed Do not use fuels other than those recommended Do not use liquid fuels The appliance and its outer surfaces in particular become very...

Страница 7: ...By laws and other regulations that affect the installation of the appliance The Building Regulations requirements can be met by adopting the relevant recommendations given in British Standards BS 8303...

Страница 8: ...the heating system Expansion tank 8 l with pre load 1 bar Safety valve calibrated 2 5 bar REAR TECHNICAL COMPARTMENT Manual air vent valve with key and rubber pipe Return pipe connection of the heati...

Страница 9: ...STAR 14 PELLET BOILER STOVE 6 EN Rev 2 1 Overall dimensions...

Страница 10: ...STOVE 7 EN Rev 2 1 Connections data sheet Description of connections M System Delivery 3 4 F R System Return 3 4 M X Safety valve drain 1 2 F A Intake pipe 43 mm S Flue gas outlet 80 mm M E Electricit...

Страница 11: ...037 Power consumption min max Watt 25 300 Nominal voltage V 220 Nominal frequency Hz 50 Expansion vessel litres preloading bar 8 1 Maximum operating recommended pressure bar 2 5 1 5 Flue pipe diamete...

Страница 12: ...must be compliant with some international standards such as EN14961 2 DIN 51731 and O NORM M7135 which establish minimum values for quality checks on pellets To facilitate the right choice of the comb...

Страница 13: ...d technical assistance centre where it is necessary to disconnect the device from the system will not be recognised under warranty as described in chapter Warranty Conditions External air intake Durin...

Страница 14: ...onditions of use refer to UNI 9615 It must be made of suitable materials capable of withstanding normal mechanical stress heat and the effects of combustion gases and condensate if any It must go upwa...

Страница 15: ...d 70 C IT IS MANDATORY TO HAVE AN INITIAL VERTICAL SECTION OF AT LEAST 1 5 MT IN ORDER TO GUARANTEE CORRECT FLUE GAS DISCHARGE Every direction change must be carried out with a T shaped fitting and in...

Страница 16: ...TRICAL CONNECTION The electric connection must only be performed by qualified staff in compliance with all general and local safety standards Check that the power supply voltage and frequency correspo...

Страница 17: ...standard boiler when the heating circulating pump of the pellet appliance starts up so as to avoid having two boilers operating simultaneously on the same system The coupled boiler is however always...

Страница 18: ...pump of the system is forcedly switched on to ensure the disposal of excessive heat thus avoiding the reaching of high temperatures of the water in the boiler For this reason it is recommended that th...

Страница 19: ...s any liability for damages caused due to incorrect assembly THE DISPLAY The appliance s operating mode is displayed on the console After turning on the menu it is possible to choose from many types o...

Страница 20: ...display when setting or programming operating parameters Set 1 2 3 4 5 6 The INPUT area shows the entered programming values The MENU LEVEL area shows the current parameter menu level The DIALOGUE ar...

Страница 21: ...ing power of the appliance Menu mode Moves you to the next menu item Programming mode Moves you to the next submenu item storing the changes made 6 Increase power 3 Working off Increases the working p...

Страница 22: ...enable disable and set the programmable thermostat weekly program functions MENU LEVEL SELECTION MEANING POSSIBLE VALUES 02 03 01 CHRONO WEEKLY Enable disable the weekly programme ON OFF The weekly pr...

Страница 23: ...TION MEANING POSSIBLE VALUES 02 04 01 CHRONO WEEK END Enable disable the weekend programme ON OFF 02 04 02 START 1 WEEK END Turn on time of the first programme Time OFF 02 04 03 STOP 1 WEEK END Turn o...

Страница 24: ...rol the appliance with the boiler temperature only disable the room sensor on the Remote control Stove settings menu Enable room sensor OFF The room sensor is automatically disabled if no external Rem...

Страница 25: ...ied or when it is filled for the first time Warning once the operation has been completed before switching on the appliance you should empty the accumulation of pellets deposited inside the brazier Me...

Страница 26: ...arranty Ignition cycle Pressing button 4 ON OFF for a few seconds allows you to start the ignition cycle After a while the display shows START and the flue gas intake device and ignition resistance sw...

Страница 27: ...rential set on Pr43 set as default at 5 C in other words if Temperature H2O SET H2O Pr43 The appliance automatically starts up again if the following condition occurs The temperature falls below the t...

Страница 28: ...set temperature the appliance will perform the same procedure as with the opening of the room thermostat See Connection to the room thermostat Remote control The following table shows the function of...

Страница 29: ...s not been done and if you have not filled the entire boiler body and system with water in order not to compromise its duration The noise level of the appliance is emphasised if the pellet container i...

Страница 30: ...ure sensor AL 3 HOT TEMP Flue gas over temperature When flue gas temperature is higher than 260 C Before displaying the alarm or when flue gas maximum temperature is reached Pr14 the display shows HOT...

Страница 31: ...ns use the personal protection devices specified in Directive 89 391 EEC The required cleaning frequency depends on the type and quality of the pellets used The schedule indicated below may therefore...

Страница 32: ...prevent damaging the vacuum cleaner We do not recommend the use of normal vacuum cleaners Non routine cleaning The extraordinary cleaning of the appliance must be done at least every 15 days so as to...

Страница 33: ...TOVE 30 EN Rev 2 1 Dismount the 4 flue diverters 2 on the right and 2 on the left placed on the combustion chamber sides figure 6 e 7 and scrape the internal walls with a spatula removing any deposit...

Страница 34: ...e boiler body Then reassemble the 4 flue diverters its bottom and the ash box To ensure correct operation it is necessary to remove the sawdust deposited on the base of the tank Figure 10 at least onc...

Страница 35: ...aranteeing correct operation optimal heat performance and durability of the device Therefore qualified staff should check the appliance at least once a year at the beginning of the season You must per...

Страница 36: ...4 11 Automatic re ignition after blackout BLACKOUT IGNITION Seconds 0 60 30 Pr49 M 9 4 12 Pellet level sensor enable PELLET RESERVE On off On off Off Pr50 M 9 4 13 Pump start for over temperature saf...

Страница 37: ...in output 1 working mode NOT USED AIR 1 SPEED Volt 65 225 65 Pr24 M 9 6 24 Exchanger 1 motor speed in output 2 working mode NOT USED AIR 2 SPEED Volt 65 225 65 Pr25 M 9 6 25 Exchanger 1 motor speed in...

Страница 38: ...ALT MANUAL RESET THERMOSTAT FUSE 4A 5X20 CN12 CN10 PCB L023 CN14 CONNECTOR FOR BOOTLOADER CONNECTION WIRES 220 V FOR CONTROLLING COUPLED BOILER IF CONNECTED AUX BLUE RED P M FOR THE ELECTRICAL CONNEC...

Страница 39: ...where it is not proved that their condition is due to a manufacturing defect rather than the effects of wear electric and electronic parts in which the malfunction can be traced to a non compliant el...

Страница 40: ...Cod CS IST ST14 EN FP KLOVER Srl Via A Volta 8 37047 San Bonifacio VR P IVA 02324280235 www klover it...

Отзывы: