Klingenburg KR4 Скачать руководство пользователя страница 3

5

4

2. Terminals at the control units KR 4 / KR7

 

L1 N

S1 S2 S3

PE PE PE

U V W

1 2 3 4 5 6 7 8 9 10

11 12 13

Mains (230V

olt) 50-60 Hz

Err

or message:

During operation S1 and S3 closed

By occurring of defects or net failur

el

 

S2 and S3 closed

3-phase AC motor (3x230 V

olt)

in delta connection

 

 with standar

d motors 230/400 V

olt

+ 10 V

olt r

efer

ence voltage

Contr

ol signal 0-10 V

olt, 0-20 mA

4-20 mA

+

-

-

 

+

blue

Running check        br

own black

Contr

ol unit r

elease

(external potential fr

ee contact closed

Thermostat r

elay motor

Optional: PTC-r

esistor motor

Operating r

epor

t:

 in operation: 11 and 13 closed

when not in operation, with faults or 

 

power failur

e 12 and 13 closed

14 15 U

a

L

Analogue Output FM

(0-10 Volt =)

Precedence freq. (for example: 

antifreeze - summer identification

Optional:

0-20 mA 4-20 mA

0-10 V

There is a supply voltage of 

24 Volt 

=

 on the contacts 

5, 7, 9 (and optional 14)  

 

3. Technical data

Controller typ

KR4

KR7

Output

0,4 kW

0,75 kW

Fuse (internal)

6,3 A delay (5 x 20 mm)

10 A delay (5 x 20 mm)

Mains voltage

220-240 Volt / 50-60 Hz 1~

Weight

3200 g

3500 g

Environmental temperature

from -10°C bis +40°C  

(for temperatures lower than 0°C it is necessary to switch on the mains voltage to 

the device without the motor running so that the controller can warm up)

temperature adjustment range

(only KR 4 Z / KR 7 Z)

Air supply temperature regulation 10°C - 40°C /summer switchover 18°C - 42°C

Other adjustment ranges must be specifically set

Type of protection

IP 54

Output frequency

0-120 Hz (factory setting 80 Hz)

Frequency resolution

0,08 Hz

Controller signal

0-10 V, 0-20 mA, 4-20 mA

Fault message relay

Potential-free changeover contact, 250 V AC, 1 A capacity

Motor connecting line

The connecting line must be shielded; chokes should be provided  

for lengths of over 50 m. Please inquire!

Dimensions

L=256 mm   B=232 mm   H=128 mm

Содержание KR4

Страница 1: ...N E R G Y R E C O V 1 Function of the controller 2 Terminal connections 3 Technical data 4 Initial operation 5 Manual mode external mode 6 Trouble shooting and fault messages 7 Safety and precautions...

Страница 2: ...short circuit proof outlet EN 55011 tested EN 61000 3 tested EN 61000 4 2 tested EN 61000 4 3 burst tested EN 61000 4 4 surge tested EN 61800 3 tested every individual module is tested detailed fault...

Страница 3: ...ly voltage of 24 Volt on the contacts 5 7 9 and optional 14 3 Technical data Controller typ KR4 KR7 Output 0 4 kW 0 75 kW Fuse internal 6 3 A delay 5 x 20 mm 10 A delay 5 x 20 mm Mains voltage 220 240...

Страница 4: ...z C o n t r b l o c k e d P l e a s e w a i t Navigating through the menu items You can choose between English and German Other menu languages are available upon request The change is made by activat...

Страница 5: ...g cycle ensures that the rotor moves regularly in a half rotation if no request comes from the controller signal or keypad for longer than 20 minutes 0 5 S t a r t p o i n t F r e q u e n c y 8 0 H z...

Страница 6: ...t f r e q 4 0 H z N o m f r e q 4 0 H z If the following image should appear instead Check the following table of errors Search method for KR4 KR7 base controller no display is visible test the fuse c...

Страница 7: ...r overloaded 09 Mains under voltage 14 Earth fault 15 Mains overvoltage 21 Overtemperature in the power amplifier environmental temperature too high controller overloaded 99 Software error The control...

Страница 8: ...restart is activated To avoid injury from possible uncontrolled restart of the fre quency converter after a power outage install a switch element on the grid side that de energises in a power outage a...

Страница 9: ...Klingenburg GmbH Boystra e 115 45968 Gladbeck Germany Tel 49 20 43 96 36 0 Fax 49 20 43 7 23 62 E mail klingenburg klingenburg de www klingenburg de E N E R G Y R E C O V E R Y DNKR4 7 Status 01 14...

Отзывы: