13
26.06.2019
Filtering unit
BIG-2000-N
8.
Troubleshooting Guide
Table No.4
Problem
Possible reason
Corrective action
1.
Drop in the intake volume flow. The filter is clogged.
Clean the surface of the filter
striking off the dusts by a “dry”
mode” (see Section 7)
or replace the filter for a new.
2.
Bad smells are not eliminated. Active carbon nonwoven Replace the activated carbon
(spunbond) is worn out. nonwoven.
3.
Dust emerges in the chamber The cartridge filter is
Replace the faulty cartridge filter.
of the electromagnetic valve.
damaged.
4.
Sudden vibrations of the
The impeller is damaged. Replace the impeller for a new.
fan are occurring.
5.
The ERGO LUX extraction arm Incorrectly adjusted
Increase the tension upon
is falling.
friction brake of the joint. the frictional disks of the
brake in the joint by tightening
the adjustment nuts.
6.
The ERGO LUX extraction arm The rotation axis of the
Carry out the positioning of the
is automatically setting (falling) swivel is not positioned
mounting flange of the
always into the same position. vertically.
ERGO LUX
extraction arm to
set the rotation axis vertically,
or put the whole device stably
on the levelled even floor.
7.
The device stops –
Q1M
motor disconnector Disconnect the plug of the socket.
S1.H1
lamp “
SUPPLY
” is not
activated,
Check the motor disconnector,
flashing.
the
S1
switch is faulty,
the
S1
switch and the protections.
The fan does not start.
the
F1
protection is
Switch all these protections on.
switched off.
9.
Maintenance
The filter cleaning proceeds automatically, without
interruption
of the
filtration and not reducing
the filtration efficiency. The construction of the device provides its function without the every-
day routine technical supervision. In case when faulty function is by noise or visually noticed
necessarily undertake its technical revision (see Table No.4).
Within the scope of periodical controls,
(every 9-12 months),
examine the technical state of the
according to the operational rules for the electrical driving devices.
During the maintenance check the mechanical, electrical and pneumatic connections.
Any activity connected with repair/technical revision has to be executed
exclusively after
the device
is switched off and disconnected from
the power supply sys-
tem.
Periodically, remove the water and impurities from the compressed air tank. Once a year, con-
trol the state of the compressed
air tank. In case of significant corrosion losses replace the tank
for a new one.
Every time, during the filter cleaning, examine the state of the filter fabric surface, and search
for mechanical damages. Replacement way
of the cartridge filter is described in Section 7 of the
present Use and Maintenance Manual.
Содержание BIG-2000-N
Страница 1: ...1 26 06 2019 Filtering unit BIG 2000 N Use and Maintenance Manual Filtering unit BIG 2000 N...
Страница 8: ...8 Filtering unit BIG 2000 N 26 06 2019 Fig No 2 Connection diagram filtering unit BIG 2000 N...
Страница 15: ...15 26 06 2019 Filtering unit BIG 2000 N Fig No 6 Compressed air tank...
Страница 18: ...18 Filtering unit BIG 2000 N 26 06 2019 NOTES...
Страница 19: ...19 26 06 2019 Filtering unit BIG 2000 N NOTES...