background image

1

2

 

16. Overview of failure code on Display (LED controller)

Wire 
controller  

Protection/Failure  

Check  

Solution  

PP01/PP1  

Inlet water temp. sensor 
failure  

1. Check the connection of inlet
water  sensor.  
2. Check if the sensor is broken.

1. Reconnect the sensor.
2. Replace the sensor.

PP02/PP2  

Outlet water temp. sensor 
failure  

1. Check the connection of outlet
water  sensor.  
2. Check if the sensor is broken.

1. Reconnect the sensor.
2. Replace the sensor.

PP03/PP3  

Coil 1 temp. sensor failure 

1. Check the connection of coil 1
temperature sensor.  
2. Check if the sensor is broken.

1. Reconnect the sensor.
2. Replace the sensor.

PP04/PP4  

Coil 2 temp. sensor failure 

1. Check the connection of coil 2
temperature sensor. temperature 
2. Check if the sensor is broken.

1. Reconnect the sensor.
2. Replace the sensor.

PP05/PP5  

Ambient temp. sensor failure 

1. Check the connection of ambient
temperature sensor.  
2. Check if the sensor is broken.

1. Reconnect the sensor.
2. Replace the sensor.

PP06/PP6  

Protection for excessive temp. 
difference between water inlet 
& outlet  

1. Check if there is any blockage in
the water circuit.  
2. Check if the water flow volume is
enough.  
3. Check if the water pump is
working.  

1. Remove the cause of
the blockage. 
2. Increase the water flow
volume.  
3. Repair or replace the
water pump.  

PP07/PP7  

Anti-freeze protection for 
cooling  

Refer to PP06.  

Refer to PP06.  

PP07/PP7  

Winter anti-freeze protection 

No action required  

PP07/PP7  

Winter anti-freeze protection 

No action required  

EE03/EE3  

Water flow switch failure 

1. Check if wiring connection of flow
switch is in correct position.  
2. Check water flow.
3. Check if flow switch is broken.
4. Check if water pump is working.

1. Reconnect the wiring.
2. Increase water flow.
3. Replace flow switch.
4. Repair or replace water
pump.  

EE04/EE4 

Order of phases incorrect 
(only for 3 phase model) 

Order of phases incorrect 

Reconnect the phases in 
right order. 

EE01/EE1  
EE06/EE6 

High / Low pressure 
protection  

1. Check if high or low pressure
switch is broken.  
2. Check if lack refrigerant level is
low (for low pressure). 
3. Ambient temp. and water inlet
temp. is too low (for low pressure). 
4. Check if there is a blockage in
water circuit or if water flow is not 
enough (for high pressure).  
5. Check if there is a blockage in
refrigerant circuit (for high 
pressure).  

1. Replace pressure
switch.  
2. Fill up with enough
refrigerant.  
3. Decrease water flow.
4. Remove cause of
blockage or increase 
water flow.  
5. Send heat pump to
dealer for     detailed 
check.  

EE05/EE5  

Failure of excessive temp. 
difference protection between 
water inlet & outlet  

1. Check if there is enough water
flow volume.  
2. Check if inlet / outlet water temp.
sensor is working. 

1. Increase water flow.
2. Replace sensor.

No 
display  

Defrosting  

EE08/EE8  

Communication failure 

Check the connection 

Reconnect the connection 
wire.  

Содержание KT10X

Страница 1: ...1 ...

Страница 2: ... professional technician It is strongly advised to place a protective guard around the unit to keep children away from the heat pump An authorized electrician must connect the Heat Pump to the power 230V 1ph or 400V 3ph Remarks Make sure that you have enough power See page 15 Cable table 380 400V 3ph 50Hz 230V 1ph 50Hz WATER PUMP POWER SUPPLY POWER SUPPLY WATER PUMP See diagram above for minimum d...

Страница 3: ...ilter pump off The unit should also switch off automatically 5 The unit and the filter pump should run 24 hours a day until the desired pool water temperature has been reached Once the set temperature is reached the unit will switch itself off As long as the filter pump is running the unit will restart automatically when the temperature of the pool water drops more than 1 C below the set temperatu...

Страница 4: ...keep your desired pool temperature at all times Example If you want your pool to be 30 C A If the pool water is below 29 C the heat pump will start heating B When the temperature reaches 31 C the heat pump will stop C If the temperature in your pool continues to rise and passes 32 C the heat pump will start again BUT in Cooling Mode and cool down to 30 C D If now the temperature continues to drop ...

Страница 5: ... MODE for 5 sec The display will start to blink both digits The first digit indicates the parameter The second digit s indicate the value of the parameter This reading mode will be deactivated if you do not press a button for 10 sec By pressing or you will see parameters from 0 to F one by one Make a note of each parameter for your records Wait 10 sec and this function is deactivated you are back ...

Страница 6: ...flash to indicate that they can be modified by pressing or 2 Press again minute digits will flash to indicate that they can be modified by pressing or 3 Press again for final confirmation of time setting Once time has been set LED display will show time when heat pump is on standby ...

Страница 7: ...to activate timer start or to activate timer stop the corresponding indicator light will be flashing Press to cancel timer start or timer stop INFO The parameter can be changed by a skilled person A code is needed to do so The procedure for this is in the Main Manual The keypad can be locked to prevent unauthorized use or changes of the heat pump The procedure for this is in the Main Manual If the...

Страница 8: ...ilter unit water inlet on heat pump 3 Start the filter pump to start the water flow to the heat pump Adjust the by pass so there is enough water running through the heat pump Normally on a small filter system the by pass can be closed so all circulated water goes through the heat pump 4 Reconnect the electrical power supply to the heat pump and turn the heat pump ON 13 Check up Our heat pumps have...

Страница 9: ...nning If the water stops running out it is condensation AN EVEN QUICKER WAY IS TO TEST THE DRAIN WATER FOR CHLORINE If no chlorine is detected the drain water is a result of condensation Also make sure that the air in and out passages are free and prevent air out from immediately re entering to the air in It is important to have min 2 5m free space at the air out side of the heat pump 14 Maintenan...

Страница 10: ...10 The manometer is showing the pressure at 14 ambient air and the pump is not running standby mode ...

Страница 11: ... heat pump to prevent damage to the compressor If the heat pump has been transported and carried all the time with the feet down it can be started immediately Note Switch off the power before carrying out any maintenance or repairs IMPORTANT REMARK if a malfunction cannot be resolved immediately in order to analyse the problem we will need to know the message error code that is showing on the disp...

Страница 12: ...eeze protection for cooling Refer to PP06 Refer to PP06 PP07 PP7 Winter anti freeze protection Ⅰ No action required PP07 PP7 Winter anti freeze protection Ⅱ No action required EE03 EE3 Water flow switch failure 1 Check if wiring connection of flow switch is in correct position 2 Check water flow 3 Check if flow switch is broken 4 Check if water pump is working 1 Reconnect the wiring 2 Increase wat...

Страница 13: ...13 ...

Страница 14: ...Default Settings Observed Settings ____________________________________________ Is the heat pump Running __ Running sometimes __ Not running at all ___ Is the heat pump Heating __ Not Heating enough __ Not heating at all __ Is the fan running YES__ NO__ Is there ice on Radiator YES__ NO__ Is there Cold Air coming out from Radiator YES__ NO__ DON T KNOW__ Are there leaves or dirt on the fins on the...

Страница 15: ... The heat pump stops Error code EE3 Too little water flow Check Filter and filter Pump Air in the Filter system Water Flow Switch defect d The heat pumps stops and starts frequently Too little water flow Air leakage in pipes on suction side Check Filter and filter Pump Air in the Filter system Water Flow Switch defect e Heat pump does not work periodically Weak power Supply To long Supply Cable To...

Страница 16: ...16 ...

Отзывы: