3-2-3(i) Refrigerant Refill
Air purge(at the time of new installation only)
Connect it to the refrigerant filling tank.
(Turn the tank upside down : Fill the refrigerant
in liquid form.)
Close the gas pipe side valve, and loosen
the pressure gauge connected.
Then open the gas pipe side valve again.
Tighten the cap of each valve using
a specified tool.
Stop operation.
Open the tank and refill the refrigerant
until arriving at the proper pressure.
(Refill the refrigent slowly checking the pressure.)
Close the gas pipe side valve by turning it
clockwise.
Connect the pressure gauge to the low
pressure side service valve, and then open
the gas pipe side valve again.
Start cooling operation.
Check the pressure of the pressure gauge.
Check whether the low pressure side is within
the range of 4.5~5.5kg/cm2G
(outside temperature 35°C).
Gas pipe side
Liquid
pipe side
Outdoor unit
Operating Instructions and Installation
Содержание KFH28PV2
Страница 4: ...2 2 2 2 Dimensions Indoor Unit Outdoor Unit unit mm 330...
Страница 26: ...Disassembly and Reassembly 4 5 No Parts Procedur e Remark...
Страница 35: ...6 1 6 Exploded Views and Parts List 6 1 Indoor Unit...
Страница 37: ...6 3 6 1 1 ASS Y COVER FRONT Exploded Views and Parts List...
Страница 39: ...6 5 6 1 2 ASS Y GRILLE INLET Exploded Views and Parts List...
Страница 41: ...6 7 6 2 Outdoor unit 19 18 14 1 16 17 15 7 6 9 11 13 12 8 2 4 5 19 1 19 2 10 3...
Страница 46: ...8 1 8 PCB Diagrams 8 1 Ass y Main PCB CODE NO DB93 10531B...
Страница 48: ...8 3 8 2 Ass y Power PCB Code No DB93 10532B...
Страница 51: ...9 1 9 Wiring Diagrams 9 1 Indoor Unit...
Страница 52: ...9 2 9 2 Outdoor Unit...
Страница 54: ...10 1 10 Schematic Diagrams 10 1 Indoor Unit...
Страница 55: ...10 2 10 2 Remote Control...