If you will install the unit on a wall-mounted 
bracket

, do the following:

 CAUTION

Before installing a wall-mounted unit, make 
sure that the wall is made of solid brick, 
concrete, or of similarly strong material. 

The 

wall must be able to support at least four 
times the weight of the unit.

1. Mark the position of bracket holes based on

dimensions in the Unit Mounting Dimensions
chart.

2. Pre-drill the holes for the expansion bolts.
3. Clean dust and debris away from holes.
4. Place a washer and nut on the end of each

expansion bolt.

5. Thread expansion bolts through holes in

mounting brackets, put mounting brackets
in position, and hammer expansion bolts into
the wall.

6. Check that the mounting brackets are level.
7. Carefully lift unit and place its mounting feet

on brackets.

8. Bolt the unit firmly to the brackets.

TO REDUCE VIBRATIONS OF WALL-
MOUNTED UNIT

If allowed, you can install the wall-mounted 
unit with rubber gaskets to reduce vibrations 
and noise.

Step 4: Connect signal and power cables

The outside unit’s terminal block is protected by 
an electrical wiring cover on the side of the unit. 
A comprehensive wiring diagram is printed on 
the inside of the wiring cover.

BEFORE PERFORMING 
ELECTRICAL WORK, 

 

READ THESE REGULATIONS

1. All wiring must comply with local and

national electrical codes, and must be
installed by a licensed electrician.

2. All electrical connections must be made

according to the Electrical Connection
Diagram located on the side panels of the
indoor and outdoor units.

3. If there is a serious safety issue with the

power supply, stop work immediately. Explain
your reasoning to the client, and refuse
to install the unit until the safety issue is
properly resolved.

4. Power voltage should be within 90-100% of

rated voltage. Insufficient power supply can
cause electrical shock or fire.

5. If connecting power to fixed wiring, install a

surge protector and main power switch with
a capacity of 1.5 times the maximum current
of the unit.

6. If connecting power to fixed wiring, a switch

or circuit breaker that disconnects all poles
and has a contact separation of at least 1/8in
(3mm) must be incorporated in the fixed
wiring. The qualified technician must use an
approved circuit breaker or switch.

7. Only connect the unit to an individual branch

circuit outlet. Do not connect another
appliance to that outlet.

8. Make sure to properly ground the air

conditioner.

9. Every wire must be firmly connected. Loose

wiring can cause the terminal to overheat,
resulting in product malfunction and possible
fire.

10.  

Do not

 let wires touch or rest against

refrigerant tubing, the compressor, or any
moving parts within the unit.

11.  If the unit has an auxiliary electric heater, it

must be installed at least 1 meter (40in) away
from any combustible materials.

Outdoor Unit 

Installation

Содержание ksie series

Страница 1: ...OUTDOOR UNIT Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference SERIES...

Страница 2: ...ort the unit and will not vibrate Noise from the unit will not disturb others Protected from prolonged periods of direct sunlight or rain DO NOT install unit in the following locations Near an obstacl...

Страница 3: ...outdoor unit If the drain joint comes with a rubber seal see Fig 4 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain jo...

Страница 4: ...n bolt 5 Hammer expansion bolts into the pre drilled holes 6 Remove the nuts from expansion bolts and place outdoor unit on bolts 7 Put washer on each expansion bolt then replace the nuts 8 Using a wr...

Страница 5: ...odes and must be installed by a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the indoor and outdoor units...

Страница 6: ...the terminal block and place it to the side 4 Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal 5 After checking...

Страница 7: ...Conditioner 15 000 25 82ft 10 33ft 15 000 and 24 000 30 98 5ft 20 66ft 24 000 and 36 000 50 164ft 25 82ft 36 000 and 60 000 65 213ft 30 98 5ft Connection Instructions Refrigerant Piping Step 1 Cut pi...

Страница 8: ...th PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction beca...

Страница 9: ...5 1 500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4lb ft 2 600 19 18lb ft 12 7 0 5 3 500 25 8lb ft 3 600 26 55lb ft 16 0 63 4 500 33 19lb ft 4 700 34 67lb ft DO NOT USE EXCESSIVE TORQUE Excessive fo...

Страница 10: ...Using a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE SPANNE R TO GRIP MAIN BOD Y OF VALVE Torque from tightening the flare nut can snap off oth...

Страница 11: ...pipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual Check to make sure all wiring is connected properly Evacu...

Страница 12: ...w pressure by hand You may tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against the stopper Do not try to...

Страница 13: ...nit immediately and call a licensed electrician to find and resolve the cause of the leakage Note This may not be required for some locations in the US Gas Leak Checks There are two different methods...

Страница 14: ...r to turn it on 3 Press the MODE button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run...

Страница 15: ...rol return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process IF AMBIENT TEMP...

Страница 16: ...s Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old appliance free of charge The manufacturer will t...

Страница 17: ...t improvement Consult with the sales agency or manufacturer for details 2190 NW 89 Place Doral FL 33172 USA Tel 305 593 8358 Fax 305 675 2212 www klimaire com sales klimaire com The Klimaire logo is a...

Отзывы: