background image

3.

Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed.

4.

Turn on the vacuum pump to evacuate the
system.

5.

Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG
(-10  Pa).

6.

Close the Low Pressure side of the manifold
gauge, and turn off the vacuum pump.

7.

Wait for 5 minutes, then check that there
has been no change in system pressure.

8.

If there is a change in system pressure, refer
to Gas Leak Check section for information
on how to check for leaks. If there is no
change in system pressure, unscrew the cap
from the packed valve (high pressure valve).

9.

Insert hexagonal wrench into the packed valve
(high pressure valve) and open the valve by
turning the wrench  in a 1/4 counterclockwise
turn. Listen for gas to exit the system, then
close the valve after 5 seconds.

10. Watch the Pressure Gauge for one minute

to make sure that there is no change in
pressure. The Pressure Gauge should read
slightly higher than atmospheric pressure.

Flare nut

Cap

Valve body

Valve stem

11. Remove the charge hose from the service port.
12. Using hexagonal wrench, fully open both the

high pressure and low pressure valves.

13. Tighten valve caps on all three valves (service

port, high pressure, low pressure) by hand.
You may tighten it further using a torque
wrench if needed.

 OPEN VALVE STEMS GENTLY

When opening valve stems, turn the hexagonal 
wrench until it hits against the stopper. Do not 
try to force the valve to open further.

Note on Adding Refrigerant

ADDITIONAL REFRIGERANT PER PIPE LENGTH

Connective Pipe 

Length (m)

Air Purging 

Method

Additional Refrigerant

< Standard pipe length Vacuum Pump

N/A

> Standard pipe

length

Vacuum Pump

Liquid Side: Ø 6.35 (ø 0.25”)

R22: 

(Pipe length – standard length) x 30g/m 

(Pipe length – standard length) x 0.32oZ/ft

Inverter R410A: 

Fixed-frequency R410A: 

Inverter R410A: 

Fixed-frequency R410A: 

(Pipe length – standard length) x 15g/m

(Pipe length – standard length) x 0.16oZ/ft

(Pipe length – standard length) x 20g/m

(Pipe length – standard length) x 0.21oZ/ft

(Pipe length – standard length) x 40g/m

(Pipe length – standard length) x 0.42oZ/ft

Liquid Side: Ø 9.52 (ø 0.375”)

R22: 

(Pipe length – standard length) x 60g/m 

(Pipe length – standard length) x 0.64oZ/ft

(Pipe length – standard length) x 30g/m

(Pipe length – standard length) x 0.32oZ/ft

 CAUTION

DO NOT

 mix refrigerant types.

Fig. 6.2

Air Evacuation

Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations. For example, in North America, the standard pipe length is 7.5m (25ft).
In other areas, the standard pipe length is 5m (16ft). The additional refrigerant to be charged can be 
calculated using the following formula: 

5

Содержание ksie series

Страница 1: ...OUTDOOR UNIT Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference SERIES...

Страница 2: ...ort the unit and will not vibrate Noise from the unit will not disturb others Protected from prolonged periods of direct sunlight or rain DO NOT install unit in the following locations Near an obstacl...

Страница 3: ...outdoor unit If the drain joint comes with a rubber seal see Fig 4 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain jo...

Страница 4: ...n bolt 5 Hammer expansion bolts into the pre drilled holes 6 Remove the nuts from expansion bolts and place outdoor unit on bolts 7 Put washer on each expansion bolt then replace the nuts 8 Using a wr...

Страница 5: ...odes and must be installed by a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the indoor and outdoor units...

Страница 6: ...the terminal block and place it to the side 4 Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal 5 After checking...

Страница 7: ...Conditioner 15 000 25 82ft 10 33ft 15 000 and 24 000 30 98 5ft 20 66ft 24 000 and 36 000 50 164ft 25 82ft 36 000 and 60 000 65 213ft 30 98 5ft Connection Instructions Refrigerant Piping Step 1 Cut pi...

Страница 8: ...th PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction beca...

Страница 9: ...5 1 500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4lb ft 2 600 19 18lb ft 12 7 0 5 3 500 25 8lb ft 3 600 26 55lb ft 16 0 63 4 500 33 19lb ft 4 700 34 67lb ft DO NOT USE EXCESSIVE TORQUE Excessive fo...

Страница 10: ...Using a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE SPANNE R TO GRIP MAIN BOD Y OF VALVE Torque from tightening the flare nut can snap off oth...

Страница 11: ...pipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual Check to make sure all wiring is connected properly Evacu...

Страница 12: ...w pressure by hand You may tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against the stopper Do not try to...

Страница 13: ...nit immediately and call a licensed electrician to find and resolve the cause of the leakage Note This may not be required for some locations in the US Gas Leak Checks There are two different methods...

Страница 14: ...r to turn it on 3 Press the MODE button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run...

Страница 15: ...rol return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process IF AMBIENT TEMP...

Страница 16: ...s Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old appliance free of charge The manufacturer will t...

Страница 17: ...t improvement Consult with the sales agency or manufacturer for details 2190 NW 89 Place Doral FL 33172 USA Tel 305 593 8358 Fax 305 675 2212 www klimaire com sales klimaire com The Klimaire logo is a...

Отзывы: