Page 38 of 72
Checklist error
Error in manual mode
Error
Cause of error / error rectification
No movement
possible in
manual mode
Check whether emergency stop is OK and acknowledge.
Check whether the motor and auxiliary protection are switched on in the master cabinet.
►
If a protection device had tripped, the error needs to be cleared in the service menu.
To do this press the green tick (see picture).
Check whether the gates are closed securely or the maintenance switch is activated.
If the gates are not closed securely, no movement is possible.
Check whether the addressing is set correctly on the sub-distributors and on the master.
Check connecting cable from the selection panel to the main cabinet.
Check whether pins are bent within the M12 plug.
Check whether the cabling between the sub-distributors and the master cabinet has been
carried out correctly (see assembly instructions
TrendVario6X00 cabling).
The bus cabling always starts on the master cabinet and leads to the 1st sub-
distributor, then to the next up to the last. The end plug for the bus must be plugged in
on the last sub-distributor.