3-4 Checking the CO2
①
The combustion may be checked after running the boiler for several minutes.
To do this it is necessary to set the boiler to Calibration Mode.
②
Ensure that all external controls are calling for heating with maximum output.
③
The appliance should be check visually for obvious defects.
④
There are two test points in the flue, one for flue gas and the other for air.
⑤
Open the air and flue gas test points.
⑥
Insert the flue gas analyzer probe as far as the retainer.
⑦
Allow the boiler to reach thermal equilibrium (around 5~10min)
⑧
The CO and CO2 values should be check each below 200ppm and 5%.
3-3 Water Circuit Diagram
Air inlet test point
Flue gas test point
Exhaust flue cap
Flue gas analyzer
NOTE
: To ensure correct readings the boiler must have reached maximum operating temperature.
. Testing the boiler before thermal equilibrium has been attained will give incorrect readings.
NOTE :
If you have only 1 probe, measure separately air and flue gas, close the test point not in
use.
7
6
1
1
4
2
9
3
5
11
15
1
1
1
1
18
12
2
20
16
22
23
24
25
8
2
2
1. AL Heat Exchanger
2. CU Heat Exchanger
3. Limit Switch
4. Heating Temperature Probe
5. MFB (Metal Fiber Burner)
6. Flame Detector (Photo Sensor)
7. Fan
8. Igniter
9. Pressure Gauge
10. Expansion Tank
11. Auto Air-vent
12. DHW Heat Exchanger
13. Three Way Valve
14. Heating Filling Valve
15. Heating Water Level Sensor
16. Circulation Pump
17. DHW Inlet Temperature Probe
18. DHW Outlet temperature Probe
19. Gas Valve
20. DHW Flow Sensor
21. Heating Filter
22. Heating Return Connection
23. Tap Water Inlet Connection
24. Hot Water Outlet Connection
25. Heating Supply Connection
24페이지
Содержание eco condensing - 16D
Страница 6: ...2 Installation 2 1 Appliance dimension and required specification 6페이지 ...
Страница 27: ...4 Direction for assembly 4 1 Part exploded view 27페이지 ...
Страница 43: ...10 Memo 43페이지 ...
Страница 44: ...11 Warranty 44페이지 ...