2-3
Models rated from 7.3 to 9.6 kW at 240 volts
•
(5.5 to 7.2 kW at 208 volts) require a separate
40-amp circuit. Models rated at 7.2 kW and
below at 240 volts (5.4 kW and below at 208
volts) require a separate 30-amp circuit.
A time-delay fuse or circuit breaker is recom-
•
mended.
Connect directly to the fused disconnect (or
•
circuit breaker box) through flexible, armored
or nonmetallic sheathed, copper cable (with
grounding wire). See “Make Electrical Con-
nection,” page 2-5.
Flexible cable from the oven should be con
-
•
nected directly to the junction box.
Fuse both sides of the line.
•
Do not cut the conduit. The length of conduit
•
provided is for serviceability of the oven.
A UL listed or CSA approved conduit con-
•
nector must be provided.
If the house has aluminum wiring follow the
•
procedure below:
1. Connect a section of solid copper wire to
the pigtail leads.
2. Connect the aluminum wiring to the added
section of copper wire using special con-
nectors and/or tools designed and UL
listed for joining copper to aluminum.
Follow the electrical connector manufacturer’s
recommended procedure. Aluminum/copper
connection must conform with local codes
and industry accepted wiring practices.