![Kirloskar Electric BPC955 V0 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/kirloskar-electric/bpc955-v0/bpc955-v0_user-manual_1972138007.webp)
BPC955V0 User Manual
EMS955V0 AMF CONTROLLER1.doc
Page 7 of 19
8/06/2011
AC Inputs
Function
Description
3 Phase Mains AC Voltage
Mains AC voltages.
3 Phase Alternator AC
Voltage
Alternator AC voltages.
3 Phase Alternator Current
Alternator AC currents via external 5A CTs.
Analog Inputs
Function
Description
Speed
Engine speed from MPU or battery charging alternator.
Lubrication Oil Pressure
Engine oil pressure. Exciting current approx 13mA
Lubrication Oil Temperature
Engine oil temperature. Exciting Current approx 5mA
Coolant Temperature
Engine coolant temperature (Air or Water). Exciting current approx 5mA
Fuel Level
Engine fuel level. Exciting current approx 13mA
Canopy Temperature
Engine canopy temperature. Exciting Current approx 5mA
Coolant Level
Engine Radiator level. Exciting frequency 500Hz
Battery Voltage (Internal)
Battery Voltage is measured internally from DC supply point.
Digital Inputs
Function
Description
Auto Start / Stop Input
Auto start.
Close to common. Current limited 10mA at 10V
Emergency Stop Input
Emergency engine stop.
Selectable Open or Close to common. Current limited 10mA at 10V
Oil Switch Input
Oil Pressure Switch sensor.
Close to common. Current limited 10mA at 10V
Digital Input 1
Configurable. Default = Bypass. No logic control but full instrumentation
available.
Digital Input 2
Configurable. Default = Canopy door open.
Close to common. Current limited 10mA at 10V
Digital Input 3
Configurable. Default = Fire. Shutdown genset and open both contactors.
Close to common. Current limited 10mA at 10V
Digital Input 4
Configurable. Status, Warning, Alarm, PC programmed message.