PREFACE
Thank you for purchasing our generators.
This manual covers operation and maintenance of the IG2600, IG2600h
generator.
All information in this publication is based on the latest product information
available at the time of approval for printing.
We reserve the right to make changes at any time without notice and without
incurring any obligation.
No part of this publication may be reproduced without written permission.
This manual should be considered a permanent part of the generator and should
remain with it if it is resold.
Pay special attention to statements preceded by the following words;
Failure to properly follow these precautions can result in
property damage, serious injury or DEATH!
Read all labels and the owner's manual before operating
this generator.
Operate only in well ventilated areas. Exhaust gas
contains poisonous carbon monoxide, and can be deadly.
Always stop engine before refueling. Wait 5 minutes
before restarting.
Check for spilled fuel or leaks. Clean and/or repair before
use.
Keep any sources of ignition away from fuel tank, at all
times.
Indicates a strong possibility of severe personal injury or
death if instructions are not followed.
Indicates a possibility of personal injury or equipment
damage if instructions are not followed.
NOTE: Gives helpful information.
If a problem should arise, or if you have any questions about the generator,
consult an authorized dealer.
Our generators are designed to give safe and dependable
service if operated according to instructions. Read and
understand the Owner's Manual before operating the gen-
erator. Failure to do so could result in personal injury or
equipment damage.
The illustration may vary according to the type.
WARNING
CAUTION
WARNING
WARNING
The conditions of generator rated output:
Altitude: 0 m Ambient temperature: 25
Relative humidity: 30%
Ambient modified coefficient: C (Relative humidity 30%)
Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P =5KW, altitude is 1000m, ambient
N
temperature is 35
, relative humidity is 80%, the rated power of generator is:
P=P
(C-0.02) = 5
(0.82-0.02) = 4KW
N
Modified coefficient table
of ambient condition power
Ambient temperature (
)
Altitude
(m)
0
500
1000
2000
3000
4000
25
1
0.93
0.87
0.75
0.64
0.54
30
0.98
0.91
0.85
0.73
0.62
0.52
35
0.96
0.89
0.82
0.71
0.6
0.5
40
0.93
0.87
0.80
0.69
0.58
0.48
45
0.90
0.84
0.78
0.66
0.56
0.46
14. APPENDIX