Parameter’s table
No
Parameters description
min
max
default UOM
1
Code
Entry code in parameters menu = “22”
0
254
0
2
SP1H
Set Point High in Channel 1
-99
2000
100 °C/mA
3
SP1L
Set Point Low in Channel 1
-99
2000
0
°C/mA
…
…
…
…
…
°C/mA
16
SP8H
Set Point High in Channel 8
-99
2000
100 °C/mA
17
SP8L
Set Point Low in Channel 8
-99
2000
0
°C/mA
18
IN1L
4 mA in Channel 1 corresponds to an indication on screen (see Specification 1)
-99
2000
0
19
IN1H
20 mA in Channel 1 corresponds to an indication on screen (see Specification 1)
-99
2000
2000
…
…
…
…
…
32
IN8L
4 mA in Channel 8 corresponds to an indication on screen (see Specification 1)
-99
2000
0
33
IN8H
20 mA in Channel 8 corresponds to an indication on screen (see Specification 1)
-99
2000
2000
34
Tisc
Time for automated refreshing of temperature indications on screen
1
150
6
sec
35
DF1H
Set Point High differential in Channel 1
1
150
2
36
DF1L
Set Point Low differential in Channel 1
1
150
2
…
…
…
…
…
49
DF8H
Set Point High differential in Channel 8
1
150
2
50
DF8L
Set Point Low differential in Channel 8
1
150
2
51
0AJ1
Zero adjustment of temperature sensor in Channel 1
-50
+50
0
°C
…
…
…
…
…
58
0AJ8
Zero adjustment of temperature sensor in Channel 8
-50
+50
0
°C
59
SCh1
Activation/deactivation of Channel 1 with values (-1÷2): “-1” = channel deactivated, “0” =
channel activated and does not belong to any average group, “1” = channel activated and
belongs to average group No.1, “2” = channel activated and belongs to average group No.2
-1
2
1
…
…
…
66
SCh8
Activation/deactivation of Channel 8
with values (-1÷2): “-1” = channel deactivated, “0” =
channel activated and does not belong to any average group, “1” = channel activated and
belongs to average group No.1, “2” = channel activated and belongs to average group No.2
-1
2
1
67
AS1H
Average Set Point High in Channel 1
-99
100
50
°C/mA
68
AS1L
Average Set Point Low in Channel 1
-99
100
-50
°C/mA
…
…
…
…
…
°C/mA
81
AS8H
Average Set Point High in Channel 8
-99
100
50
°C/mA
82
AS8L
Average Set Point Low in Channel 8
-99
100
-50
°C/mA
83
Ti1H
Time-delay of Set Point High Alarm in Channel 1
0
200
0
sec
84
Ti1L
Time-delay of Set Point Low Alarm in Channel 1
0
200
0
sec
…
…
…
…
…
sec
97
Ti8H
Time-delay of Set Point High Alarm in Channel 8
0
200
0
sec
98
Ti8L
Time-delay of Set Point Low Alarm in Channel 8
0
200
0
sec
99
Tia1
Time-delay of Average Set Points High (AS1H) and Low (AS1L ) Alarms in Channel 1
0
200
0
sec
…
…
…
…
…
sec
106
Tia8
Time-delay of Average Set Points High (AS8H) and Low (AS8L) Alarms in Channel 8
0
200
0
sec
107
OOF1
Drive the failure line alarm (OV F, WRC) of Channel 1 to one of the 11 outputs
0
200
0
sec
…
…
…
…
…
…
…
114
OOF8
Drive the failure line alarm (OV F, WRC) of Channel 8 to one of the 11 outputs
0
200
0
sec
115
OS1H
Drive the Set Point High command in Channel 1 to an output
1
11
0
116
OS1L
Drive the Set Point Low command in Channel 1 to an output
1
11
0
…
…
…
…
…
129
OS8H
Drive the Set Point High command in Channel 8 to an output
1
11
0
130
OS8L
Drive the Set Point Low command in Channel 8 to an output
1
11
0
131
OA1H
Drive the Average Set Point High command in Channel 1 to an output
1
11
0
132
OA1L
Drive the Average Set Point Low command in Channel 1 to an output
1
11
0
…
…
…
…
…
145
OA8H
Drive the Average Set Point High command in Channel 8 to an output
1
11
0
146
OA8L
Drive the Average Set Point Low command in Channel 8 to an output
1
11
0
147
OLE1
Drive the LED of Channel 1 to an output
1
11
1
…
…
…
…
…
154
OLE8
Drive the LED of Channel 8 to an output
1
11
8
155
HC1H
Invert Set Point High command in Channel 1 to (Hot) or (Cool)
HoT / Col
CoL
156
HC1L
Invert Set Point Low command in Channel 1 to (Hot) or (Cool)
HoT / Col
HoT
…
…
…
HoT / Col
169
HC8H
Invert Set Point High command in Channel 8 to (Hot) or (Cool)
HoT / Col
CoL
170
HC8L
Invert Set Point Low command in Channel 8 to (Hot) or (Cool)
HoT / Col
HoT
171
MoSP
Set Points alarms (SP1H/SP1L÷SP8H/SP8L) can function either as alarm (OFF) or as limit
supervisor (ON)
ON / OFF ON
172
OFWC
Over Flow and Wrong Connection alarms activate (ON) or do not activate (OFF) the internal
general relay alarm
ON / OFF ON
173
rP2H
Not in use
174
rP2L
Not in use
…
…
…
185
rP8H
Not in use
186
rP8L
Not in use
187
rEPE
Not in use
188
V-AD
Device’s address on monitoring network
0
98
0
189
ChM1
Input signal type in Channel 1, values: ”1” for J sensor, “2” for K sensor, “3” for PT100 sensor
with 3 cables, “4” for ΡΤ100 sensor with 2 cables, “5” for 4÷20 mA and “6” for 0÷20 mA
1
5
1
…
…
…
…
…
196
ChM8
Input signal type in Channel 8, values: ”1” for J sensor, “2” for K sensor, “3” for PT100 sensor
with 3 cables, “4” for ΡΤ100 sensor with 2 cables, “5” for 4÷20 mA and “6” for 0÷20 mA
1
5
1
3