Capability of inverting Set Point commands. For example, in channel No.1, the parameter SP1L (Set Point 1 Low) corresponds to 
parameter HC1L (Heating Cooling 1 Low). If we set HC1L to Col, the command is executed over the Set Point. If we set HC1L to      

Hot, the command is executed below the Set Point. For example, in High and High-High surveillance, the parameters are set as      
follows: HC1H = Col and HC1L = Col

5.

 

The screen depicts 4 temperature channels at the same time. It refreshes automatically to the next set of temperatures and the 
two average group temperatures. The refreshing time can be set from the parameter Tisc. By pressing [SET] we manually change 
the indication. 

6.

 

When an alarm appears, the temperature indication of the channel with the alarm starts flashing on screen, while the corresponding 
channel group freezes on screen. Each incoming alarm is recorded and numbered according to the alarm sequence into a table. Up 
to 30 alarms are recorded, with the new incoming alarm being placed to the 30

th

 position and the 1

st

 being lost. By pressing [ ] and 

[SET] the alarm table appears on screen. To clean the whole table, we press at the same time [ ] and [SET]. The temperature 
indications appear on screen by pressing [SET].  

7.

 

There are up to 32 alarms where each channel has 4, two Set Point alarms (HIGH, LOW) and two average alarms (HIGH, LOW). 
When a channel does not belong to any group, the two average alarms are automatically deactivated.  

8.

 

Each alarm is driven to an output (1÷11) by adjusting the proper parameter. The outputs of Set Point alarms are adjusted from 

parameters  (OS1H/OS1L÷OS8H/OS8L),  while  the  outputs  of  average  alarms  are  adjusted  from  parameters   
(OA1H/OA1L÷ΟΑ8Η/ΟΑ8L)
.  Alarms  can  be  driven  to  outputs  independently  or  in  groups.  If  we  set  “0”,  the  alarm  doesn’t 
correspond to any output and if we set from “1÷11”, the alarm corresponds to the selected output. 

9.

 

Each  channel  has  one  LED,  in  a  total  of  8  LEDs.  A  LED  starts  flashing  when  an  alarm  appears  and  remains  ON  until  it  is 
recognized by [RESET]. If the cause of the alarm remains after the RESET, the LED remains steadily ON and turns off when the 

cause disappears. 

10.

 

Each LED can be driven to an output (1÷11) for monitoring. This adjustment is set from parameters (OLE1÷OLE8). If we set “0”, 
the LED will not correspond to any output while if we set from “1÷11”, the LED of the respective channel is driven to the selected 

output. 

11.

 

General  internal  relay  alarm  (250VAC,  10  A  resistive  loads).  When  one  or  more  of  the  32  alarms  appear,  the  general  relay  is 
activated. If the parameter No.172 OFWC is set to OFF, the OVER FLOW and WRONG CONNECTION alarms do not activate the 

general relay. 

12.

 

Internal relay with one associated auxiliary contact 250VAC 10A for setting up an external alarm circuit in case of  main power 

supply failure. 

13. 

Detection of cutline or short circuit line in the temperature sensors or 4÷20 mA, 0÷20 mA (sensor failure) in each channel.   

 

 

 

 

Button’s function   

 

 

 

 

                Managing the parameters 

 

By pressing [ENTER] we enter the parameter’s menu and 
the first parameter is displayed, Code. In order to access 

the  parameters,  we  have  to  set  the  parameter  Code  to 
22”. 

 
By  pressing  [SET]  the  arrow  flashes  next  to  the 
parameter’s value and with the arrows [ ], [ ] we can 

modify its value.  
 
By  pressing  [ENTER]  we  confirm  the  new  value  and 

the arrow flashes next to the parameter’s name. 
By pressing [SET] we cancel the new value and return 

to  the  parameter’s  indication  while  the  arrow  flashes 
next to the parameter’s name. 
 
With  the  arrows  [   ],

 

[ ]  we  scroll  into  the  parameters 

with the order they appear in the parameter’s table.  

 
By pressing [ENTER] we exit parameters menu. 
 

 

 
 
 

 
 
 

 
 

 

 

 

 button  function 

ΕΝΤΕR 

- access parameters menu 
- confirm the new value of a parameter 

 

 
 
  SET 

1. cancel the new value of a parameter 

2. while programming parameters: 
By pressing once, an arrow starts flashing next to the parameter  
value and its value can be modified with the arrows 

By pressing again, the arrow starts flashing next to the parameter 
name and we can scroll into the parameters with the arrows 
3. when not programming parameters: 

- displays the next group of temperatures/mA 
- when the alarms appear on screen, by pressing SET we change  

  the indication to the set of temperatures/mA 

 

- inside parameters menu, we can scroll through the parameters  
  or change their values 

- outside parameters menu, functions as TEST LAMP 

 

-  inside parameters menu, we can scroll through the parameters  
  or change their values 
- outside parameters menu, functions as alarm RESET 

 

clears the alarms table (does not reset alarms) 

 

the alarm table appears on screen   

Содержание ALAN-8

Страница 1: ...ach channel 19 Capability to drive each of the 32 alarms to the outputs 1 11 independently or in groups 20 8 LEDs one for each channel 21 Capability to drive the LED operation to the outputs for monitoring 22 One general internal relay output 250VAC 10A for siren activation 23 Time delay for each of the 32 alarms NOTE Time delay for the Average Set Point High and Low alarms is common to each chann...

Страница 2: ...11 for monitoring This adjustment is set from parameters OLE1 OLE8 If we set 0 the LED will not correspond to any output while if we set from 1 11 the LED of the respective channel is driven to the selected output 11 General internal relay alarm 250VAC 10 A resistive loads When one or more of the 32 alarms appear the general relay is activated If the parameter No 172 OFWC is set to OFF the OVER FL...

Страница 3: ...Channel 8 0 200 0 sec 98 Ti8L Time delay of Set Point Low Alarm in Channel 8 0 200 0 sec 99 Tia1 Time delay of Average Set Points High AS1H and Low AS1L Alarms in Channel 1 0 200 0 sec sec 106 Tia8 Time delay of Average Set Points High AS8H and Low AS8L Alarms in Channel 8 0 200 0 sec 107 OOF1 Drive the failure line alarm OV F WRC of Channel 1 to one of the 11 outputs 0 200 0 sec 114 OOF8 Drive th...

Страница 4: ...ads Internal relay with one associated auxiliary contact 250VAC 10A for setting up an external alarm circuit in case of main power failure Accuracy 1 1 digit LCD screen 2x16 characters Operating temperature 15 70 C Storage temperature 20 80 C The devise is mounted on a panel hole with dimension 137x137mm Connection with plug in screw terminals IP protection rating IP42 front side To be installed i...

Страница 5: ... parameters 4 0 20mA a cutline the general relay is activated the corresponding input s LED is flashing and the screen displays OV F b short circuit line short circuit alarm corresponds to 0mA and the reception of the alarm can be adjusted by the parameters Power failure setup An internal relay 250VAC 10A with one contact terminal blocks 34 35 is available to set up an external alarm circuit in ca...

Отзывы: