background image

6

8. GAS PIPING 

All gas piping must be done in accordance with all
applicable codes CAN./CGA-BI49.1 or .2
installation codes or ANSI -Z223.1 as well as local
codes. 

The appliance and its individual shutoff valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 psig (3.5 kPa). 

The appliance must be isolated from the gas supply
piping system by closing its individual manual
shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig (3.5 kPa).

The gas line to the fireplace insert should be of
adequate size to minimize the pressure drop and
should never be smaller than that supplied with the
valve. A ground joint union should be used as close
to the valve as possible to facilitate removal of the
gas valve and burner base pan. 

Check that the gas piping is not supported by the
gas valve. A manual shut-off valve should be
installed in the gas line, inside the fireplace. All
piping joints must be tight and an approved non-
hardening sealing compound shall be used ( one
which is suitable for future service). 

For the state of Massachusetts a 

T-handle gas shut-off valve

must be used on a gas appliance.  This T-handle gas shut-off
valve must be listed and approved by the state of
Massachusetts.  This is in reference to the state of
Massachusetts state code CMR238.

CAUTION: Never use a flame to check for 

leaks - use an approved leak test solution. 

9. VENTING 

Before any vent liner is run through a masonry
chimney or other approved venting system the

chimney must be inspected. cleaned and 
rep aired 

if necessary . A chimney which was used

for a solid fuel fireplace must be professionally
cleaned in order to reduce corrosion of the vent and
other possible safety hazards. 

VENT LENGTH (4” Diameter Vent) 

Vertical (rise)

Horizontal (run)

Min  l0 ft - 3.1m 

0 ft -  0.0 m 

Max  50 ft - 16.2 m

2 ft - 0.6 m 

This fireplace insert is approved for use with a 
4” inch diameter. 

All venting lining products must be approved and
installed according to the vent manufactures
installation instructions. All vent liners must
terminate in a rain cap to prevent debris and rain
from entering the vent and possibly damaging the
appliance or creating an unsafe condition. The area
between the existing chimney and liner must be
capped off for the same reasons as above and to
reduce the chances of venting problems and
corrosion of the vent. 

This heater must be properly connected to a 

venting system. This heater is equipped with 

a vent safety spill switch shutoff system. 

WARNING 

Operation of this heater when not connected to a

properly installed and maintained venting 

system or tampering with the vent safety spill

switch shutoff system can result in carbon

monoxide (CO) poisoning and possible death. 

It is strongly recommended that the area between
the damper and the liner be blocked to prevent the
possibility of flue products entering the area
between the chimney and the vent liner. 

If this fireplace insert is to be used to replace an
existing fireplace insert the existing vent liner must
be of the proper size and if so it must be inspected
for obstructions, damage and/or corrosion.
Replacement must be done as necessary . 

NOTE: Follow vent manufacturer’s 

installation instructions. 

Содержание VFI25LP

Страница 1: ...anual Installation and service must be performed by a qualified installer service agency or the gas supplier Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this...

Страница 2: ...wn between each Be aware during log and firebox paint curing that a white deposit may be developing on the inside of the glass doors It is important to remove this white deposit from the glass doors w...

Страница 3: ...0 11 Field Conversion for C30GEK 11 12 Combustion Air Unit Operation Checkout 12 14 Unit Adjustment 13 15 Maintenance 14 16 Surround and Brass Trim Assembly Instructions and Parts List 15 17 Surround...

Страница 4: ...variable gas input 3 HEAT OUTPUT It must be remembered that both the units in this manual produce significant amounts of heat within a varying input range VFI25N NATURAL GAS 0 4500ft Output BTU HR In...

Страница 5: ...the front of the unit to a combustible floor is 0 15 metres 6 inches Clearance from adjacent side wall is 7 inches from side of unit Minimum clearances from the top of the grill to a mantel and maxim...

Страница 6: ...imney or other approved venting system the chimney must be inspected cleaned and rep aired if necessary A chimney which was used for a solid fuel fireplace must be professionally cleaned in order to r...

Страница 7: ...in place 19 is required 6 If the lintel is wider than 12 305mm then the height of the solid fuel fireplace must be at least 25 63 5 cm to allow for an offset elbow See Figure 2 If providing an offset...

Страница 8: ...solid fuel fireplace Make sure that the fireplace is completely cool and has not been used for a few days 7 Make sure that the solid fuel fireplace base is level and if not make any necessary adjustm...

Страница 9: ...and pull forward to the grate bars Place log 2 on rear log holder and center it Step 3 Place Log 3 onto the notched areas as shown Place Log 4 onto the notched areas as shown Refer to step 2 for notch...

Страница 10: ...to step 2 for Log 5 notch locations Fill the exposed areas of the ember plates and front burner tube with ember rocks Do not place ember rocks on rear burner tube Step 4 Place lava rock around the sid...

Страница 11: ...rill 1 8 Drill Bit 1 4 Nut Driver Bit Step 1 Remove existing grate bar by bending bar slightly forward and drill out rivets Step 2 Seal rivet holes with two supplied screws ZDV6000 ONLY Step 3 Center...

Страница 12: ...not be allowed to contact glass and unit should be allowed to run for a minimum of 10 minutes area of sensing tube will become quite hot A minimum draft pressure of 02 inches of water column is requi...

Страница 13: ...left of the valve E Inlet Pressure and A Manifold Pressure and connecting a manometer Pressure ranges are as listed below Gas Supply Pressure inches w c Min Normal Max Natural Gas 4 5 7 0 9 0 L P pro...

Страница 14: ...ple is necessary replace from top and bottom of firebox bottom Reference lower diagram Page 18 c Logs CAUTION The logs can stay hot for several hours after the fireplace is shut off Serious burns coul...

Страница 15: ...placement For valve replacement it is recommended that the burner assembly be removed this is done by removing two 1 4 hex screws on the left and right side of the firebox and lifting the complete bur...

Страница 16: ...ure all panels All brass trims D E and F are installed with 5 16 x 6 32 self tapping screws attach part D E and F to outer edge of surround Than place On Off switch into slot upper right corner after...

Страница 17: ...Brass Trim Top 1 E 3000 305 3000 315 3000 330 Brass Trim Left 1 F 3000 306 3000 316 3000 329 Brass Trim Right 1 G 3000 307 3000 317 3000 324 Brass Panel Top 1 Gl n a n a 3000 327 Brass Panel Bottom 1...

Страница 18: ...ITCH Wiring Diagram SIT 820 639 and 820 640 True Millivolt Systems This System does not have a thermocouple For units with serial number greater than 13930 see 820639 820640 systems Wiring diagram wit...

Страница 19: ...Kit Antique Brass V25T2129C Trim Kit Chrome V25T2129P Trim Kit Polish Brass Size 21 High x 29 Wide V25S2738B Surround Kit Large Flat Black V25T2738A Trim Kit Antique Brass V25T2738C Trim Kit Chrome V...

Страница 20: ...ts are not available for Deluxe Surrounds V25ADDX Arch Door Frame Deluxe Black 352 V25ADTH Arch Door Frame Top Half Black 353T V25ADDA Arch Door Frame Double Arch Black 354 V25ADDD Arch Door Frame Dou...

Страница 21: ...P136WR Thermopile GOAI 524 1001 P069SI Electrode Sparker 915 069 TC SIT 1001 P216SI Thermocouple 290 216 TC SIT 1001 P165SI Orifice Pilot NG 977 165 TC SIT 1001 P167SI Orifice Pilot LP 977 167 TC SIT...

Страница 22: ...Hood Assembly 2000 079 Gasket for Flue 2500 BNGSI Burner Assy c w Valve Natural Gas 2500 BLPSI Burner Assy c w Valve Liquid Propane 3000 930 Spill Safety Switch 36T21 3000 940 Glass Robax 23 22 x 11 7...

Страница 23: ...ot screw to provide proper sized flame Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire Size Max Length 14 GA 100 FT 16 GA 64 FT 18 GA 40 FT 20 GA 25 FT 22 GA 16 F...

Страница 24: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: