TROUBLESHOOTING Cont.

5.

Pilot flame not touching thermocouple, which allows

5.

Contact local gas company.

thermocouple to cool, causing pilot flame to go out.
Problem could be caused by one or both of the following:
A) Low gas pressure
B) Dirty or partially clogged ODS/pilot.

6.

Thermocouple damaged.

6.

Replace thermocouple

7.

Control valve damaged.

7.

Replace control valve.

One or both burners do not light after ODS/pilot is lit.

Possible Cause

Remedy

1.

Burner orifice is clogged.

1.

Clean burner or replace light burner orifice.

2.

Inlet pressure is too low.

2.

Contact qualified service person.

Delayed ignition of burner.

Possible Cause

Remedy

1.

Manifold pressure is too low.

1.

Contact local gas company.

2.

Burner orifice is clogged.

2.

Clean burner or replace burner orifice.

Burner backfiring during combustion.

Possible Cause

Remedy

1.

Burner orifice is clogged or damaged.

1.

Clean burner or replace burner orifice.

2.

Burner is damaged.

2.

Replace burner.

3.

Gas regulator is defective.

3.

Replace Gas regulator.

Slight smoke or odor during initial operation.

Possible Cause

Remedy

1.

Vapors from paint or curing process of logs.

1.

Problem will stop after a few hours of operation. Run 
the heater with the damper open if you have one or open
a window for the first few hours.

Log appears to smoke (after initial operation).

Possible Cause

Remedy

1.

Log heater is intended to be smokeless. Turn off heater 
and call qualified service person.

Heater produces a whistling noise when burner is lit.

Possible Cause

Remedy

1.

Turning control knob to HI position when burner is cold. 1.

Turn control knob to LO position and let warm up for a
minute

2.

Air in gas line.

2.

Operate burner until air is removed from line. Have gas
line checked by local gas company.

3.

Dirty or partially clogged burner orifice.

3.

Clean burner or replace burner orifice.

No Gas to pilot.

Possible Cause

Remedy

1.

LP regulator shut down due to inlet pressure being

1.

Verify LP tank regulator is installed and set at 11 to 13

too high

inches w.c.

2.

Replace LP regulator on heater.

Содержание FVF300

Страница 1: ...ation and service must be performed by a quali ed installer service agency or the gas supplier Warning Improper installation adjustment alteration service or maintenance can cause injury or property d...

Страница 2: ...2...

Страница 3: ...ctory However due to the high temperature silicone components the paint will cure when heat is applied to the appliance as it is rst used The following information applies to the curing process to get...

Страница 4: ...Air Flow for Firebox Location 9 Ventilation Air From Inside Building 10 Ventilation Air From Outdoors 11 Installing 12 Installation Clearances 12 Installing Gas Line 14 Installing Burner Systems into...

Страница 5: ...FVF300 Free Standing Cast Stove as above Black FVF300AL Free Standing Cast Stove as above Porcelain Almond FVF300BL Free Standing Cast Stove as above Porcelain Black FVF300 GR Free Standing Cast Stov...

Страница 6: ...ther material on top of logs or logs into ame 5 Always operate appliance with front replace screens closed 6 Make sure any safety screen or guard removed for servicing is in place before running appli...

Страница 7: ...ervised when they are in the same room with the appliance 27 Must be installed by a licenced gas tter in the Commonwealth of Massachusetts Complies to code 527CMR LOCAL CODES Install and use replace w...

Страница 8: ...atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 per pasec m2 or less with openings gasketed or sealed and b weather stripping has been added on openable windows...

Страница 9: ...ors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used __________________ Btu Hr maximum the space can support __________________ Btu Hr...

Страница 10: ...he oor on the wall connecting the two spaces You can also remove door into adjoining room Follow the National Fuel Gas Code NFPA 54 ANSIZ223 1 Section 5 3 Air for Combustion and Ventilation for requir...

Страница 11: ...the power vent FIGURE 6 Ventilation Air from Outdoors Vertical Venting in Cold Climates In cold climate conditions where temperatures go below 10 degrees Celsius or 14 degrees Fahrenheit we recommend...

Страница 12: ...r wall should not be less than 3 inches C Clearance from the side of unit in corner 45 degree installation is 3 inches D Clearance from top of stove is 41 inches NOTICE A quali ed service person must...

Страница 13: ...ing Commissioner before installing this appliance otherwise your insurance company may not cover this appliance DANGER CARBON MONOXIDE POISONING MAY LEAD TO DEATH WARNING Any changes to this heater or...

Страница 14: ...burner pressure is controlled by the regulator Check pressure at the pressure test point which is located on the side of the gas control near the pilot outlet Make sure that the pressure tap is compl...

Страница 15: ...ot use cleaning uids to clean logs or any part of the heater Use a soft bristle brush or a vacuum with brush attachment Vacuum loose particles and dust from burner ports valve and blower compartments...

Страница 16: ...ructions in manual 7 Once the gas line is connected the piezo wire can be attached This is done by locating the single wire lead from the pilot system and attaching it to the piezo ignitor For the on...

Страница 17: ...with the stove Fig 3 Log A has 2 locating holes Position the 2 holes on the log over the 2 pins on the left side of the log mounting pan as shown in the picture Fig 4 Log B has 2 locating holes Posit...

Страница 18: ...ensure that the wall switch is in the ON position NOTE For Millivolt models the ON OFF wall switch may be replaced with a wall thermostat allowing main burner to light and turn off automatically depen...

Страница 19: ...e proceeding 5 Turn the stove on Once the sensor unit reaches operating temperature in approximately 10 to 15 minutes the fan will turn on The fan can be switched off if desired by turning the switch...

Страница 20: ...asher 7 4000 208 Mixing Sleeve 8 Air Shutter 9 350VF 200 Burner Assembly 10 350 520 Burner Retainer 11 350 520 R Burner Retainer 12 350 221 Burner Mount 13 350 221R Burner Mount 14 4000 P963VE 375 x 3...

Страница 21: ...ifice 3 1000 253 750 x125 Nipple 4 2000 213 Elbo90 125 5 27FP P90F44 125x375 Flare 6 1 x 437 IN washer 7 33VF P8404 ODS LP 7 33VF P8214 ODS NG 8 350 P3875D 375 x 8 Flex 9 33VF P316VE Air Tubing 10 33V...

Страница 22: ...FF position Possible Cause Remedy 1 Gas leak 1 Locate and correct all leaks 2 Control valve defective 2 Replace control valve When ignitor button is pressed there is a spark at ODS pilot but no igniti...

Страница 23: ...er is damaged 2 Replace burner 3 Gas regulator is defective 3 Replace Gas regulator Slight smoke or odor during initial operation Possible Cause Remedy 1 Vapors from paint or curing process of logs 1...

Страница 24: ...th service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoe...

Отзывы: