ZCV3622 / ZCVRB3622 Framing Dimensions and Clearances
-With Factory Installed Flue Restrictor-
NOTE:
Units above the following Serial Numbers will have the Flue Restrictor:
ZCV3622 #2016 / ZCVRB3622- #10674
Determine whether face of fireplace will be:
Flush with finished wall (e.g., for surround, cultured stone or other non combustible covering).
Flush with framing (to be covered with concrete board for a Flat Wall appearance).
Refer to Nailing Tab Guide section also.
Clearance to Combustibles ZCV3622 / ZCVRB3622
Front
36” [92cm]
Back (from Stand-offs)
0” [0cm]
Side (from Stand-offs)
0” [0cm]
Floor
*
0” [0cm]
Minimum Ceiling Height (from bottom of
fireplace)
60”
Top (from Stand-offs)
0” [0cm]
Top of 90° Bend in minimum Enclosure
of 60”
2-1/2” [6.35cm]
VENTING SYSTEMS
Top of Horizontal Pipe
1/1/2” [3.8cm]
Side & Bottom of Horizontal Pipe
1” [2.5cm] All Vent
Systems
Vertical Vent Pipe
1” [2.5cm] All Vent
Systems
Framing for Horizontal
Vent Termination
(See
Installation of
Side Wall Venting
Section)
These structures are not load bearing.
NOTE:
See
Nailing Tab Guide
section also.
54” MIN for NG
54” MIN for LP
Plus Rise of 1/4”
Per Foot*
RIGHT SIDE
This area can be recessed
up to 3” from Face of Unit
for a TV Recess.
*Note: If appliance is installed directly on carpeting or other
combustible material other than wood flooring, a metal or
wood panel extending the full width and depth of the
appliance must be used. Carpet may extend 1 inch above the
floor of the appliance.
Support
Straps
CORNER
FRAMING
14
Содержание ZCV3622LP
Страница 28: ...Optional Log 4 in raised position LOG 4 28...
Страница 45: ...Gas Conversion for Modulator PART C 45...
Страница 51: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 51...
Страница 52: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 52...
Страница 59: ...Proflame 2 Remote Control 59...
Страница 61: ...61...