9 - AUTOMATIC GATE TRAVEL LEARNING

Before the Automatic Learning!

- In this process  the controller “learns” the gate’s travel time and automatically sets the default 

slowdown points

- During the Automatic Learning  safety devices are disabled! Keep the gate travel area clear 

to prevent any damage that may be caused by crushing into an object, vehicle, person, animals...

- Ensure that the mechanical and or electrical limit switches are in-place and operating

 

- To stop this programming mode at any time press the SET and RADIO 

 

buttons simultaneously.

- For systems with single motor, use MOT1 (terminal 24 and 25) and adjust

the DELAY potentiometer to (-) minimum 

- For double (twin) wings, connect the motor that opens first to MOT1 (terminal  24 and 25)

- To changing the default slowdown points – see section 10

Automatic Gate Travel  Learning procedure

1) Make sure that DipSwitch 2 is ON and DipSwitch 3 is OFF- step-by-step mode

2) Engage (Open) the manual override lever and move the wings to half way, 

then disengage (close) the manual override 

 

3) Press and hold the SET button for 2 seconds 

 

- the yellow SET LED flashes

4) Immediately press the Set button again for 2 sec - gate start opening , SET LED remain 

on till the end of learning

5) If the wing(s) begin moving to closing, stop the Automatic Learning process 

(press the SET and RADIO simultaneously) and reveres (swap) the motor(s) wires.

Automatic Gate Travel  Learning done

Advanced Programming

10 - CHANGING THE FACTORY SLOWDOWN POINTS

1) The Automatic Gate Travel Learning should be done first, the default slow down points are set at 15% of full travel 

2) You may remove, or set new slowdown points 

3) For new slowdown points, mark the points on the driveway 

4) Make sure that the operation mode is Step By Step (DipSwitch 2 ON / 3 OFF) 

5) Move the wings to half way position 

6) Press the 

SET

 button for 2 seconds  

 

>> the 

SET LED

 flashes for 5 seconds  

7) Press the 

RADIO

 button for 1 second  

 

>> the 

SET LED

 turns steady on and gate starts moving 

8) The gate begins to open slowly, then the wings will close one after the other until fully closed 

9) Press the 

SET

 button, or the remote control  

>> wings begin to open 

To remove the slowdown points in opening let the wings open all the way; Or, for new slowdown point(s): 

 

When wing 1 arrives to the new slowdown point >> press the 

SET

 button, or button 1 of the remote control 

 

When wing 2 arrives to the new slowdown point >> press the 

RADIO

  button, or button 

2

 of the remote control  

10) Press the 

SET

 button or the remote control  

 

>> wings begins closing 

To remove slowdown points in closing let the wings to go the way; 

Or, for new slowdown point(s)

 

When wing 1 arrives to the slowdown point >> press the 

SET

 button, or button 1 of the remote control 

 

When wing 2 arrives to the slowdown point >> press the 

RADIO

 button, or button 2 of the remote control  

 

ADVANCE FEATURES

14 - SAFETY DEVICES DETAILED DESCRIPTION 

Crossing safety receivers

& transmitters 

PHO1- SAFETY DEVICES IN CLOSING

Input PHO1 (terminal 16 and 18) is used for connecting photo-sensors as safety devices to intervene during closing.

PHO2: SAFETY DEVICES IN OPENING AND CLOSING

Input PHO2 (terminals 16 and 17) intervene both in closing and in opening

There are two options determined by DipSwitch 

4

:

DipSwitch 

4 ON

:  if trigged by safety device   >> gate stops and when path is cleared keeps going 

DipSwitch 

4 OFF

: (for Safety Edge in Opening): 

Trigged in opening  

 

>> stops and closes for 2 seconds

 Trigged in closing  

 

>> no effect 

NOTE:

If more than one pair of photo-sensors is used, it is 

recommended to have the position of the transmitters 

and receivers alternated between the pair,

in order to avoid cross triggering.

SAFETY AUTO TEST

The Auto safety test is recommended in Europe. The control unit has a Safety Device Test mode  

to check the operation of the devices connected to inputs PHO1 (terminals)

and PHO2 (terminals).

ENTER THE SAFETY DEVICE TEST:

1) First connect the Photo-sensor’s +VE end to the TX input (terminal 20) instead of the VA input (terminal 19), 

for which it should be connected during normal operation.

2) Press the 

RADIO

 button for 2 sec 

>> RADIO-LED Red turns on

3) Press the 

SET

 button 4 times 

 

>> SET LED Yellow turns on

4) Wait 10 seconds 

 

 

>> SET LED and RADIO LED both turn off

 

 

 

 

 

Safety Auto Test is now activated

EXIT THE SAFETY AUTO TEST MODE

 (if error LED on press the SET button, and wait unit the SET LED turns off) then:

1) Press the 

RADIO

 button for 2 seconds 

>>SET LED and red RADIO LED both turn on

2) Press the 

START

 button once   

>> SET LED turns off

3) Wait 10 seconds 

 

 

>> RADIO LED turns off

 

 

 

 

 

Safety Auto Test is now deactivated

NOTE:

 Entering the test with the safety devices not properly connected will cause the unit to malfunction.

To determine whether the unit is in the test mode press the RADIO button for 3 seconds: if the RADIO LED turns on 

then the self-test is disabled. If both the red RADIO led and the yellow SET led turn on then the test is active.

12 - RESET THE PEDESTRIAN OPENING GAP TO DEFAULT SETTING 

1) Make sure that the  gate is in the closed position 

2) Press the 

SET

 button for 2 seconds 

>> 

SET LED

 begins to flash 

3) Press the 

START 

button  

 

>> 

SET LED

 turns steady on  

4) Press the 

SET

 button   

 

>> 

SET LED

 flashes rapidly and turns off 

 

 

 

 

 

Pedestrian opening gap reset 

 

13 - DELETING PEDESTRIAN ACCESS BY REMOTE CONTROL

1) Make sure that the  gate is in the closed position 

2) Press the 

SET

 button for 2 seconds 

>> 

SET LED

 begins to flash 

3) Press the 

START 

button  

 

>> 

SET LED

 turns steady on  

4) Press the 

SET

 button   

 

>> 

SET LED

 flashes rapidly and turns off 

 

 

Pedestrian access by remote control deleted 

(push button command terminal 15 still active) 

 

11 - ADJUSTING THE PEDESTRIAN ACCESS OPENING GAP

1) Make sure that the remote control(s) is programmed for pedestrian  access opening (DipSwitch 8 OFF)  

2) Make sure that the  gate is in the closed position 

3) Press the 

SET

 button for 2 seconds 

 

>> 

SET LED

 begins to flash 

4) Press the 

START

 button  

 

 

>> 

SET LED

 turns steady on 

5) Press the 

START

 or remote or push button 

>> 

Wing 1

 begins to open 

6)  When wing 1 arrives at the desired opening point -  stop it by pressing 

START

, remote , or push button 

 

 

 

 

 

 

The new Pedestrian opening gap is set 

 

RX 

TX 

TX 

RX 

Содержание Star 224

Страница 1: ...Jet motors Modus motors KINGgates srl Via A Malignani 42 33077 Sacile PN ITALY Tel 39 0434 737082 Fax 39 0434 783382 web www king gates com Email info king gates com Allegro Gate Automation Pty Ltd U2...

Страница 2: ...r liquids cannot enter the control box Before connecting the control box to the mains power 1 Verify that all wirings done as described in section 2 above 2 Ensure that the gate can move freely throug...

Страница 3: ...ables that are at least 0 5mm2 for distance 30 100meter Do not connect cables in underground boxes or inside conduits POWER SUPPLY N 24O VAC L 19 18 18 16 19 18 RX TX NC NO C MOTOR 1 MOTOR 2 21 22 23...

Страница 4: ...ition before automatically closing for auto closing modes only The delay range is 1 to 90 seconds Remember let the cycle finish before readjusting DELAY between the wings in opening and closing This p...

Страница 5: ...OTE CONTROLS FROM THE CONTROL BOX 1 Press the RADIO button for 4 seconds and release the RADIO LED starts flashing 2 While it flashes press the RADIO button again until the RADIO LED flashing rapidly...

Страница 6: ...set at 15 of full travel 2 You may remove or set new slowdown points 3 For new slowdown points mark the points on the driveway 4 Make sure that the operation mode is Step By Step DipSwitch 2 ON 3 OFF...

Страница 7: ...Press the SET button 4 times SET LED Yellow turns on 4 Wait 10 seconds SET LED and RADIO LED both turn off Safety Auto Test is now activated EXIT THE SAFETY AUTO TEST MODE if error LED on press the SE...

Страница 8: ...rd connected to HAZ terminals 10 11 Voltage free dry contact Max 250Vac 500W Time range 0 to 120 Seconds 16 STATUS LED S SET Yellow LED FLASHING for 5 seconds when power is turned on ON during Gate Tr...

Страница 9: ...9 NOTES opening the board case may cancel the warranty for the board 17 INSIDE THE CONTROL UNIT advanced only 12V 2Amp fuse Remotes Memory card Remotes Receiver...

Страница 10: ...operation mode DipSwitches 2 ON DipSwitch 3 OFF Step By Step mode Check that DipSwitch 7 Close after Photo is OFF GATE STOPS HALFWAY AND THEN MOVES IN THE OPPOSITE DIRECTION The obstacle sensitivity...

Страница 11: ...11...

Страница 12: ...King Gates S r l Via A Malignani 42 33077 Sacile PN ITALY Tel 39 0434 737082 Fax 39 0434 783382 e mail info king gates com web www king gates com...

Отзывы: