43
As shown in Fig. 6-23, if the drive’s output frequency is
within the detecting range of preset frequency, a pulse
signal will be output.
Fig.6-23 Frequency arriving signal
A6.20 FDT1 level
0.00
~
300.0Hz
【
50.00Hz
】
A6.21 FDT1 lag
0.00
~
300.0Hz
【
1.00Hz
】
A6.22 FDT2 level
0.00
~
300.0Hz
【
25.00Hz
】
A6.23 FDT2 lag
0.00
~
300.0Hz
【
1.00Hz
】
A6.20
~
A6.21 is a complement to the No.2 function in
Table 6-6. A6.22
~
A6.23 is a complement to the No.3
function in Table 6-6. Their functions are the same.Take
A6.20
~
A6.21 for example:
When the drive’s output frequency reaches a certain
preset frequency (FDT1 level), it outputs an indicating
signal until its output frequency drops below a certain
frequency of FDT1 level (FDT1 level-FDT1 lag), as
shown in Fig. 6-27
Fig.6-27 FDT level
A6.24 Virtual terminal setting 0
~
007FH
【
00h
】
A6.25 Y2 terminal output
0
~
88
【
0
】
0~50
:
Y2 is used as Y terminal output; its function is the
same as Table 6-6.
51~88
:
Y2 function.
Pulse frequency frequency of Y2:0
~
Max pulse output
frequency(Defined in A6.26).
The linear relationship between the displaying range and
the output values of Y2 is shown as Table 6-7.
Table 6-7 Displaying range of Y2 terminal
Setting
Function
Range
51
Output frequency
0
~
Max.
output
frequency
52
Preset frequency
0
~
Max.
output
frequency
53
Preset frequency
(After Acc/Dec)
0
~
Max.
output
frequency
54
Motor speed
0
~
Max. speed
55
Output
current
Iei
0
~
2 times of motor’s
rated current
56
Output
current
Iem
0
~
3 times of motor’s
rated current
57
Output torque
0
~
3 times of motor’s
rated torque
58
Output voltage
0
~
1.2 times of drive’s
rated voltage
60
Bus voltage
0
~
800V