13
Category Terminals Name
Function description
Specification
Common
port
COM
Common port of
24V power
supply
Three common ports in all, cooperate
with other terminals
Relay
output
terminal 1
RA
Relay output
Can be defined as multi-function relay
output terminal(Refer to the A6.16 for
function description)
R1a-R1b
:
Normally closed
,
R1a-R1c
:
normally open
Contact capacity
:
AC250V/2A
(
COSΦ
=
1
)
AC250V/1A
(
COSΦ
=
0.4
)
DC30V/1A
Input voltage of relay output
terminal 's overvoltage class is
overvoltage class II
RB
RC
Arrangement of control circuit terminals is as follows
J606
24V PLC
AI1
AI2
+10V
X1
X2
X3
X4
X5
Y1
AO1 AO2 OP
COM
PE
RA RB RC
Wiring of OP
1
:
When
:
J606
24V PLC
Use in24V power supply
Wirings of multiple function input terminal and operation terminal
AI1
AI2
+10V
X1
X2
X3
X4
X5
Y1
AO1 AO2 OP
COM
PE
RA RB RC
2
:
When
:
J606
24V PLC
Use external power supply
Wirings of multiple function input terminal and operation terminal
AI1
AI2
+10V
X1
X2
X3
X4
X5
Y1
AO1 AO2 OP
COM
PE
RA RB RC
+
-
Wiring of analog input
1
)
AI1, AI2 can be connected to analog voltage or current sigle-ended input. Voltage or current mode can be seleted by
AI1and AI2. The wiring is as follows: