Type
Size
Description
Example
Serial number
8 octets
Class (1 byte)
Range (1 byte)
Year (2 bytes)
Month (1 byte)
Number (3 bytes)
'3' (
0x33
)
'F' (
0x46
)
13 (
0x00
0D
)
8 (
0x08
)
98765 (
0x01
81
CD
)
Format
Byte 2 (range)
Byte1 (class)
Byte 4 (year)
Byte 3
(year)
Byte 6
(number)
Byte 5
(month)
Byte 8
(number)
Byte 7
(number)
0x46
0x33
0x00
0x0D
0xCD
0x08
0x01
0x81
Example with 3F13898765: 0x
01
81
CD
08
00
0D
46
33
Alarms and relays status – Modbus code: 7000
Encoded on 4 octets (U32)
Byte 2
Byte 1
b8 – b15
b7 – b4
b3
b2
b1
b0
Unused
Unused
Unused
Channel 3
Channel 2
Channel 1
Alarm state
*
(*)
1:
the channel is in alarm state
/
0:
the channel is not in alarm state
Byte 4
Byte 3
b31 – b28
b27
b26
b25
b24
b23 – b20
b19
b18
b17
b16
Unused
Relay 4
**
Relay 3
**
Relay 2
**
Relay 1
**
Unused
Unused
Alarm 3
***
Alarm 2
***
Alarm 1
***
(**)
1:
the relay is triggered
/
0:
the relay is not triggered
(***)
1:
the alarm is activated
/
0:
the alarm is deactivated
•
Values
– Modbus code: 7010 (channel 1)
7040 (channel 2)
7070 (channel 3)
•
Number of digits after the decimal point
– Modbus code: 7020 (channel 1)
7050 (channel 2)
7080 (channel 3)
•
Unit
– Modbus code: 7030 (channel 1)
7060 (channel 2)
7090 (channel 3)
List of units:
Field
Unit
Value
None
0
Temperature
°C
16
°F
17
Hygrometry
%HR
32
g/Kg
33
Modbus
7